NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

16

Figure 43

A

B

D

C

C

Hearth Extension Dimensions

(For 

Figures 43 and 44 )

A

20"

B

41"

C

12"

D

65"

Note:

 Any noncombustible material whose k

value is less than .84 or whose r value is more
than 1.19 is acceptable.

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided)
on the floor extending half under the fire-
place and half under the hearth extension.

A wall shield is required where a continuous
perpendicular side wall is within 15" of the
fireplace opening (

see

 Figure 44 

). Use a 40" W

x 40" H wall shield constructed of a durable,
noncombustible material having an equal or
better (lower k value) insulating value than k =
.84 BTU IN/FT

2

 HR 

°

F.  At no time may a

perpendicular side wall be located closer than
12" from the fireplace opening.

If fireplace is installed diagonally across a 90

°

corner; no wall shields are required.

Methods of Determini

ng Hearth Extension and Wall Shield

Equivalents -

 To determine the thickness required for the alternate

material when either the 

“k”

 value or 

“r”

 value is known, use either the

k formula

 or 

r formula

.

Example:

 If Micore 160 is to be used for the hearth extension fireplace,

how thick must this material be?

k

M

 = k value per inch of 

alternate

 material

r

M

 = r value per inch of 

alternate

 material

T

M

 =  minimum thickness required for 

alternate

 material

T

 =  standard thickness of the 

alternate

 material

k

L

 = k value per inch of 

listed

 material

r

L

 = r value per inch of 

listed

 material

T

L

 

= minimum thickness of 

listed

 material

Note:  

An asterix “

*

” indicates, it is a value taken from 

Table 1

.

Using the k formula:

Minimum

k-value (per Inch) of

Specified min.

thickness of

=

alternate material (k

M

) x

thickness

alternate

k-value  (per inch)

of listed

material (T

M

)

of listed material (k

M

)

material (T

L

)

T

M

 (inches)

=

      

      k

M

x

T

L

         *.84

T

M

 (inches)

=

         *.35

x

1"

         *.84

.416  (inches) =

           .416

x

1"

Answer  - The minimum required thickness of the Micore 160 is .417”,
therefore round up to nearest standard thickness available which is 1/2”.

Using the r formula:

Minimum

r-value (per Inch)

Specified min.

thickness of

=

of listed material

x

thickness

alternate

r-value  (per inch)

of listed

material

of alternate material

material

T

M

 (inches)

=

            

r

L

x

T

L

         

   r

M

T

M

 (inches)

=

         *1.19

x

1"

         *2.86

.416  (inches) =

           .416

x

1"

Figure 44

Wall Shield Required
Where Less Than 15"

A

B

C

C

36”

24”

D

Содержание Elite LA41TCF

Страница 1: ...not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and acc...

Страница 2: ...damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distribut...

Страница 3: ...e fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chimneys fireplaces and solid fuel burning appliances NFPA 211 and in accordance with co...

Страница 4: ...avoid overhead obstructions such as trees power lines etc A chase should be constructed and insulated just like any outside wall In a cold climate we recommend the base of the chase should also be ins...

Страница 5: ...nd the fireplace positioned into the opening Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney an...

Страница 6: ...movement Note The Z type safety strip is not supplied Step 3 Refer to fireplace drawings and specifi cationsonpages6and7forframingdimensions and details Frame appliance enclosure as illus trated in F...

Страница 7: ...uding Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Framing Dimensions for Roof Pitch C D 0 12 19 19 483 mm 483 mm 6 12 19 22 483 mm 559 mm 12 12 19 27...

Страница 8: ...o determine chimney cen terline useplumblinefromrooforceilingabove fireplace to center of flue collar on fireplace Figure 18 Step 3 Position appropriate firestop spacer at ceiling and nail temporarily...

Страница 9: ...r section down into respective section of proceeding flue pipe and locking outer stabi lizer section into place over the outer chimney pipe Position for proper clearance through framedopeningandnailst...

Страница 10: ...ngaged Using a FTF10 CTDT Chase Termination Refer to specific installation instructions in cluded with the FTF10 CTDT chase termination for clearance and installation details Using a FTF10 CT1 Chase T...

Страница 11: ...y Chimneys 30 offset and return elbows Use two elbows an offset elbow to initiate the offset and a return elbow to terminate it A 30 offset elbow angling in any direction may be the first component us...

Страница 12: ...6 2 0 8 300 25 0 1 1 8 308 25 8 0 0 9 318 26 8 1 0 9 324 27 0 0 1 9 328 27 4 2 0 9 334 27 10 1 1 9 342 28 6 0 0 10 352 29 4 1 0 10 Height Of Number Of FTF10 Chimney Only Chimney Lengths Inches Feet In...

Страница 13: ...tep2 ProceedbyusingtheStraightUpInstal lation Instructions for cutting and framing ceil ing and roof openings FTF10 OFFSET ELEVATION CHART A B FTF10 ES30 Number of FTF10 Offset Height Offset Return FT...

Страница 14: ...OPTIONAL EQUIPMENT CONSIDERATIONS Gas Line Connection Install a gas supply line through fireplace wall for connection to a decorative gas appli anceinsidethefirebox Outside thegassupply line connects...

Страница 15: ...y sit directly on a combus tible surface A 2 air space is required be tween combustible framing and the chimney Combustible mantels and trim may be in stalled 12 above the fireplace opening as per NFP...

Страница 16: ...r the k value or r value is known use either the k formula or r formula Example If Micore 160 is to be used for the hearth extension fireplace how thick must this material be kM k value per inch of al...

Страница 17: ...ville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common brick 5 00 20 5 95 6 Cement mortar 5 00 20 5 95 6 Ceramic tile 12 5 08 14 88 14 7 8 Marble 11 09 13 10 13 1 8 Table 1 Calculating Minimum T...

Страница 18: ...extension used must be equal to or greater than R r x TL 3 70 x 1 3 70 If it is desired to elevate a marble hearth exten sion to a level of 5 or more above the floor surface What combination of noncom...

Страница 19: ...lar 63L59 FSC 63L40 F10F6 Flashing 63L41 F10F12 Round Termination 63L423 FTF10 CTD Chase Termination Square 63L49 FTF10 CT1 Firestop Spacer Flat 63L36 F10FS 2 Chase Termination Round 63L46 FTF10 CTDT...

Страница 20: ...ges at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S...

Отзывы: