Lennox Elite XC16-024-230 Скачать руководство пользователя страница 26

Page 26

506637−01 11/10

UNIT COMPONENTS

IMPORTANT

Some scroll compressor have internal vacuum protector
that will unload scrolls when suction pressure goes
below 20 psig. A hissing sound will be heard when the
compressor is running unloaded. Protector will reset
when low pressure in system is raised above 40 psig. DO
NOT REPLACE COMPRESSOR.

The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switch
is in the 

ON

 position, the indoor blower operates

continuously.

High Pressure Switch (S4)

XC16 units are equipped with a high-pressure switch that
is located in the liquid line of the compressor as illustrated
in 

Unit Dimensions 

on page 2. The switch is a Single Pole,

Single Throw (SPST), manual−reset switch with red cap
that is normally closed and removes power from the
compressor when discharge pressure rises above factory
setting at 590 + 10 psi.

Low Pressure Switch (S87)

XC16 units are also equipped with a low pressure switch
that is located in the vapor line of the compressor. The
switch (SPST, auto−reset, normally closed) removes
power from the compressor when vapor line pressure
drops below factory setting at 40 + 5 psi.

Crankcase Thermostat (S40) (−048 and −060 Units

Only)

Compressor in the XC16−048 and −060 units are equipped
with a 70 watt, belly band type crankcase heater. HR1
prevents liquid from accumulating in the compressor. HR1
is controlled by a thermostat located on the liquid line.
When liquid line temperature drops below 50° F the
thermostat closes energizing HR1. The thermostat will
open, de−energizing HR1 once liquid line temperature
reaches 70° F .

Liquid Line Filter Drier

A filter drier is factory-installed as illustrated in 

Unit

Dimensions

 on page 2, with each XC16 unit to ensure a

clean, moisture−free system. A replacement filter drier is
available from Lennox. Refer to Lennox Repair Part
Program.

Maintenance

DEALER

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each
cooling season, the system should be checked as follows:

Outdoor Unit

1. Clean and inspect the outdoor coil. The coil may be

flushed with a water hose. Ensure the power is turned
off before you clean the coil.

2. Outdoor fan motor is prelubricated and sealed. No

further lubrication is needed.

3. Visually inspect connecting lines and coils for

evidence of oil leaks.

4. Check wiring for loose connections.

5. Check for correct voltage at the unit (with the unit

operating).

6. Check amp−draw outdoor fan motor.

UNIT NAMEPLATE: _________ ACTUAL: __________

NOTE − If owner reports insufficient cooling, the unit should
be gauged and refrigerant charge checked.

Outdoor Coil

It may be necessary to flush the outdoor coil more
frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may contain
high levels of corrosive chemicals such as salts)

Outdoor Coil  The outdoor coil may be flushed with
a water hose.

Outdoor Coil (Sea Coast)  Moist air in ocean
locations can carry salt, which is corrosive to most
metal. Units that are located near the ocean require
frequent inspections and maintenance. These
inspections will determine the necessary need to wash
the unit including the outdoor coil. Consult your
installing contractor for proper intervals/procedures
for your geographic area or service contract.

INDOOR UNIT

1. Clean or change filters.

2. Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

3. Check blower drive belt for wear and proper tension.

4. Check all wiring for loose connections

5. Check for correct voltage at unit (blower operating).

6. Check amp−draw on blower motor.

UNIT NAMEPLATE: _________ ACTUAL: __________

INDOOR COIL

1. Clean coil, if necessary.

2. Check connecting lines and coils for signs of oil leaks.

3. Check condensate line and clean, if necessary.

TWO−STAGE COMPRESSOR CHECKS

Use the checklist procedure on page 28, to verify part-load
and full-load capacity operation of two-stage modulation
compressors.

IMPORTANT

This performance check is ONLY valid on systems that
have clean indoor and outdoor coils, proper airflow over
coils, and correct system refrigerant charge. All
components in the system must be functioning proper to
correctly perform compressor modulation operational
check. (Accurate measurements are critical to this test
as indoor system loading and outdoor ambient can affect
variations between low and high capacity readings).

Tools Required

Refrigeration gauge set

Содержание Elite XC16-024-230

Страница 1: ...rvice valve s internal seals INSTALLATION INSTRUCTIONS Elite Series XC16 Units AIR CONDITIONER 506637 01 11 10 Supersedes 506101 01 TABLE OF CONTENTS General 1 Shipping and Packing List 1 Unit Dimensi...

Страница 2: ...39 991 30 1 2 775 35 889 13 7 8 352 7 3 4 197 3 1 4 83 27 1 8 689 3 5 8 92 4 1 2 114 20 5 8 524 XC16 036 230 45 1143 XC16 048 230 39 991 XC16 060 230 39 991 35 1 2 902 39 3 8 1001 16 7 8 429 8 3 4 222...

Страница 3: ...LVE SUCTION LINE SERVICE VALVE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH MANUAL RESET S4 COMPRESSOR HARNESS GROUND LUG SINGLE POLE CONTACTOR K1 DUAL RUN CAPACITOR C12 CONTROL PANEL PLUMBI...

Страница 4: ...nt loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application N...

Страница 5: ...2 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench...

Страница 6: ...ressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction press...

Страница 7: ...ow Glass has a very high level of sound transmission For proper placement of unit in relation to a window see the provided illustration in figure 4 detail A PLACING UNIT ON SLAB When installing unit a...

Страница 8: ...f two 2 degrees or two inches per five feet 50 mm per 1 5 m away from building structure MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTENE...

Страница 9: ...ERED PANEL REMOVAL Remove the louvered panels as follows 1 Remove two screws allowing the panel to swing open slightly 2 Hold the panel firmly throughout this procedure Rotate bottom corner of panel a...

Страница 10: ...door unit coil braze connections Use Lennox L15 sweat non flare series line set or field fabricated refrigerant line sizes as listed in table 2 NOTE When installing refrigerant lines longer than 50 fe...

Страница 11: ...R RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices sho...

Страница 12: ...N Brazing alloys and flux contain materials which are hazardous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and...

Страница 13: ...FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT...

Страница 14: ...instructions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY...

Страница 15: ...d check expansion valve and the two Teflon rings H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GA...

Страница 16: ...line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface o...

Страница 17: ...nder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the li...

Страница 18: ...et and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves...

Страница 19: ...fer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use only w...

Страница 20: ...Page 20 506637 01 11 10 Figure 13 Typical Unit Wiring Diagram...

Страница 21: ...e remaining in the oil It may be necessary to replace the filter drier several times to achieve the required dryness level If system dryness is not verified the compressor will fail in the future Unit...

Страница 22: ...ide to the suction line service port CConnect the manifold gauge set s high pressure side to the liquid line service port DPosition temperature sensor on liquid line near liquid line service port OUTD...

Страница 23: ...14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70 Temp of air entering indoor coil F INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19 A Dry bulb We...

Страница 24: ...HOD Weigh in or remove refrigerant based upon line length SC Subcooling Values F 1 0 C 0 6 BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the...

Страница 25: ...stem is not properly charged or that a problem exists with some component in the system Temp of air entering outdoor coil 5F 5C 024 036 048 060 Liquid Suction Liquid Suction Liquid Suction Liquid Suct...

Страница 26: ...door fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines and coils for evidence of oil leaks 4 Check wiring for loose connections 5 Check for cor...

Страница 27: ...pection and maintenance for your equipment Make sure no obstructions restrict airflow to the outdoor unit Grass clippings leaves or shrubs crowding the unit can cause the unit to work harder and use m...

Страница 28: ...door Return Air Same Indoor Coil Discharge Air Lower PRESSURES Suction Vapor Lower Liquid Higher Start Up and Performance Checklist Job Name Job no Date Job Location City State Installer City State Un...

Отзывы: