background image

Page 10

506637−01 11/10

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or
replacement of existing line set. If new or replacement line
set is not being installed then proceed to 

Brazing

Connections 

on page 12.

IMPORTANT

Lennox highly recommends changing line set when
converting the existing system from HCFC−22 to
HFC−410A

.

 If that is not possible and the line set is the

proper size as reference in table 2, use the procedure
outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and
isolate the opening so vibration is not transmitted to the
building. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolated
from building structures (walls, ceilings. floors), the
refrigerant lines will not create unnecessary vibration and
subsequent sounds. See figure 6 for recommended
installation practices. Also, consider the following when
placing and installing a high−efficiency outdoor unit.

Liquid lines that meter the refrigerant, such as RFC1 liquid
lines, must not be used in this application. Existing line set
of proper size as listed in table 2 may be reused. If system
was previously charged with HCFC−22 refrigerant, then
existing line set must be flushed (see 

Flushing Line Set

and Indoor Coil 

on page15).

Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit to the indoor unit coil (braze
connections). Use Lennox L15 (sweat, non−flare) series
line set, or field−fabricated refrigerant line sizes as listed in
table 2.

NOTE  When installing refrigerant lines longer than 50
feet, see the Lennox Refrigerant Piping Design and
Fabrication Guidelines, CORP. 9351−L9, or contact
Lennox Technical Support Product Applications for
assistance.

To obtain the correct information from Lennox, be sure to
communicate the following information:

Model (XC16) and size of unit (e.g. −036).

Line set diameters for the unit being installed as listed
in table 2 and total length of installation.

Number of elbows vertical rise or drop in the piping.

The compressor is charged with sufficient Polyol ester oil
for line set lengths up to 50 feet. Recommend adding oil to
system based on the amount of refrigerant charge in the
system. No need to add oil in system with 20 pounds of
refrigerant or less. For systems over 20 pounds − add one
ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL
ARCTIC 22 CC or ICI EMKARATE

 RL32CF.

IMPORTANT

Mineral oils are not compatible with HFC−410A

.

 If oil

must be added, it must be a Polyol Ester oil.

Table 2. Refrigerant Line Set  Inches (mm)

Model

Field Connections

Recommended Line Set

Liquid Line

Suction Line

Liquid Line

Suction Line

L15 Line Set

XC16−024−230

3/8" (10 mm)

3/4" (19 mm)

3/8" (10 mm)

3/4" (19 mm)

L15−41  15 ft. − 50 ft. (4.6 m − 15 m)

XC16−036−230

3/8" (10 mm)

7/8" (22 mm)

3/8" (10 mm)

7/8" (22 mm)

L15−65  15 ft. − 50 ft. (4.6 m − 15 m)

XC16−048−230

XC16−060−230

3/8" (10 mm)

1−1/8" (29 mm)

3/8" (10 mm)

1−1/8" (29 mm)

Field Fabricated

NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter

Содержание Elite XC16-024-230

Страница 1: ...rvice valve s internal seals INSTALLATION INSTRUCTIONS Elite Series XC16 Units AIR CONDITIONER 506637 01 11 10 Supersedes 506101 01 TABLE OF CONTENTS General 1 Shipping and Packing List 1 Unit Dimensi...

Страница 2: ...39 991 30 1 2 775 35 889 13 7 8 352 7 3 4 197 3 1 4 83 27 1 8 689 3 5 8 92 4 1 2 114 20 5 8 524 XC16 036 230 45 1143 XC16 048 230 39 991 XC16 060 230 39 991 35 1 2 902 39 3 8 1001 16 7 8 429 8 3 4 222...

Страница 3: ...LVE SUCTION LINE SERVICE VALVE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH MANUAL RESET S4 COMPRESSOR HARNESS GROUND LUG SINGLE POLE CONTACTOR K1 DUAL RUN CAPACITOR C12 CONTROL PANEL PLUMBI...

Страница 4: ...nt loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application N...

Страница 5: ...2 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench...

Страница 6: ...ressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction press...

Страница 7: ...ow Glass has a very high level of sound transmission For proper placement of unit in relation to a window see the provided illustration in figure 4 detail A PLACING UNIT ON SLAB When installing unit a...

Страница 8: ...f two 2 degrees or two inches per five feet 50 mm per 1 5 m away from building structure MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTENE...

Страница 9: ...ERED PANEL REMOVAL Remove the louvered panels as follows 1 Remove two screws allowing the panel to swing open slightly 2 Hold the panel firmly throughout this procedure Rotate bottom corner of panel a...

Страница 10: ...door unit coil braze connections Use Lennox L15 sweat non flare series line set or field fabricated refrigerant line sizes as listed in table 2 NOTE When installing refrigerant lines longer than 50 fe...

Страница 11: ...R RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices sho...

Страница 12: ...N Brazing alloys and flux contain materials which are hazardous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and...

Страница 13: ...FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT...

Страница 14: ...instructions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY...

Страница 15: ...d check expansion valve and the two Teflon rings H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GA...

Страница 16: ...line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface o...

Страница 17: ...nder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the li...

Страница 18: ...et and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves...

Страница 19: ...fer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use only w...

Страница 20: ...Page 20 506637 01 11 10 Figure 13 Typical Unit Wiring Diagram...

Страница 21: ...e remaining in the oil It may be necessary to replace the filter drier several times to achieve the required dryness level If system dryness is not verified the compressor will fail in the future Unit...

Страница 22: ...ide to the suction line service port CConnect the manifold gauge set s high pressure side to the liquid line service port DPosition temperature sensor on liquid line near liquid line service port OUTD...

Страница 23: ...14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70 Temp of air entering indoor coil F INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19 A Dry bulb We...

Страница 24: ...HOD Weigh in or remove refrigerant based upon line length SC Subcooling Values F 1 0 C 0 6 BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the...

Страница 25: ...stem is not properly charged or that a problem exists with some component in the system Temp of air entering outdoor coil 5F 5C 024 036 048 060 Liquid Suction Liquid Suction Liquid Suction Liquid Suct...

Страница 26: ...door fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines and coils for evidence of oil leaks 4 Check wiring for loose connections 5 Check for cor...

Страница 27: ...pection and maintenance for your equipment Make sure no obstructions restrict airflow to the outdoor unit Grass clippings leaves or shrubs crowding the unit can cause the unit to work harder and use m...

Страница 28: ...door Return Air Same Indoor Coil Discharge Air Lower PRESSURES Suction Vapor Lower Liquid Higher Start Up and Performance Checklist Job Name Job no Date Job Location City State Installer City State Un...

Отзывы: