NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

17

Answer  - The minimum required thickness of the Micore 160 is .417”,
therefore round up to nearest standard thickness available which is 1/2”.

** If the hearth extension material(s) that is intended to be used is NOT listed
on Table 1, the material can still be used if the material(s) is noncombustible.
However, the manufacturer of the material must provide either the listed k-
value per inch or r-value per inch with listed thickness so that the minimum
thickness required for the hearth can be calculated (per instructions on this
Page and/or as specified in the NFI Certification manuals).

Note: Also see NFI (National Fireplace Institute) Certification Manuals showing
other acceptable calculation methods and acceptable alternate materials
which can be used.

Listed Material

k (per inch)

r (per inch)

Listed Min.Thickness

Listed Material

.84

K

L

1.19

r

L

1

"

T

L

** Approved Alternate Materials for Floor/Hearth Protection

AlternativeMaterials

Thermal Values

MinimumThickness

(rounded to nearest 1/8 inch)

k (per inch)

K

M

r (per inch)

r

M

Min. Thickness

T

M

Kaowool M Board

.47

2.13

.56" (1/2")

Micore 160™

U.S. Gypsum

.35

2.86

.42" (3/8")

Micore 300™

U.S. Gypsum

.46

2.17

.55" (1/2")

Durock™ Cement Board

U.S. Gypsum

1.92

.52

2.29" (2-1/4")

Hardibacker™

1.95

.513

2.32" (2-3/8")

Hardibacker 500™

2.30

.435

2.74" (2-3/4")

Cultered Stone Hearth-
stone™

2.82

.355

3.36" (3-3/8")

Wonderboard

3.23

.31

3.85" (3-7/8")

Super Firetemp M

Johns-Manville

.61

1.64

.73" (3/4")

Super Firetemp L

Johns-Manville

.54

1.85

.64" (5/8")

Face brick

9.00

.111

10.71" (10-3/4")

Common brick

5.00

.20

5.95" (6")

Cement mortar

5.00

.20

5.95" (6")

Ceramic tile

12.5

.08

14.88" (14-7/8")

Marble

11

.09

13.10" (13-1/8")

Table 1

Calculating Minimum Thickness if Multiple
Materials are Used

At times it is important to know what
combination of materials are acceptable for
use as floor protection. The “R values” are
used to determine acceptable combinations of
materials because “R values” are additive where
r and k values are not.

“R value” =  1/k  =  “r” x thickness of material
used

Example:

  Given that the required “R value”

for a suitable floor protector used must be
equal to or greater than:

“R” = r

L

 x T

L

 = 1.19 x 1” = 1.19.”

If it is desired to elevate a marble hearth ex-
tension to a level of 5” or more above the floor
surface.  What combination of noncombus-
tible materials can be used to accomplish this?

If common brick is used so that the 3 1/2”
dimension is the height, “R” for the common
brick becomes:

brick

“R”

M

 = r

M

 x T

S

 =  0.20   x 3 1/2"  = .70

Using 1/2” of mortar to set the brick, “R” for
the mortar is calculated as follows:

mortar

“R”

M

 = r

M

 x T

S

 =  0.20  x 1/2"  = .10

Next, a 3/4" marble slab set in 1/2" mortar cov-
ers the brick, “R” for the marble and mortar
becomes:

marble

“R”

M

 = r

M

 x T

S

 =  0.05   x 3/4"  = .038

mortar

“R”

M

 = r

M

 x T

S

 =  0.20  x 1/2"  = .10

The sum of all “R values” is: .70 + .10 +. 038
+ .10 = .938

This would NOT be an acceptable combination
of material for the hearth extension since the
total calculated “R value” of the materials used
is under the required “R value” of 1.19.  An
additional layer of insulating materials must
be used.

Note:

 Also see NFI Certification Manuals for

expanded explanation on calculating “R val-
ues” when multiple materials are used.

Содержание Elite LA41TCF

Страница 1: ...not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and acc...

Страница 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribut...

Страница 3: ...e fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance with co...

Страница 4: ...avoid overhead obstructions such as trees power lines etc A chase should be constructed and insulated just like any outside wall In a cold climate we recommend the base of the chase should also be ins...

Страница 5: ...nd the fireplace positioned into the opening Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney an...

Страница 6: ...movement Note The Z type safety strip is not supplied Step 3 Refer to fireplace drawings and specifi cationsonpages6and7forframingdimensions and details Frame appliance enclosure as illus trated in F...

Страница 7: ...uding Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Framing Dimensions for Roof Pitch C D 0 12 19 19 483 mm 483 mm 6 12 19 22 483 mm 559 mm 12 12 19 27...

Страница 8: ...o determine chimney cen terline useplumblinefromrooforceilingabove fireplace to center of flue collar on fireplace Figure 18 Step 3 Position appropriate firestop spacer at ceiling and nail temporarily...

Страница 9: ...r section down into respective section of proceeding flue pipe and locking outer stabi lizer section into place over the outer chimney pipe Position for proper clearance through framedopeningandnailst...

Страница 10: ...ngaged Using a FTF10 CTDT Chase Termination Refer to specific installation instructions in cluded with the FTF10 CTDT chase termination for clearance and installation details Using a FTF10 CT1 Chase T...

Страница 11: ...y Chimneys 30 offset and return elbows Use two elbows an offset elbow to initiate the offset and a return elbow to terminate it A 30 offset elbow angling in any direction may be the first component us...

Страница 12: ...6 2 0 8 300 25 0 1 1 8 308 25 8 0 0 9 318 26 8 1 0 9 324 27 0 0 1 9 328 27 4 2 0 9 334 27 10 1 1 9 342 28 6 0 0 10 352 29 4 1 0 10 Height Of Number Of FTF10 Chimney Only Chimney Lengths Inches Feet In...

Страница 13: ...tep2 ProceedbyusingtheStraightUpInstal lation Instructions for cutting and framing ceil ing and roof openings FTF10 OFFSET ELEVATION CHART A B FTF10 ES30 Number of FTF10 Offset Height Offset Return FT...

Страница 14: ...OPTIONAL EQUIPMENT CONSIDERATIONS Gas Line Connection Install a gas supply line through fireplace wall for connection to a decorative gas appli anceinsidethefirebox Outside thegassupply line connects...

Страница 15: ...y sit directly on a combus tible surface A 2 air space is required be tween combustible framing and the chimney Combustible mantels and trim may be in stalled 12 above the fireplace opening as per NFP...

Страница 16: ...r the k value or r value is known use either the k formula or r formula Example If Micore 160 is to be used for the hearth extension fireplace how thick must this material be kM k value per inch of al...

Страница 17: ...ville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common brick 5 00 20 5 95 6 Cement mortar 5 00 20 5 95 6 Ceramic tile 12 5 08 14 88 14 7 8 Marble 11 09 13 10 13 1 8 Table 1 Calculating Minimum T...

Страница 18: ...extension used must be equal to or greater than R r x TL 3 70 x 1 3 70 If it is desired to elevate a marble hearth exten sion to a level of 5 or more above the floor surface What combination of noncom...

Страница 19: ...lar 63L59 FSC 63L40 F10F6 Flashing 63L41 F10F12 Round Termination 63L423 FTF10 CTD Chase Termination Square 63L49 FTF10 CT1 Firestop Spacer Flat 63L36 F10FS 2 Chase Termination Round 63L46 FTF10 CTDT...

Страница 20: ...ges at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S...

Отзывы: