TROUBLESHOOTING THE ELECTRONIC IGNITION SYSTEM

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

See Below.

Disconnect the two black wires from the wire nuts. Test switch(s) for
continuity with a multimeter. If continuity is not indicated, switch(s) is
defective and must be replaced.

Note: 

Before replacing “OFF/ON” switch, be sure to check wiring for loose

connections or broken wires and repair as needed.

Check main burner orifice(s) for stoppage. Clean or replace.

Check vent system for obstructions.

A.

Faulty Valve System.

B.

“OFF/ON” or wall switch
defective.

A.

Burner orifice plugged.

B.

Obstructed vent system.

1.

Burner will not light.

2.

Burners come “ON” but
go “OFF.”

N

ote:

  Before troubleshooting, be sure that the appliance main line gas shut-off valve, the gas control valve and the wall switch are in

the “ON” position.

Important:

 Valve system troubleshooting should only be accomplished by a qualified service technician.

• Turn Off Gas Supply
• Assure Valve Switch Is In ON Position
• Disconnect Control Harness
• Set Thermostat To Call For Heat

• Check For Proper Voltage At Control Harness
  (See Insert A).  Voltage Should Be 24V
  Between Thermostat Or Pressure Switch
  And 24V Common And 24V Hot.

• Line Voltage Power
• Low Voltage Transformer
• Limit Controller
• Thermostat
• Wiring

2

CHECK

START

NO

• Plug Control Harness Into Valve.  Wait For
   Internal Check Delay.

YES

• Igniter Warms Up And Glows Red.

• With Pilot Burner Cable Connected, Measure
   Voltage At Valve HSI Element Output.  24V
   Nominal.  (See Insert B)

NO

• Replace Igniter/Flame Rod Assembly.

YES

• Replace Valve.

NO

• Turn On Gas Supply.    • Pilot Burner Lights.

• Check That Pilot Gas Is Flowing.  Wait To
   Assure Plot Gas Tubing Is Purged.  Recycle
   Call For Heat If Necessary.

NO

YES

NO

YES

YES

1

• Measure Voltage Between 24V Hot And 24V Common
  Leads To Valve Control.  Must Measure At Least 19.5
  VAC With Igniter Powered (See Insert A).  To Identify
  Proper Lead, This Check Must Be Done With The
  Valve Control Connected And Igniter Powered.

• Check Transformer And
   Line Volt Supply.

NO

• Replace Pilot Assembly.

YES

• Check That Pilot Flame Makes Good Contact With
   Pilot Burner Flame Rod.
• Check For Good Electrical Connection Through The
   Pilot Tubing.
• If Both Of The Above Are Good, Replace Igniter/Flame
   Rod Assembly.

• Cycle Thermostat Off And Back On.

YES

• Main Valve Opens And Main Burner Lights.

NO

YES

• System Is Okay.

YES

• Main Burner Lights.

NO

2

1

Igniter Will Cycle Off And Back On Once During
The 90 Second Ignition Trial.  All Voltage
Measurements Must Be Taken While The Igniter
Is Powered.

When Measured Voltage At Connections, Use
Care To Assure Terminals Are Not Damaged.

• Replace Valve.

• Replace Valve.

24 Volt Hot

End View Of
Control Harness
Connector

24 Volt
Common

24 Volt
Switched

Check For Damaged Or Missing Terminals
In Connector

Insert A

Igniter Terminals

Insert B

2

1

Содержание Elite series

Страница 1: ...cutéparunqualifié installeur agencedeserviceoulefournisseurdegaz DIRECT VENT ELITE SERIES RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE OTL Report No 116 F 05 5 s l e d o M t l o v i l l i M s l e d o M c i n o r t c e l E M N C 0 3 5 3 V D E E N C 0 3 5 3 V D E M N C 5 3 0 4 V D E E N C 5 3 0 4 V D E M N C 0 4 5 4 V D E E N C 0 4 5 4 V D E M P C 0 3 5 3 V D E B E N C 0 3 5 3 V D E M P C 5 3 0 4 ...

Страница 2: ...e these units These appliances comply with National Safety Standards and are tested and listed by Omni Test Laboratories Report No 116 F 05 5 to ANSI Z21 88 2002 in Canada CSA 2 33 2002 and CAN CGA 2 17 M91 in both USA and Canada as vented gas fireplace heaters The Installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the N...

Страница 3: ... V D E 0 0 0 3 3 o N l e d o M e z i s e c i f i r O n o i t a v e l E t e e F s r e t e m t a N p o r P 0 3 5 3 V D E 0 4 3 5 0 0 5 4 0 2 7 3 1 0 5 3 0 4 V D E 6 3 2 5 0 4 5 4 V D E 3 3 1 5 WARNING FAILURE TO COMPLY WITH THE INSTALLATION AND OPER ATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OP ERATING APPLIANCE VOIDING ITS WARRANTY ANY CHANGE TO THIS APP...

Страница 4: ...ctronic Appliances To light electronic appliances refer to the detailed lighting instructions found in both English and French on pages 13 and 14 of these instructions respectively Electronic appliance lighting instructions may also be found on the pull out lighting instruction labels attached to the gas control valve Electronic appliances are fitted with an ON OFF Rocker Switch for appliance ON O...

Страница 5: ...O NOT USE ABRASIVE CLEANERS NEVER CLEAN THE GLASS WHEN IT IS HOT Front Glass Enclosure Panel Removal and Installation These are direct vent appliances They are de signed to operate only when the front glass enclosure panel is installed Generally the front glass enclosure panel should not be removed except to gain access to the components within the firebox and the appliance may only be oper ated w...

Страница 6: ...res 6 EDV3530 7 EDV4035 or 8 EDV4540 on page 7 and verify the flame pattern and height displayed by the appliance conforms to the picture Flames must not impinge on the logs RefertoFigure9 SIT orFigure10 Honeywell on page 8 Remove any surface build up on pilotandburnerassembly Wipethepilotnozzles ignitor flame rod and hood Ensure the pilot flame engulfs the flame sensor as shown Inspect the vent s...

Страница 7: ... opening respectively Position the air shutter to the factory setting as shown in Figure 5 on page 7 Allow the burner to operate for at least 15 minutes Observe the flame continuously If it appears weak or sooty as previously de scribed adjust the air shutter by pushing or pulling on the adjustment rod until the flame appearance is as desired Theadjustmentrodandassociatedadjustableair shutter is p...

Страница 8: ...n a p o r P m m s e h c n i 0 3 5 3 V D E 8 1 2 3 8 3 5 9 5 3 0 4 V D E 5 9 8 3 0 4 5 4 V D E 5 9 8 3 Air Shutter Opening Burner Venturi Tube Air Shutter Door Orifice Increase Air Shutter Opening Decrease Air Shutter Opening Air Shutter Adjusting Arm WARNING LOGS GET VERY HOT AND WILL REMAIN HOT UP TO ONE HOUR AFTER GAS SUPPLY IS TURNED OFF HANDLE ONLY WHEN LOGS ARE COOL TURN OFF ALL ELECTRICITY T...

Страница 9: ... hardware re quired to install the unit The remote receiver can be wall or hearth mounted Deluxe Remote Control System The Model RCL T Deluxe Remote Control System has all of the features of the standard system along with an added easy to read LCD screen which presents access to many en hancements including battery power level in dicator timer mode of operation thermostatic display including room ...

Страница 10: ...K l e n a P e c a F n a e l C o N l e d o M o N g o l a t a C o N l e d o M 0 3 5 3 V D E 6 3 L 8 8 2 C 5 3 D A R 5 3 0 4 V D E 7 3 L 8 8 2 C 0 4 D A R 0 4 5 4 V D E 8 3 L 8 8 2 C 5 4 D A R s t i K r e v u o L d e l b m e s s A o N l e d o M o N g o l a t a C o N l e d o M d e h s i l o P s s a r B d e h s u r B s s e l n i a t S 0 3 5 3 V D E 8 2 L 8 8 2 B P 5 3 R V L 2 3 L 8 8 S B 5 3 R V L 5 3 ...

Страница 11: ... between the wall board and the fireplace providing the appliance a brass perimeter highlight s t i K m i r T h s i n i F o N l e d o M o N g o l a t a C o N l e d o M d e h s i l o P s s a r B 0 3 5 3 V D E 4 5 4 0 H 3 B P E 5 3 K T 5 3 0 4 V D E 2 2 K 6 9 3 B P 0 4 K T 0 4 5 4 V D E 3 2 K 6 9 3 B P 5 4 K T The brickaded panel liner kits include ceramic panels of the side walls the rear and the b...

Страница 12: ...wter H0941 APD45AB 45 Arch Pane Doors Antique Brass H0942 APD35EC 35 Elite Arch Pane Doors Charcoal H0943 APD35ETI 35 Elite Arch Pane Doors Textured Iron H0944 APD35ESP 35 Elite Arch Pane Doors Satin Pewter H0945 APD35EAB 35 Elite Arch Pane Doors Antique Brass EDV4035 EDV4540 EDV3530 SQUARE DESIGN KITS Cat No Model Description Model Series H0950 SD40C 40 Sq Doors Charcoal H0951 SD40TI 40 Sq Doors ...

Страница 13: ...3 CLGK40C 40 Crescents Lower Grille Kit Charcoal H3555 40 Crescents Lower Grille Kit Satin Pewter CLGK40SP H3557 CUGK45C 45 Crescents Upper Grille Kit Charcoal EDV4540 H3559 45 Crescents Upper Grille Kit Satin Pewter CUGK45SP H3561 CLGK45C 45 Crescents Lower Grille Kit Charcoal H3563 45 Crescents Lower Grille Kit Satin Pewter CLGK45SP Sunrise Grille Kits Cat No Model Description Model Series H3565...

Страница 14: ...TION Thermopile TH TP TH TP Millivolt Wiring Diagram If any of the original wire as supplied must be replaced it must be replaced with Type AWM 105 C 18 GA wire OR OPTIONAL WALL MOUNTED ON OFF SWITCH OR OPTIONAL THERMOSTAT OR OPTIONAL REMOTE CONTROL RECEIVER Factory Wired Field Wired Schematic Representation Only APPLIANCE MOUNTED ON OFF SWITCH Turn the appliance mounted ON OFF burner control swit...

Страница 15: ...15 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTES ...

Страница 16: ...ontrol knob all the way and hold in Immediately light the pilot by triggering the spark ignitor pushing the button until pilot lights Continue to hold the control knob in for about 1 minutes after the pilot is lit Release knob and it will pop back up Pilot should remain lit If it goes out repeat steps 5 through 8 If knob does not pop up when released stop and immediately call your service technici...

Страница 17: ...allume gaz à étincelle en poussant le bouton jusqu à ce que la veilleuse s enflamme Continuez de tenir le bouton de réglage enfoncé pendant environ 90 secondes après l allumage de la veilleuse Relâchez le bouton et il sortira subitement La veilleuse devrait rester allumée Si elle s éteint répétez les étapes 5 à 8 inclusivement Si le bouton ne sort pas automatiquement après avoir été relâché arrête...

Страница 18: ...y part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS ELECTRONIC 1 For complete shut down turn remote wall switch to OFF 2 Open lower control compartment door 3 Turn the ON OFF switch to OFF Do not force 4 Close the main line shut off valve 5 Close lower control compartment door TO TURN OFF GAS TO APPLIANCE LIGHTING INSTRUCTIONS 1 STOP Read the safety in...

Страница 19: ...osition d arrêt OFF 3 Ouvrez la porte du compartiment de contrôle du bas 4 Assurez vousquelasoupaped arrêtdelacanalisationprincipale est ouverte 5 Tournezlamanettederéglagedugazàlapositiond arrêt OFF 6 Attendez cinq 5 minutes pour l evacuation du gaz Si vous décelez une odeur de gaz ARRÊTEZ Retournez au point B des consignes de sécurité au verso de cette plaque Si vous ne remarquez aucune odeur de...

Страница 20: ...a qualified service technician Clean and or adjust pilot flame for maximum flame impinge ment on thermocouple Figure 9 on page 8 Check burner orifice for stoppage and remove Checkthermopilewithmillivoltmeter Takereadingatthermo pile terminals of gas valve Should read 325 millivolts mini mum with optional wall switch OFF Replace faulty thermo pile if reading is below specified minimum Check wall sw...

Страница 21: ... NO Plug Control Harness Into Valve Wait For Internal Check Delay YES Igniter Warms Up And Glows Red With Pilot Burner Cable Connected Measure Voltage At Valve HSI Element Output 24V Nominal See Insert B NO Replace Igniter Flame Rod Assembly YES Replace Valve NO Turn On Gas Supply Pilot Burner Lights Check That Pilot Gas Is Flowing Wait To Assure Plot Gas Tubing Is Purged Recycle Call For Heat If ...

Страница 22: ...t a L 1 2 L 9 6 2 1 2 L 9 6 2 1 2 L 9 6 2 9 c i t e n g a M r o o D h c t a C 1 3 L 9 6 1 1 3 L 9 6 1 1 3 L 9 6 1 0 1 e t e l p m o C t e S g o L 2 0 M 5 5 1 3 0 M 5 5 1 3 0 M 5 5 1 1 1 y l b m e s s A r e n r u B 9 2 M 5 5 1 0 3 M 5 5 1 0 3 M 5 5 1 2 1 y l b m e s s A e t a r G 0 9 9 4 H 1 1 9 9 4 H 1 1 9 9 4 H 1 3 1 r e t t u h s r i A i r u t n e V 7 0 7 3 H 1 7 0 7 3 H 1 7 0 7 3 H 1 4 1 r e n ...

Страница 23: ...23 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE REPLACEMENT PARTS 4 8 14 7 41 40 31 30 43 33 32 34 42 36 35 16 13 2 5 6 2 3 17 18 19 11 9 1 12 21 10 15 20 EDV4035 EDV4540 EDV3530 ...

Страница 24: ...75 021M REV G 03 2007 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 ...

Отзывы: