506228−01 05/09
Page 40
Action to Clear / Recovery
Condition
System Action
Display Text (Screen2)
Display Text (Screen1)
Condition
ERROR MESSAGE
Outdoor Sensor error with
Humiditrol
®
enabled (OR
ODT was used for bal-
ance point control only):
outdoor sensor reads out
of range (−50F to 180F)
NO OUTDOOR SENSOR
REMIND SERVICE
See
REMIND/SERVICE
notes
No Humiditrol or Humidity operation
is run. D terminal stays activated
and other operation will keep work-
ing.
Stat will stop the operation that re-
quires ODT infro i.e. between point
control & stage lock in. Stat will
switch the control to the operation
that does not require ODT informa-
tion.
The display of Outdoor sensor from
HOME will be turned OFF. If user
turns on the display from USER
SETTINGS, this error is displayed
again.
If the outdoor sensor reads a value
out of its normal range. (User can
call the dealer to
replace outdoor
sensor
)
Outdoor Sensor error with
Dew point control enable:
outdoor sensor reads out
of range (−50F to 180F)
NO OUTDOOR SENSOR
REMIND SERVICE
See
REMIND/SERVICE
notes
No Dew point control or Humidity
operation is run. D terminal stays
activated and other operation will
keep working.
Stat will stop the operation that re-
quires ODT infro i.e. between point
control & stage lock in. Stat will
switch the control to the operation
that does not require ODT informa-
tion.
The display of Outdoor sensor from
HOME will be turned OFF. If user
turns on the display from USER
SETTINGS, this error is displayed
again.
If the outdoor sensor reads a value
within its normal range. (User can
call the dealer to
replace outdoor
sensor
)
table continued on next page