background image

Page 3

ELS120S4S, ELS120S4D AND ELS150S4D

Corner Weight

Model No.

AA

BB

CC

DD

lbs.

kg

lbs.

kg

lbs.

kg

lbs.

kg

ELS 120S4S

130

59

124

56

107 49

111

50

ELS 120S4D

122

55

119

54

127

58

131

59

ELS 150S4D

144

66

132

60

133

60

145

66

Centers of Gravity

Model No.

EE

FF

inch

mm

inch

mm

ELS 120S4S

20.5

521

33.5

851

ELS 120S4D

21.0

533

28.5

724

ELS 150S4D

19.0

483

30.0

762

DISCHARGE

AIR

REFRIGERANT

LINE CONNECTIONS

SEE DETAIL

DISCHARGE

AIR

41−3/8

(1051)

LIFTING HOLES

(For Rigging)

SIDE VIEW

43−5/8

(1108)

48−3/4

(1238)

3−1/2

(89)

45−1/4

(1149)

BASE

60−1/8

(1527)

57−7/8

(1470)

COMPRESSOR

BASE

FRONT VIEW

FORKLIFT SLOTS

(Both Sides)

CONTROL

BOX ACCESS

ELECTRICAL 

INLETS (Above

Refrigerant Lines)

TOP VIEW

FF

EE

INLE

AI

R

INLET AIR

B

B

A

A

CC

DD

CENTER OF

GRAVITY

ELECTRICAL

INLETS (Above

Refrigerant Lines)

OUTDOOR FAN

GUARDS (2)

INLET AIR

OPTIONAL

COIL GUARD

(Field Installed

All Coil Sides)

(Not used with

Hail Guard)

2(51)

OPTIONAL HAIL GUARD

(Field Installed All Coil Sides)

(Not used with Coil Guard)

OPTIONAL HAIL GUARD

(Field Installed All Coil Sides)

(Not used with Coil Guard)

5

(127)

(54)

(232)

(29)

(95)

(165)

SUCTION

LINES

LIQUID

LINES

SINGLE STAGE

ELS120S4S

STAGE 1

ELS120S4D

ELS150S4D

STAGE 2

ELS120S4D

ELS150S4D

(29)

REFRIGERANT LINE

CONNECTIONS DETAIL

(286)

(Not used with

Hail Guard)

OPTIONAL COIL GUARD

(Field Installed All Coil Sides)

(Not used with Hail Guard)

OPTIONAL

COIL GUARD

(Field Installed

All Coil Sides)

9−1/8

6−1/2

3−3/4

1−1/8

1−1/8

2−1/8

11−1/4

Содержание Elite ELS Series

Страница 1: ...IR CONDITIONERS 6 20 TONS 507743 02 5 2019 Elite ELS Series 6 20 Ton Shipping and Packing List Check the unit for shipping damage If damaged or parts are missing immediately contact the last shipping...

Страница 2: ...CC DD 37 5 8 956 48 3 4 1238 3 1 2 89 45 1 4 1149 REFRIGERANT LINE CONNECTIONS SEE DETAIL REFRIGERANT LINE CONNECTIONS DETAIL EE FF CONTROL BOX ACCESS COMPRESSOR COMPRESSOR CENTER OF GRAVITY INLET AIR...

Страница 3: ...CONTROL BOX ACCESS ELECTRICAL INLETS Above Refrigerant Lines TOP VIEW FF EE INLET AIR INLETAIR B B A A CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Lines OUTDOOR FAN GUARDS 2 INLETAIR...

Страница 4: ...D LINE 2 OUTDOOR FAN GUARDS 4 REFRIGERANT LINE CONNECTIONS DETAIL INLET AIR INLET AIR ELECTRICAL INLETS Above Refrigerant Lines DISCHARGE AIR REFRIGERANT LINE CONNECTIONS SEE DETAIL ELECTRICAL INLETS...

Страница 5: ...Page 5 Unit Plumbing Parts Arrangement ELS072S4S ELS090S4S...

Страница 6: ...Page 6 ELS120S4S ELS120S4D STAGE 2...

Страница 7: ...Page 7 ELS120S4D STAGE 1 ELS150S4D STAGE 2...

Страница 8: ...Page 8 ELS150S4D STAGE 1 ELS180S4D STAGE 2...

Страница 9: ...Page 9 ELS180S4D STAGE 1 ELS240S4D STAGE 2...

Страница 10: ...0 Tons 150 12 5 Tons 180 15 Tons 240 20 Tons Cooling Efficiency S Standard Efficiency Minor Design Sequence 1 1st Revision 2 2nd Revision 3 3rd Revision Voltage Y 208 230V 3 phase 60hz G 460V 3 phase...

Страница 11: ...Page 11 Unit Control Box Components Arrangement...

Страница 12: ...adequate strength and length An H style frame will prevent the top of the unit from being damaged Caution do not walk on unit Important all panels must be in place for rigging Lifting point should be...

Страница 13: ...ntrol box Piping can be routed directly from the service valves or field supplied elbows can be added to divert the piping as required Refer to table 1 for field fabricated refrigerant line sizes for...

Страница 14: ...AT DISCONNECT SWITCH OR TO AN EARTH GROUND CIRCUIT SIZING AND DISCONNECT SWITCH DISCONNECT SWITCH MAIN FUSE BOX BREAKER PANEL 1 2 TYPICAL HIGH VOLTAGE POWER SUPPLY CONNECTIONS Install room thermostat...

Страница 15: ...MAINTAINS SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS NOTE DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX Two Stage Compressor Solenoid L34 Resistance Check Resistanc...

Страница 16: ...Page 16 FIGURE 7 Typical Wiring Diagram ELS072S4S ELS090S4S and ELS120S4S G J M Y Voltages...

Страница 17: ...VOLTAGE CB8 CIRCUIT BREAKER TRANS T1 S24 S25 T1 SWITCH LOSS OF CHARGE COMP 1 SWITCH LOSS OF CHARGE COMP 2 TRANSFORMER CONTROL SECTION A 3 WIRING DIAGRAM 4 S25 S24 3 1 CB8 T1 208V COOL 1 COOL 2 C2 C1 2...

Страница 18: ...OL 1 C2 C1 CB8 CIRCUIT BREAKER TRANS T1 S24 S25 T1 TRANSFORMER CONTROL SWITCH LOSS OF CHARGE COMP 1 SWITCH LOSS OF CHARGE COMP 2 WIRING DIAGRAM SECTION A 4 4 2 5 3 1 S25 S24 T1 240 460 575V 208V CB8 2...

Страница 19: ...ssure is high remove refrigerant from the system If liquid pressure is low add refrigerant to the system Add or remove charge in increments Allow the system to stabilize at least 5 minutes each time r...

Страница 20: ...91 142 125 52 540 155 558 157 545 140 553 144 548 146 SCFM 2600 2750 2725 2750 3850 pressures at 80F dry bulb and 67F wet bulb entering indoor air temperatures TABLE 5 Normal Operating Pressures Cooli...

Страница 21: ...408 141 423 147 420 147 115 46 465 138 463 142 480 149 477 150 125 52 526 139 522 143 544 152 541 152 SCFM 5400 7125 Entering Outdoor Air Temp F C ELS240 ELA240 ELS240 2 ELA120 STAGE 1 STAGE 2 STAGE 1...

Страница 22: ...5 374 134 373 137 375 136 105 41 446 143 441 142 425 139 427 137 427 141 428 139 115 46 505 145 501 144 483 143 484 141 484 144 486 142 125 52 569 148 566 147 545 146 548 145 547 147 550 146 SCFM 3615...

Страница 23: ...ked as follows OUTDOOR UNIT 1 Clean and inspect the condenser coil You can flush the coil with a water hose 2 The outdoor fan motor is prelubricated and sealed No further lubrication is necessary 3 Vi...

Страница 24: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Отзывы: