Troubleshooting:   Burner runs continuously (too little heat).

Source

Procedure

Causes

Correction

Combustion

Check burner
combustion for
CO2, stack tem­
perature, and
smoke

Low CO

less

than 10%.

Too much combustion air

Reduce combustion air.

Air leaks into heat exchanger
around inspection door, etc.

Correct cause of air leak.

Excessive overfire draft

Adjust barometric draft con­
trol for correct draft.

Incorrect nozzle assembly
depth

Set to 1.13.

High smoke
reading more
than a trace.

Dirty or plugged heat exchanger

Clean heat exchanger.

Readjust burner.

Insufficient overfire draft

Increase draft.

Incorrect nozzle assembly 
depth

Set to 1.13.

Too little combustion air

Increase combustion air.

High stack tem­
perature is more
than 550

_

F Net.

Low volume indoor blower air

Check pump coupling for
wear / slippage.

Dirty heat exchanger

Clean heat exchanger.

Dirty burner blower wheel

Clean burner blower wheel.

Dirty furnace air filters

Clean or replace filter.

Restricted or closed registers or
dampers

Readjust registers or damp­
ers.

Oil Pressure

Inspect fire and check

oil pressure.

Partially plugged or bad nozzle

Replace nozzle.

Oil pressure is too low 
(less than 140 psi.)

Increase oil pressure to 140
psi.

ELO183DH Start-Up & Performance Check List 

Filter Clean & Secure?

Supply Voltage

Electrical Connections Tight?

Job Name

Job Location

Installer

Unit Model No.

Oil Pump Pressure [recommended minimum 140 psi]

Job No.

City

City

Serial No.

Date

State

Serviceman

Draft Reading (recommended .03-.04 inches w.c.)

Flue Connections Tight?

HEATING SECTION

THERMOSTAT

Calibrated?

Heat Anticipator Properly Set?

Level?

Blower Motor Amps

Blower Motor H.P.

Piping Connections Tight?

Vent Clear?

State

Temperature Rise

External Static Pressure

Net Stack Temp

Burner Model No.

Serial Number

All Valves Open?

PROPER DRAFT

% CO

2

% O

2

ppm CO

Stack Draft

Overfire Draft

Ambient Temp

Smoke Test

Содержание Elite ELO183DH Series

Страница 1: ...ist 1 Unit Dimensions 2 ELO183DH Unit Parts Arrangement 3 Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Installation 7 Adjustments 8 Venting 9 Flue Connections 10 Supply R...

Страница 2: ...IEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furnac...

Страница 3: ...XCHANGER CLEAN OUT PORT ELO183DH Oil Burner Parts Arrangement Figure 2 ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WITH ELECTRODE ASSEMBLY AND N...

Страница 4: ...the type and construction outlined in section 160 of NFPA No 31 Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No 31 or in Cana da CSA Standard B139 When...

Страница 5: ...side for combustion Also exhaust fans ap pliance vents chimneys and fireplaces force additional air that could be used for combustion out of the house Unless outside air is brought into the home for c...

Страница 6: ...per 1 000 Btu 293 W per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches 614 5 square centimeters Oil Furnace Air from Outside If air from outside i...

Страница 7: ...ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application Air flow may be reversed to right side discharge or unit may be used as downflow 1 Reversing Airflow...

Страница 8: ...odes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flange for re moving the burner assembly from the vestibule Loosen the nuts and turn the wh...

Страница 9: ...t be smaller than the out let diameter of the vent outlet of the furnace 4 Pipe should be at least 24 gauge galvanized 5 Single wall vent pipe should not run outside or through any unconditioned space...

Страница 10: ...and win dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appli...

Страница 11: ...is no complete return air duct sys tem a return air connection should be run the same size as the return air opening to a location outside the room containing the furnace 5 Install supply and return a...

Страница 12: ...itions require that you use of a two pipe system which consists of a return line that purges the fuel pump of air by returning it to the tank To determine the run and lift for piping refer to table 5...

Страница 13: ...it See figure 13 3 Attach the return and inlet pipes Start the burner Air bleeding is automatic NOTE If a faster bleed is necessary open the bleed valve 4 The return pipe must terminate 3 to 4 above t...

Страница 14: ...wire WARNING Run 24V Class II wiring only through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening CAUTION Use c...

Страница 15: ...re fuel pump pressure with unit off Attach pressure gauge to pump outlet Turn unit on and check pressure and compare to table 9 Adjust if necessary Temperature Rise Adjustment To measure temperature r...

Страница 16: ...rotate the shutter until the desired smoke level is achieved If smoke cannot be reduced to the desired level by moving the air shutter adjust the air band to increase the air To adjust the air band lo...

Страница 17: ...f the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove the locking screw and cap from the observa tion tube and with the spiral wire brush reach upward toward the rear o...

Страница 18: ...ontinue to flow as long as cad cell senses flame D Heat fan on timing 1 to 30 seconds begins When timing is complete the indoor blower is at heat speed and warm air is delivered to the controlled spac...

Страница 19: ...ls Burner motor is de energized and oil primary control goes into recycle mode If heat fan off delay is longer than the recycle delay timing the heat fan continues to run through the next trial for ig...

Страница 20: ...nect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off fals...

Страница 21: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Страница 22: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Страница 23: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Страница 24: ...nger Clean heat exchanger Dirty burner blower wheel Clean burner blower wheel Dirty furnace air filters Clean or replace filter Restricted or closed registers or dampers Readjust registers or damp ers...

Отзывы: