6- Evaluate the heat exchanger integrity by inspecting the

heat exchanger per the AHRI heat exchanger inspec­
tion procedure.  This procedure can be viewed at
www.ahrinet.org. See “Induced-draft Furnace Heat Ex­
changer Inspection Procedure”.

7- Ensure sufficient combustion air is available to the fur­

nace.  Fresh air grilles and louvers (on the unit and in the
room where the furnace is installed) must be properly
sized, open and unobstructed to provide combustion

air

.

8- Inspect the furnace venting system to make sure it is in

place, structurally sound, and without holes, corrosion,
or blockage. Vent system must be free and clear of ob­
structions and must slope upward away from the fur­

nace

.

 Vent system should be installed per the National

Fuel Gas Code

9- Inspect the furnace return air duct connection to ensure

the duct is sealed to the furnace. Check for air leaks on

supply and return ducts and seal where necessary

.

10- Check the condition of the furnace cabinet insulation

and repair if necessary.

11- Perform a complete combustion analysis during the fur­

nace inspection to ensure proper combustion and oper­
ation.  Consult Service Literature for proper combustion
values.

12- Verify operation of smoke detectors and CO detectors

and replace batteries as required.

Perform a general system test. Turn on the furnace to
check operating functions such as the start-up and shut-off
operation.
 1 - Check the operation of the ignition system, inspect

and clean flame sensor. Check microamps before and
after. Check controls and safety devices (gas valve,
flame sensor, temperature limits). Consult Service
Manual for proper operating range. Thermal Limits
should be checked by restricting airflow and not dis­
connecting the indoor blower. For additional details,
please see Service and Application Note H­04­9.

 2 - Verify that system total static pressure and airflow set­

tings are within specific operating parameters.

 3 - Clock gas meter to ensure that the unit is operating at

the specified firing rate. Check the supply pressure
and the manifold pressure. 

If manifold pressure ad­

justment is necessary, consult the Service Literat­
ure for unit specific information on adjusting gas
pressure. Not all gas valves are adjustable

.

 

Verify

correct temperature rise.

Содержание EL180UHNE Series

Страница 1: ...phone in your building D Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions D If you cannot reach your gas supplier call the fire department D Leave the building immediately GAS FURNACE FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exact ly could result in serious injury death or property damage WARNING Improper installation adjustment al...

Страница 2: ...t user Notice to Homeowner This furnace is equipped with safety devices that protect you and your property If one or more of these devices is activated furnace operation will stop If your home is left unattended for an extended period of time equipment op eration must be checked periodically If this is not possible the water supply to the house should be shut off and the pipes should be drained Th...

Страница 3: ...re operating Gas fumes which could contain carbon monoxide can be drawn into the living space resulting in personal injury or death Your furnace is a gas appliance It is critical that the gas supplied to the unit be completely burned to avoid the pro duction of carbon monoxide gas Complete combustion of the gas requires but is not limited to correct gas pressure and gas flow rate adequate combusti...

Страница 4: ... 2 Set the thermostat to the lowest setting 3 Turn off all electrical power to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 Move switch on gas valve to OFF See figure 3 7 Wait five minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier ...

Страница 5: ...ce flue collar at all times For your safety and to fulfill the terms of the limited warranty a licensed professional service technician or equivalent must annually inspect this furnace and its vent system CAUTION To ensure proper operation a licensed professional service technician or equivalent should check the burner flame and conduct a combustion analysis annually Annually before heating season...

Страница 6: ...WARNING Do not use this furnace if any part has been under water A flood damaged furnace is extremely dan gerous Attempts to use the furnace can result in fire or explosion Immediately call a licensed pro fessional service technician or equivalent to in spect the furnace and to replace all gas controls control system parts and electrical parts that have been wet or to replace the furnace if deemed...

Страница 7: ...plete combustion analysis during the fur nace inspection to ensure proper combustion and oper ation Consult Service Literature for proper combustion values 12 Verify operation of smoke detectors and CO detectors and replace batteries as required Perform a general system test Turn on the furnace to check operating functions such as the start up and shut off operation 1 Check the operation of the ig...

Страница 8: ...ller or equivalent service agency or gas supplier Cabinet Parts Access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel Blower housing Motor Motor mounting frame Motor power choke Blower housing cutoff plate Heating Parts Flame sensor Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Ma...

Отзывы: