background image

20

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM

1.

Spark ignitor will not light
pilot after repeated
triggering of ignitor button.

2.

Pilot will not stay lit after
carefully following the
lighting instructions.

3.

Pilot burning, no gas to
burner, Valve knob “ON,”
Wall Switch “ON.”

4.

Frequent pilot/burner outage
problem.

CORRECTIVE ACTION

SYMPTOM

A.

Defective ignitor
(no spark at electrode).

B.

Defective or misaligned electrode
at pilot (spark at electrode).

C.

Gas supply pressure errant.

D.

Pilot orifice plugged.

A.

Defective pilot generator

(thermocouple).

A.

Wall switch or wires defective.

B.

Thermopile may not be generating
sufficient millivoltage.

C.

Plugged burner orifice.

A.

Pilot flame may be too low or
blowing (high) causing the pilot/
valve safety to drop out.

Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace ignitor.

POSSIBLE CAUSES

Note: 

Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas supply inlet) is in

the “ON” position.

Important:

 Valve system troubleshooting should only be accomplished by a qualified service technician.

Clean and/or adjust pilot flame for maximum flame impinge-
ment on thermocouple 

(Figure 9 on page 8)

.

Check burner orifice for stoppage and remove.

Check thermopile with millivolt meter. Take reading at thermo-
pile terminals of gas valve. Should read 325 millivolts mini-
mum with optional wall switch “OFF.” Replace faulty thermo-
pile if reading is below specified minimum.

Check wall switch and wires for proper connections. Jumper
wire across terminals at wall switch, if burner comes on,
replace defective wall switch. If okay, jumper wires across wall
switch wires at valve, if burner comes on, wires are faulty or
connections are bad.

Check pilot flame, it must impinge on thermocouple 

(Figure

9 on page 8) 

Clean and/or adjust pilot for maximum flame

impingement on thermocouple. Ensure that the connection
between the valve and thermocouple are tight and secure.

Clean or replace pilot orifice.

Check inlet gas pressure. It should be within the limits as
marked on the rating plate.

Using a match, light pilot. If pilot lights, turn off pilot and
trigger the ignitor button again. If pilot lights, an improper gas
mixture caused the bad lighting and a longer purge period is
recommended. If pilot will not light – check gap at electrode
and pilot – should be 

¹⁄₈

" to have a strong spark. If gap

measures 

¹⁄₈

", replace pilot 

(Figure 9 on page 8)

.

Содержание Elite series

Страница 1: ...cutéparunqualifié installeur agencedeserviceoulefournisseurdegaz DIRECT VENT ELITE SERIES RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE OTL Report No 116 F 05 5 s l e d o M t l o v i l l i M s l e d o M c i n o r t c e l E M N C 0 3 5 3 V D E E N C 0 3 5 3 V D E M N C 5 3 0 4 V D E E N C 5 3 0 4 V D E M N C 0 4 5 4 V D E E N C 0 4 5 4 V D E M P C 0 3 5 3 V D E B E N C 0 3 5 3 V D E M P C 5 3 0 4 ...

Страница 2: ...e these units These appliances comply with National Safety Standards and are tested and listed by Omni Test Laboratories Report No 116 F 05 5 to ANSI Z21 88 2002 in Canada CSA 2 33 2002 and CAN CGA 2 17 M91 in both USA and Canada as vented gas fireplace heaters The Installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the N...

Страница 3: ... V D E 0 0 0 3 3 o N l e d o M e z i s e c i f i r O n o i t a v e l E t e e F s r e t e m t a N p o r P 0 3 5 3 V D E 0 4 3 5 0 0 5 4 0 2 7 3 1 0 5 3 0 4 V D E 6 3 2 5 0 4 5 4 V D E 3 3 1 5 WARNING FAILURE TO COMPLY WITH THE INSTALLATION AND OPER ATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OP ERATING APPLIANCE VOIDING ITS WARRANTY ANY CHANGE TO THIS APP...

Страница 4: ...ctronic Appliances To light electronic appliances refer to the detailed lighting instructions found in both English and French on pages 13 and 14 of these instructions respectively Electronic appliance lighting instructions may also be found on the pull out lighting instruction labels attached to the gas control valve Electronic appliances are fitted with an ON OFF Rocker Switch for appliance ON O...

Страница 5: ...O NOT USE ABRASIVE CLEANERS NEVER CLEAN THE GLASS WHEN IT IS HOT Front Glass Enclosure Panel Removal and Installation These are direct vent appliances They are de signed to operate only when the front glass enclosure panel is installed Generally the front glass enclosure panel should not be removed except to gain access to the components within the firebox and the appliance may only be oper ated w...

Страница 6: ...res 6 EDV3530 7 EDV4035 or 8 EDV4540 on page 7 and verify the flame pattern and height displayed by the appliance conforms to the picture Flames must not impinge on the logs RefertoFigure9 SIT orFigure10 Honeywell on page 8 Remove any surface build up on pilotandburnerassembly Wipethepilotnozzles ignitor flame rod and hood Ensure the pilot flame engulfs the flame sensor as shown Inspect the vent s...

Страница 7: ... opening respectively Position the air shutter to the factory setting as shown in Figure 5 on page 7 Allow the burner to operate for at least 15 minutes Observe the flame continuously If it appears weak or sooty as previously de scribed adjust the air shutter by pushing or pulling on the adjustment rod until the flame appearance is as desired Theadjustmentrodandassociatedadjustableair shutter is p...

Страница 8: ...n a p o r P m m s e h c n i 0 3 5 3 V D E 8 1 2 3 8 3 5 9 5 3 0 4 V D E 5 9 8 3 0 4 5 4 V D E 5 9 8 3 Air Shutter Opening Burner Venturi Tube Air Shutter Door Orifice Increase Air Shutter Opening Decrease Air Shutter Opening Air Shutter Adjusting Arm WARNING LOGS GET VERY HOT AND WILL REMAIN HOT UP TO ONE HOUR AFTER GAS SUPPLY IS TURNED OFF HANDLE ONLY WHEN LOGS ARE COOL TURN OFF ALL ELECTRICITY T...

Страница 9: ... hardware re quired to install the unit The remote receiver can be wall or hearth mounted Deluxe Remote Control System The Model RCL T Deluxe Remote Control System has all of the features of the standard system along with an added easy to read LCD screen which presents access to many en hancements including battery power level in dicator timer mode of operation thermostatic display including room ...

Страница 10: ...K l e n a P e c a F n a e l C o N l e d o M o N g o l a t a C o N l e d o M 0 3 5 3 V D E 6 3 L 8 8 2 C 5 3 D A R 5 3 0 4 V D E 7 3 L 8 8 2 C 0 4 D A R 0 4 5 4 V D E 8 3 L 8 8 2 C 5 4 D A R s t i K r e v u o L d e l b m e s s A o N l e d o M o N g o l a t a C o N l e d o M d e h s i l o P s s a r B d e h s u r B s s e l n i a t S 0 3 5 3 V D E 8 2 L 8 8 2 B P 5 3 R V L 2 3 L 8 8 S B 5 3 R V L 5 3 ...

Страница 11: ... between the wall board and the fireplace providing the appliance a brass perimeter highlight s t i K m i r T h s i n i F o N l e d o M o N g o l a t a C o N l e d o M d e h s i l o P s s a r B 0 3 5 3 V D E 4 5 4 0 H 3 B P E 5 3 K T 5 3 0 4 V D E 2 2 K 6 9 3 B P 0 4 K T 0 4 5 4 V D E 3 2 K 6 9 3 B P 5 4 K T The brickaded panel liner kits include ceramic panels of the side walls the rear and the b...

Страница 12: ...wter H0941 APD45AB 45 Arch Pane Doors Antique Brass H0942 APD35EC 35 Elite Arch Pane Doors Charcoal H0943 APD35ETI 35 Elite Arch Pane Doors Textured Iron H0944 APD35ESP 35 Elite Arch Pane Doors Satin Pewter H0945 APD35EAB 35 Elite Arch Pane Doors Antique Brass EDV4035 EDV4540 EDV3530 SQUARE DESIGN KITS Cat No Model Description Model Series H0950 SD40C 40 Sq Doors Charcoal H0951 SD40TI 40 Sq Doors ...

Страница 13: ...3 CLGK40C 40 Crescents Lower Grille Kit Charcoal H3555 40 Crescents Lower Grille Kit Satin Pewter CLGK40SP H3557 CUGK45C 45 Crescents Upper Grille Kit Charcoal EDV4540 H3559 45 Crescents Upper Grille Kit Satin Pewter CUGK45SP H3561 CLGK45C 45 Crescents Lower Grille Kit Charcoal H3563 45 Crescents Lower Grille Kit Satin Pewter CLGK45SP Sunrise Grille Kits Cat No Model Description Model Series H3565...

Страница 14: ...TION Thermopile TH TP TH TP Millivolt Wiring Diagram If any of the original wire as supplied must be replaced it must be replaced with Type AWM 105 C 18 GA wire OR OPTIONAL WALL MOUNTED ON OFF SWITCH OR OPTIONAL THERMOSTAT OR OPTIONAL REMOTE CONTROL RECEIVER Factory Wired Field Wired Schematic Representation Only APPLIANCE MOUNTED ON OFF SWITCH Turn the appliance mounted ON OFF burner control swit...

Страница 15: ...15 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTES ...

Страница 16: ...ontrol knob all the way and hold in Immediately light the pilot by triggering the spark ignitor pushing the button until pilot lights Continue to hold the control knob in for about 1 minutes after the pilot is lit Release knob and it will pop back up Pilot should remain lit If it goes out repeat steps 5 through 8 If knob does not pop up when released stop and immediately call your service technici...

Страница 17: ...allume gaz à étincelle en poussant le bouton jusqu à ce que la veilleuse s enflamme Continuez de tenir le bouton de réglage enfoncé pendant environ 90 secondes après l allumage de la veilleuse Relâchez le bouton et il sortira subitement La veilleuse devrait rester allumée Si elle s éteint répétez les étapes 5 à 8 inclusivement Si le bouton ne sort pas automatiquement après avoir été relâché arrête...

Страница 18: ...y part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS ELECTRONIC 1 For complete shut down turn remote wall switch to OFF 2 Open lower control compartment door 3 Turn the ON OFF switch to OFF Do not force 4 Close the main line shut off valve 5 Close lower control compartment door TO TURN OFF GAS TO APPLIANCE LIGHTING INSTRUCTIONS 1 STOP Read the safety in...

Страница 19: ...osition d arrêt OFF 3 Ouvrez la porte du compartiment de contrôle du bas 4 Assurez vousquelasoupaped arrêtdelacanalisationprincipale est ouverte 5 Tournezlamanettederéglagedugazàlapositiond arrêt OFF 6 Attendez cinq 5 minutes pour l evacuation du gaz Si vous décelez une odeur de gaz ARRÊTEZ Retournez au point B des consignes de sécurité au verso de cette plaque Si vous ne remarquez aucune odeur de...

Страница 20: ...a qualified service technician Clean and or adjust pilot flame for maximum flame impinge ment on thermocouple Figure 9 on page 8 Check burner orifice for stoppage and remove Checkthermopilewithmillivoltmeter Takereadingatthermo pile terminals of gas valve Should read 325 millivolts mini mum with optional wall switch OFF Replace faulty thermo pile if reading is below specified minimum Check wall sw...

Страница 21: ... NO Plug Control Harness Into Valve Wait For Internal Check Delay YES Igniter Warms Up And Glows Red With Pilot Burner Cable Connected Measure Voltage At Valve HSI Element Output 24V Nominal See Insert B NO Replace Igniter Flame Rod Assembly YES Replace Valve NO Turn On Gas Supply Pilot Burner Lights Check That Pilot Gas Is Flowing Wait To Assure Plot Gas Tubing Is Purged Recycle Call For Heat If ...

Страница 22: ...t a L 1 2 L 9 6 2 1 2 L 9 6 2 1 2 L 9 6 2 9 c i t e n g a M r o o D h c t a C 1 3 L 9 6 1 1 3 L 9 6 1 1 3 L 9 6 1 0 1 e t e l p m o C t e S g o L 2 0 M 5 5 1 3 0 M 5 5 1 3 0 M 5 5 1 1 1 y l b m e s s A r e n r u B 9 2 M 5 5 1 0 3 M 5 5 1 0 3 M 5 5 1 2 1 y l b m e s s A e t a r G 0 9 9 4 H 1 1 9 9 4 H 1 1 9 9 4 H 1 3 1 r e t t u h s r i A i r u t n e V 7 0 7 3 H 1 7 0 7 3 H 1 7 0 7 3 H 1 4 1 r e n ...

Страница 23: ...23 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE REPLACEMENT PARTS 4 8 14 7 41 40 31 30 43 33 32 34 42 36 35 16 13 2 5 6 2 3 17 18 19 11 9 1 12 21 10 15 20 EDV4035 EDV4540 EDV3530 ...

Страница 24: ...75 021M REV G 03 2007 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 ...

Отзывы: