background image

Page 23

System Operation 

The outdoor unit and indoor blower cycle on demand from 

the room thermostat. When the thermostat blower switch 

is in the ON position, the indoor blower operates contin-

uously. 

HIGH PRESSURE SWITCHES (S4 AND S7) 

These units are equipped with a manual reset high pres-

sure switch (single-pole, single-throw) which is located on 

the discharge line. The switch shuts off the compressor 

when discharge pressure rises above the factory setting. 

High Pressure (auto reset) – trip at 640 psig; reset at 512 

psig. 

LOSS OF CHARGE SWITCHES (S24 AND S25) 

NOTE

 – 

Used on units with two single-speed compres-

sors.

These units are equipped with a loss-of-charge switch that 

is located in the liquid line. The switch is a SPST, auto-re-

set switch that is normally closed. The switch opens at 40 

psi and closes at 90 psi.

LOW PRESSURE SWITCH (S87)

NOTE

 – 

Used on units with one two-stage compressor.

These units are equipped with a loss-of-charge switch that 

is located in the liquid line. The switch is a SPST, auto-re-

set switch that is normally closed. The switch opens at 40 

psi and closes at 90 psi. 

Maintenance 

At the beginning of each cooling season, the system 

should be checked as follows: 

OUTDOOR UNIT 

1 - 

 Clean and inspect the condenser coil. You can flush 

the coil with a water hose. 

2 -   The outdoor fan motor is prelubricated and sealed. 

No further lubrication is necessary. 

3 -   

Visually inspect connecting lines and coils for 

evidence of oil leaks. 

4 -  Check wiring for loose connections. 
5 -   Check for correct voltage at the unit while the unit is 

operating and while it is off. 

6 -   

Check amp-draw of the outdoor fan motor. 

 

Unit nameplate _________ Actual ____________

 

7 -   

Check amp-draw of the compressor. 

 

Unit nameplate _________ Actual ____________ 

NOTE

 – 

If  the  owner  complains  of  insufficient  cooling, 

gauge the unit and check the refrigerant charge. Refer to 

section on refrigerant charging in this instruction.

 

INDOOR COIL 

1 -  If necessary, clean the coil. 
2 -   Check connecting lines and coils for evidence of oil 

leaks. 

3 -   If necessary, check the condensate line and clean it. 

INDOOR UNIT 

1 - 

Clean or change filters. 

2 -   Adjust the blower speed for cooling. Measure the 

pressure drop over the coil to determine the correct 

blower CFM. Refer to the unit information service 

manual for pressure drop tables and procedure. 

3 -   On belt drive blowers, check the belt for wear and 

proper tension. 

4 -  Check all wiring for loose connections. 
5 -   

Check for correct voltage at the unit (blower 

operating). 

6 -   

Check amp-draw on blower motor. 

 

Unit nameplate _________ Actual ____________

Содержание Elite ELS Series

Страница 1: ...IR CONDITIONERS 6 20 TONS 507743 02 5 2019 Elite ELS Series 6 20 Ton Shipping and Packing List Check the unit for shipping damage If damaged or parts are missing immediately contact the last shipping...

Страница 2: ...CC DD 37 5 8 956 48 3 4 1238 3 1 2 89 45 1 4 1149 REFRIGERANT LINE CONNECTIONS SEE DETAIL REFRIGERANT LINE CONNECTIONS DETAIL EE FF CONTROL BOX ACCESS COMPRESSOR COMPRESSOR CENTER OF GRAVITY INLET AIR...

Страница 3: ...CONTROL BOX ACCESS ELECTRICAL INLETS Above Refrigerant Lines TOP VIEW FF EE INLET AIR INLETAIR B B A A CC DD CENTER OF GRAVITY ELECTRICAL INLETS Above Refrigerant Lines OUTDOOR FAN GUARDS 2 INLETAIR...

Страница 4: ...D LINE 2 OUTDOOR FAN GUARDS 4 REFRIGERANT LINE CONNECTIONS DETAIL INLET AIR INLET AIR ELECTRICAL INLETS Above Refrigerant Lines DISCHARGE AIR REFRIGERANT LINE CONNECTIONS SEE DETAIL ELECTRICAL INLETS...

Страница 5: ...Page 5 Unit Plumbing Parts Arrangement ELS072S4S ELS090S4S...

Страница 6: ...Page 6 ELS120S4S ELS120S4D STAGE 2...

Страница 7: ...Page 7 ELS120S4D STAGE 1 ELS150S4D STAGE 2...

Страница 8: ...Page 8 ELS150S4D STAGE 1 ELS180S4D STAGE 2...

Страница 9: ...Page 9 ELS180S4D STAGE 1 ELS240S4D STAGE 2...

Страница 10: ...0 Tons 150 12 5 Tons 180 15 Tons 240 20 Tons Cooling Efficiency S Standard Efficiency Minor Design Sequence 1 1st Revision 2 2nd Revision 3 3rd Revision Voltage Y 208 230V 3 phase 60hz G 460V 3 phase...

Страница 11: ...Page 11 Unit Control Box Components Arrangement...

Страница 12: ...adequate strength and length An H style frame will prevent the top of the unit from being damaged Caution do not walk on unit Important all panels must be in place for rigging Lifting point should be...

Страница 13: ...ntrol box Piping can be routed directly from the service valves or field supplied elbows can be added to divert the piping as required Refer to table 1 for field fabricated refrigerant line sizes for...

Страница 14: ...AT DISCONNECT SWITCH OR TO AN EARTH GROUND CIRCUIT SIZING AND DISCONNECT SWITCH DISCONNECT SWITCH MAIN FUSE BOX BREAKER PANEL 1 2 TYPICAL HIGH VOLTAGE POWER SUPPLY CONNECTIONS Install room thermostat...

Страница 15: ...MAINTAINS SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS NOTE DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX Two Stage Compressor Solenoid L34 Resistance Check Resistanc...

Страница 16: ...Page 16 FIGURE 7 Typical Wiring Diagram ELS072S4S ELS090S4S and ELS120S4S G J M Y Voltages...

Страница 17: ...VOLTAGE CB8 CIRCUIT BREAKER TRANS T1 S24 S25 T1 SWITCH LOSS OF CHARGE COMP 1 SWITCH LOSS OF CHARGE COMP 2 TRANSFORMER CONTROL SECTION A 3 WIRING DIAGRAM 4 S25 S24 3 1 CB8 T1 208V COOL 1 COOL 2 C2 C1 2...

Страница 18: ...OL 1 C2 C1 CB8 CIRCUIT BREAKER TRANS T1 S24 S25 T1 TRANSFORMER CONTROL SWITCH LOSS OF CHARGE COMP 1 SWITCH LOSS OF CHARGE COMP 2 WIRING DIAGRAM SECTION A 4 4 2 5 3 1 S25 S24 T1 240 460 575V 208V CB8 2...

Страница 19: ...ssure is high remove refrigerant from the system If liquid pressure is low add refrigerant to the system Add or remove charge in increments Allow the system to stabilize at least 5 minutes each time r...

Страница 20: ...91 142 125 52 540 155 558 157 545 140 553 144 548 146 SCFM 2600 2750 2725 2750 3850 pressures at 80F dry bulb and 67F wet bulb entering indoor air temperatures TABLE 5 Normal Operating Pressures Cooli...

Страница 21: ...408 141 423 147 420 147 115 46 465 138 463 142 480 149 477 150 125 52 526 139 522 143 544 152 541 152 SCFM 5400 7125 Entering Outdoor Air Temp F C ELS240 ELA240 ELS240 2 ELA120 STAGE 1 STAGE 2 STAGE 1...

Страница 22: ...5 374 134 373 137 375 136 105 41 446 143 441 142 425 139 427 137 427 141 428 139 115 46 505 145 501 144 483 143 484 141 484 144 486 142 125 52 569 148 566 147 545 146 548 145 547 147 550 146 SCFM 3615...

Страница 23: ...ked as follows OUTDOOR UNIT 1 Clean and inspect the condenser coil You can flush the coil with a water hose 2 The outdoor fan motor is prelubricated and sealed No further lubrication is necessary 3 Vi...

Страница 24: ...e or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Vapor Pressure Refrigerant Lines...

Отзывы: