background image

Page 26

IX- Troubleshooting 

Troubleshooting:  Heating Sequence of Operation

HEATING SEQUENCE OF OPERATION

NORMAL AND ABNORMAL HEATING MODE

CONTROL SELF-CHECK OKAY?

YES

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF. (RESET CONTROL BY

TURNING MAIN POWER OFF.)

NO

POLARITY REVERSED.

STATUS ERROR CODE 5 + 4.

POWER ON

POLARITY OKAY?

 SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED.

STATUS ERROR CODE 5 + 3.

IS THERE A

PROPER GROUND?

NO

YES

A

NORMAL OPERATION:

STATUS LED -- PULSE

B

THERMOSTAT CALLS FOR HEAT:

STATUS LED -- HEARTBEAT

YES

PRIMARY AND SECONDARY LIMIT

SWITCHES CLOSED?

YES

NO

COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER ON. HAS PRIMARY OR

SECONDARY LIMIT RESET WITHIN 3 MINUTES?

STATUS ERROR CODE 3 + 1.

ROLLOUT SWITCH CLOSED?

GAS VALVE OFF. COMBUSTION AIR INDUCER ON.

INDOOR BLOWER ON.

STATUS ERROR CODE 5 + 1.

SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS
RESET AND MAIN POWER IS INTERRUPTED OR

T'STAT IS CYCLED OFF/ON FOR 3 SEC. MINIMUM.

NO

YES

FIRST (LOW) STAGE PRESSURE SWITCH

CONTACTS OPEN?

NO

GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF. CONTROL REMAINS UNTIL

PRESSURE SWITCH IS DETECTED OPEN.

STATUS ERROR CODE 2 + 4

YES

GAS VALVE OFF.

COMBUSTION AIR INDUCER OFF.

INDOOR BLOWER OFF.

CONTROL WILL NOT ATTEMPT SECOND-STAGE

OPERATION DURING THIS HEAT DEMAND.

FIRST-STAGE OPERATION WILL BE ATTEMPTED.

STATUS ERROR CODE 2 + 6.

NO

TWO-STAGE OR SINGLE-STAGE THERMOSTAT

CALL FOR HEAT

COMBUSTION AIR INDUCER ON LOW SPEED.

STATUS LED -- HEARTBEAT

CONTINUED ON NEXT PAGE

NO

NO

60-MINUTE LIMIT WATCHGUARD MODE.

GAS VALVE OFF, COMBUSTION AIR INDUCER

OFF, INDOOR BLOWER OFF WITH DELAY.

STATUS ERROR CODE 4 + 5.

YES

NO

YES

SECOND (HIGH) STAGE PRESSURE SWITCH

CONTACTS OPEN?

NO

YES

1

1

If the furnace is operating on continuous fan mode (terminals “R” and “G” are energized), the combustion
air inducer will energize on high speed, the gas valve will energize on second-stage heat and the furnace

will operate on high fire. Furnace will stay on high fire 60 seconds then switch to low fire.

Содержание EL280DF SERIES

Страница 1: ...nual except where noted are recommendations only and do not consti tute code TABLE OF CONTENTS Specifications Page 2 Blower Performance Data Page 3 Parts Identification Page 4 I Unit Components Page 5...

Страница 2: ...2 x 10 Motor output hp 1 3 1 2 1 Tons of add on cooling 2 3 5 3 4 4 5 Air Volume Range cfm 717 1562 917 1929 1517 2760 Electrical Data Voltage 120 volts 60 hertz 1 phase Blower motor full load amps 6...

Страница 3: ...1585 572 1332 489 0 20 1864 717 1745 623 1544 540 1321 463 0 30 1779 683 1676 588 1496 510 1296 440 0 40 1694 647 1600 558 1443 473 1265 417 0 50 1596 607 1502 511 1363 440 1212 393 0 60 1483 577 141...

Страница 4: ...ION Control Box includes integrated control transformer and door switch Secondary Limit Internal Flue Pipe Assembly Gas Val ve Burner Box Assembly Combustion Air Inducer Indoor Blower Heat Exchanger P...

Страница 5: ...pted 4 SureLight Integrated Control A92 EL280DF units are equipped with the Lennox two stage in tegrated SureLight control The system consists of a igni tion blower control figures 5 and 6 with contro...

Страница 6: ...eration flow charts in the back of this manual for more detail DIP Switch Settings Switch 1 Thermostat Selection This unit may be used with either a single stage or two stage thermostat The thermostat...

Страница 7: ...ool ing only TWO STAGE INTEGRATED CONTROL THERMOSTAT CONNECTIONS TB1 1 4 QUICK CONNECT TERMINALS DIP SWITCH FUNCTIONS DIP SWITCHES DIAGNOSTIC LEDs ON BOARD LINKS 1 ERROR CODE RECALL H 24V HUMIDIFIER O...

Страница 8: ...Page 8 INTEGRATED CONTROL FIGURE 6...

Страница 9: ...5 1 Hard lockout Rollout circuit open or previously opened 5 2 Control failed self check internal error control will restart if error recovers 5 3 No Earth ground control will restart if error recove...

Страница 10: ...as Valve The two stage gas valve figure 11 is internally redundant to assure safety shut off If the gas valve must be replaced the same type valve must be used 24VAC terminals and ON OFF switch are lo...

Страница 11: ...Page 11 EL280DF HEATING COMPONENTS FIGURE 7 Ignitor Burners Sensor Gas Valve Manifold and Gas Orifices Rollout Switch...

Страница 12: ...t damage plug Check voltage during 20 second ignitor warm up period Voltage should read 120 volts or 10 If voltage is above or below these values check for correct supply voltage to furnace Test 1 Che...

Страница 13: ...thermostat contacts to cycle system 7 When main burners are in operation for two minutes take reading TABLE 5 Flame Signal in Microamps Normal Low Drop Out 1 9 or greater 1 4 or less 20 FIGURE 9 Measu...

Страница 14: ...f the combus tion air inducer is not operating or if the flue becomes ob structed On heat demand first or second stage the switch senses that the combustion air inducer is operating It closes a cir cu...

Страница 15: ...ove access panel 4 Turn switch on gas valve to OFF Do not force See fig ure 11 5 Replace access panel Failure To Operate If the unit fails to operate check the following 1 Is the thermostat calling fo...

Страница 16: ...on various metals used in gas piping Use of a specialty Gas Leak Detector is strongly recommended It is available through Lennox under part number 31B2001 See Corp 8411 L10 for further details Do not...

Страница 17: ...re adjustment or replacement to ensure proper operation at higher altitudes See table 10 for manifold pressures and table 11 for pressure switch kits and gas conversion kits TABLE 10 Manifold Pressure...

Страница 18: ...E 13 Return Supply TEMPERATURE RISE Supply Duct Temperature Return Duct Temperature _ Temperature Rise C External Static Pressure 1 Tap locations shown in figure 14 2 Punch a 1 4 diameter hole in supp...

Страница 19: ...and unobstructed to provide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or blockage Vent system must be free and cl...

Страница 20: ...e careful with the collector box gas ket If the gasket is damaged it must be replaced to prevent leakage 6 Disconnect gas supply piping Remove the screw se curing the burner box cover and remove cover...

Страница 21: ...bustion air inducer Failure to replace all screws may cause leaks Inspect gaskets for any damage and replace if necessary 15 Reinstall burner box manifold assembly and burner box cover 16 Reconnect al...

Страница 22: ...Page 22 VII Wiring and Sequence of Operation EL280DF Schematic Wiring Diagram...

Страница 23: ...first stage de mand is satisfied OR a second stage heat demand is initiated 6 Second stage heat demand initiated A 30 second sec ond stage recognition period begins 7 The combustion air inducer ramps...

Страница 24: ...DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 1 Heat 1 Cool NOTE Use DIP switch 2 to set sec ond stage heat ON delay OFF10 minutes ON 15 minutes ON Intact Intact S1 T STAT CONTROL TERM STRIP OU...

Страница 25: ...P Switch Settings and On Board Links See figure 6 Wiring Connections DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 2 Heat 2 Cool OFF Cut Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 2 Heat 1...

Страница 26: ...OR T STAT IS CYCLED OFF ON FOR 3 SEC MINIMUM NO YES FIRST LOW STAGE PRESSURE SWITCH CONTACTS OPEN NO GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF CONTROL REMAINS UNTIL PRESSURE SWITCH I...

Страница 27: ...NDS AFTER GAS VALVE OPENS u0 19 microamps GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF STATUS LED HEARTBEAT HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HE...

Страница 28: ...ST STAGE HEAT DEMAND SATISFIED GAS VALVE OFF COMBUSTION AIR INDUCER OFF FOLLOWING POST PURGE INDOOR BLOWER OFF WITH DELAY STATUS LED PULSE YES SECOND STAGE HEAT DEMAND SECOND STAGE HEAT DEMAND REQUIRE...

Страница 29: ...ODE DIP SWITCH SET AT SINGLE YES YES FIRST AND SECOND STAGE HEAT DEMAND SATISFIED SIMULTANEOUSLY STATUS LED HEARTBEAT YES GAS VALVE OFF COMBUSTION AIR INDUCER OFF AFTER 5 SECOND LOW SPEED POST PURGE P...

Страница 30: ...ZED NO IS THERE PROPER GROUND YES NO INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL SPEED AFTER 2 SECOND DELAY FIRST STAGE DEMAND FOR COOL SATISFIED NO THERMOSTAT CALLS FOR SECOND STAGE COOL COMPRESSOR A...

Страница 31: ...TO LOW HEAT SPEED FIRST STAGE HEAT DEMAND SATISFIED YES NO THERMOSTAT CALLS FOR SECOND STAGE HEAT YES INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30 SECOND RECOGNITION PERIOD SECOND STAGE HEAT DE...

Отзывы: