SUCTION

POCKET

SUCTION

ORBITING SCROLL

STATIONARY SCROLL

SUCTION

SUCTION

DISCHARGE

 POCKET

SUCTION

INTERMEDIATE PRESSURE

GAS

CRESCENT

SHAPED

GAS POCKET

HIGH PRESSURE GAS

FLANKS SEALED

BY CENTRIFUGAL

FORCE

MOVEMENT OF ORBIT

FIGURE 8

C − Outdoor Fan Motor

All units use single−phase PSC fan motors which require a run
capacitor. In all units, the condenser fan is controlled by
the compressor contactor.

ELECTRICAL DATA tables in this manual show specifi-
cations for condenser fans used in XP13’s.

Access to the condenser fan motor on all units is gained
by removing the four screws securing the fan assembly.
See figure 9. The grill fan assembly can be removed from
the cabinet as one piece. See figure 10. The condenser
fan motor is removed from the fan guard by removing the
four nuts found on top of the grill. See figure 10 if con-
denser fan motor replacement is necessary.

Make sure all power is disconnected before
beginning electrical service procedures.

DANGER

FIGURE 9

Remove

screws

Remove

screws

ALIGN FAN HUB FLUSH WITH END OF SHAFT

FIGURE 10

NUTS (4)

D − Reversing Valve L1 and Solenoid

A refrigerant reversing valve with electromechanical so-
lenoid is used to reverse refrigerant flow during unit op-
eration. The reversing valve requires no maintenance. It
is not repairable. If the reversing valve has failed, it must
be replaced.

Содержание Elite XP13018

Страница 1: ...RNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect resulting from Flood wind lightning or installation and opera ti...

Страница 2: ...230V 208 230V 208 230V 3 Maximum overcurrent protection amps 20 30 30 35 35 40 50 60 2 Minimum circuit ampacity 11 9 17 5 18 4 21 6 21 9 23 2 28 9 34 6 Compressor Rated load amps 8 97 13 46 14 1 16 6...

Страница 3: ...1 OUTDOOR FAN COMPRESSOR HIGH PRESSURE SWITCH REVERSING VALVE FILTER DRIER CONTROL BOX EXPANSION VALVE VAPOR LINE SERVICE VALVE LIQUID LINE SERVICE VALVE A Control Box Figure 2 XP13 units are not equi...

Страница 4: ...the TEST position at power up the control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If the jumper is removed befo...

Страница 5: ...TION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls f...

Страница 6: ...oving the four screws securing the fan assembly See figure9 The grill fan assembly can be removed from the cabinet as one piece See figure 10 The condenser fan motor is removed from the fan guard by r...

Страница 7: ...pole single throw high pressure switch is located in the liquid line This switch shuts off the compres sor when liquid line pressure rises above the factory setting The switch is normally closed and i...

Страница 8: ...ON OF REFRIGERANT FLOW SERVICE PORT SUCTION EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD INTERNAL COMPRESSOR LIMIT DISTRIBUTOR INDOOR COIL COIL SENSOR FIGURE...

Страница 9: ...ation and serves as the primary leak seal To Access Schrader Port 1 Remove service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is complete replace service por...

Страница 10: ...only 3 Open the high pressure side of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 k...

Страница 11: ...urn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off th...

Страница 12: ...5 Charge Using the Approach Method Outdoor Temperature 65 F 18 C The following procedure is intended as a general guide and is for use on expansion valve systems only For best results indoor temperatu...

Страница 13: ...0A refriger ant absorb moisture very quickly It is very impor tant that the refrigerant system be kept closed as much as possible DO NOT remove line set caps or service valve stub caps until you are r...

Страница 14: ...the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tables and procedure 3 Belt Drive Blowers Check belt for wear and proper ten sion 4 Check a...

Страница 15: ...Page 15 VIII WIRING DIAGRAM AND SEQUENCE OF OPERATION 5 6 1 2 4 3 3 6...

Страница 16: ...tdoor fan motor B4 are de energized and stop immediately Terminal O is de energized when indoor room thermo stat is out of cooling mode de energizing the reversing valve L1 Heating demand initiates at...

Отзывы: