ASSEMBLY AND INSTALLATION INSTRUCTIONS

DC40.

Installation instructions
. Separate the cover of the instrument from the bodypart using a screwdriver as shown in Fig. 8.. 
2. Open the instrument with a “hinge” movement, pivoting the cover of the instrument upwards.

Lower view

Fig. 8.

Fig. 8.2

3. Fix the rear part to the wall, taking care that the connection cables pass through the hole in the centre of the rear casing. 
The distances between the fastening holes are designed so as to be able to fit the DC40 to a flush-mounting connection box 

compliant with the CEI C.43 - IEC 670 standards. If this is not available, use the fastening holes on the casing as a guide 

for drilling the holes in the wall, and then use the kit of screws and plugs supplied.

4. Connect the cables to the terminals located in the casing as indicated in the casing itself or in the electrical diagram.

5. Once the installation is complete, fit the terminal onto the casing by pivoting the cover with a “hinge” movement and close it. 
When closing, make sure that the pins on the board fit into the corresponding terminals.

Installation warnings

 

- Disconnect the power supply before working on the DC40 during operations of assembly, maintenance and replacement.

 

-  The terminal must be fastened to the wall in such a way as to allow the circulation of air through the slits on the rear casing.

 

- Avoid installing the boards in environments with the following characteristics:

 

 

- Avoid locations where there is a great variation in room temperature.

 

 

- Near doors leading to the outside.

 

 

- On outside walls.

 

 

- Where it will be exposed to direct sunlight or to conditioned air flow.

 

 

- Where there are strong magnetic and/or radio frequency interference (for example, near transmitting antennae). 

Keep the DC40’s inductive load cables separate from 
those of any power devices (contactors, etc.) in order to 
prevent electromagnetic interference.
Do not lay power and communications cables together

- Run a connection from the electrical box in the outdoor unit to 
the DC40 device: 

      . 91 and 92 terminal blocks respectively to Tx+ and Tx-  

       (Twisted pair for communications).

      . 93 and 94 terminal blocks respectively to GO and G.

       (Twisted pair for 24VAC power). 
      . 90 to GND. (shield).

2 x TWISTED PAIR

SCREEN WIRE AWG20

L.max=100m

 x TWISTED PAIR

SCREEN WIRE AWG20

+ 2 x ,5 mm

2

L.max=200m

Содержание CLIMATIC 40

Страница 1: ...Providing indoor climate comfort CLIMATIC 40 MUL37E 0607 12 2009 Original manual translation User manual ...

Страница 2: ... TERMINAL AIRCOOLAIR MENU REGULATION 1 ECOLEAN 2 AIRCOOLAIR 3 AIRCUBE ADVANCED FUNCTIONS 1 REMOTE ON OFF 2 REMOTE WINTER SUMMER CHANGEOVER 3 DYNAMIC SET POINT 4 BMS COMUNICATIONS 5 TIME BANDS PROGRAM ECOLEAN 6 LOW NOISE 7 ANALOGUE DIGITAL INPUT 8 TIMING AND DELAYS 9 DEFROST 10 CONDENSER FAN SPEED CONTROL 11 FREE COOLING PARAMETERS SAFETY DEVICES INSTRUCTIONS FOR ASSEMBLY AND INSTALLATION ALARMS ...

Страница 3: ...nt evaporator tem perature pressure condenser and outdoor temperature probes optional Proportional regulation based on remote ambient return temperature cooling heating and automatic mode Defrost cycle heat pump units with pres sure tranducer Condensing pressure control with tempe rature probe or pressure transducer Antifreeze high and low pressure protections Compressors indoor and o utdoor fans ...

Страница 4: ...de Request BUTTON DESCRIPTION TIME Go up a sub group inside the programming area Press once Access the direct parameters Press for 5 s Select item inside the programming area confirm changes to the parameters Press once Program parameters afters entering password Press for 5 s Select top item inside the programming area Press once Increase value Press once Switch from standby to heat pump mode and...

Страница 5: ... in cooling or heating mode in order to change the operating mode you first have to turn the unit off and only then can you turn it on in the operating mode you want 1 1 3 SELECTING THE WATER TEMPERATURE OF THE SYSTEM To modify unit s working set point you have to change parameter r1 cool set point or parameter r3 heat set point To see how to change a parameter see chapter 3 MENU SETTINGS AND OPER...

Страница 6: ... and vice versa Change operating mode cooling heating automatic Switch the indoor fan from automatic mode to always ON and vice versa ActivateS deactivateS the sleep mode ActivateS deactivateS the time bands ShowS the set point when the unit is OFF Set the temperature BUTTON BUTTON PRESS FUNCTION 3 seconds Sets sleep differential value of the current operating mode 3 seconds Sets the time bands ho...

Страница 7: ...sday 2 etc 6 Set the day by using the buttons 7 Press the button to accept 3 1 TURN ON OFF THE UNIT WITH REMOTE CONTROL DC40 AIRCOOLAIR 3 2 SELECTING THE UNIT S OPERATING MODE Once the unit is turned on you can select Cooling Heating or Automatic mode just pressing the Mode button In the automatic mode you just choose the set point and the system automatically switches from cooling to heating mode...

Страница 8: ...Enter time bands menu b Set 1ST time band for weekday start hour c Accept d Set 1ST time band of weekday start minutes e Accept f Set 1ST time band of weekday set point on off tem perature g Accept h Repeat steps b c d e f g to programme 2nd time band for weekdays i Repeat steps b c d e f g h to programme the two time bands for weekends Weekdays Time band 1 flashing Flashing Flashing Flashing Time...

Страница 9: ... appears on the display Move inside the menu as explained below 1 sec 5 sec B SETPOINT SETTINGS AND OPERATING HOURS DISPLAY MENU C PARAMETERS EDITING MENU a Press Pgr and Sel at the same time for 5 seconds c Press Sel to accept d Press Sel to enter parameters Editing menu Go up a sub group inside the programming area UP or increase valve Down or decrease valve Go down a sub group or accept paramet...

Страница 10: ...pe up to the main menu to save it otherwise modifications will be cancelled c If no operations are performed on the keypad for 60 seconds the controller exits the parameter editing menu on timeout and any changes are cancelled MENU TREE PROBES SETTINGS ATIFREEZE AND ELECTRICAL HEATER PROBES COMPRESSORS DEFROST FANS UNIT SETTING ALARMS REGULATION TIMER SETTING SOFTWARE ...

Страница 11: ...M STEP 2 STEP 1 Unit 2 CM Ambient or return air duct temperature is thermostatically controlled via set point and tolerance range differential as shown in the following diagrams 2 1 AUTOMATIC MODE Heat pump 2 2 AUTOMATIC MODE Cooling only Electrical heater 2 3 AFFECTED PARAMETERS 3 AIRCUBE Aircube is regulated by digital input see section 7 advanced functions for more details HEAT COOL HEAT COOL I...

Страница 12: ...ctivate this function set parameter H06 1 3 DYNAMIC SET POINT With this function which needs to incorporate an additional outdoor temperature probe it s possible to adjust the set point dynamically based on ambient temperature The set point value can be increased or decreased when the external conditions are more advantageous thus achieving extra energy saving Dynamic set point must be activated i...

Страница 13: ...e units Aircoolair units don t need the converter it s integrated but they do need the ambient or duct remote sensor option 5 TIME BANDS PROGRAM Ecolean The Climatic 40 controller allows 2 time bands to be programmed for each day each with a different set point The setting parameters are explained in the following table For further information please see BMS communication manual EXAMPLE Cooling WA...

Страница 14: ...C 1003 1103 1303 1403 1604 1804 SM ANCM 112D 128D 152D KSCM 112D 128D 152D 214D NOTE Optional kits could change probes settings PROBE Ambient temperature Inlet water temperature Return or remote ambient temperature Outlet water temperature 1st Circuit evaporator temperature 1st Circuit condenser temperature Outdoor temperature 1st Circuit condenser temperature Outdoor temperature 1st Circuit conde...

Страница 15: ...n both heating and cooling modes the compressors start 150 seconds after the water pump has started in order to stabilize the water system In addition to that the water pump stops 4 minutes after the last compressor has stopped in order to take advantage of the remaining thermal energy in the exchanger Compressor Water pump 240 s 150 s DIGITAL INPUT Flow switch Termal overload fan ON OFF Cool Heat...

Страница 16: ...At first there is a by pass during the first 150 seconds of water pump operation which operates according to the water flow switch signal When the alarm has been activated the water pump is stopped The water pump starts again every 90 seconds for 150 seconds in order to try to reset the alarm This procedure is repeated 5 times and after that the pump remains stopped until the alarm is reset manual...

Страница 17: ...he fan FAN SPEED CONDENSER TEMPERATURE ºC NOTA At start up the fan works at maximum speed for 20 seconds so as to overcome the mechanical inertia of the motor The same time is observed with regard to compressor start up irrespective of the condensing temperature in order to improve temperatures probes reading 1 3 ON OFF CONTROL BASED ON PRESSURE Models ECOLEAN EAR 1003 1804 SM AIRCOOLAIR ANHM 112D...

Страница 18: ... air to achieve the comfort setpoint The illustration below shows freecooling regulation With free cooling Open air damper Close air damper Without freecooling Stop air damper Ambient temperature ºC Ambient temperature ºC OPTION To get a constant air renewal when freecoling conditions are satisfied the damper is mantained opened partially 20 according to the following values Par DESCRIPTION Min Ma...

Страница 19: ...lative set point 1st step Auxiliary heater differential Auxiliary heater absolute set point 2st step Auxiliary heater relative set point 1st step Lower discharge air temperature in freecooling Probes Config of probe to be shown on the display 0 probe B1 1 probe B2 2 probe B3 3 probe B4 4 probe B5 5 probe B6 6 probe B7 7 probe B8 8 Set point without compensation 9 Dynamic set point with possible co...

Страница 20: ... ON 1 Depending on compressor in parallel operating mode 2 Depending on compressors in ON OFF control 3 Depending on compressors in speed control mode Temp value for min speed cooling Pressure value for min speed cooling 20 if F2 3 22 if F2 2 20 if F2 3 22 if F2 2 20 if F2 3 22 if F2 2 Differential value for max speed in cooling mode temp Differential value for max speed in cooling mode pres Fan s...

Страница 21: ... UD BY DEFAULT ECOLEAN AIRCOOLAIR AIRCUBE Regulation Cooling set point Differential in cooling mode Heating set point Differential in heating mode Dead zone Cooling compensation constant Maximum distance from the set point Start compensation temerature in cooling mode Start compensation temerature in heating mode Second cooling set point Second heating set point Select automatic change over probe ...

Страница 22: ... temperature reaches 8ºC in standard unit LOW WATER TEMPERATURE ALARM ECOLEAN The unit is protected by means of a temperature probe located in the indoor piping when the indoor temperature goes drops 2ºC WITHOUT FREECOOLING The compressors shut down and the antifreeze alarm goes on The alarm is reset automatically when the temperature reaches 7ºC WITH FREECOOLING Air intake gate closes Once the ga...

Страница 23: ...n the board fit into the corresponding terminals Installation warnings Disconnect the power supply before working on the DC40 during operations of assembly maintenance and replacement The terminal must be fastened to the wall in such a way as to allow the circulation of air through the slits on the rear casing Avoid installing the boards in environments with the following characteristics Avoid loc...

Страница 24: ...DT41 power supply and the DC41 terminal using the telephone cable 80 cm supplied If the cable is not long enough use a pin to pin telephone cable with a maximum length of 10 m Fig 8 3 Fig 8 4 Thelefone cable Max L 200m AWG20 Keep the DC41 s inductive load cables separate from those of any power devices contactors etc in order to prevent electromagnetic interference Do not lay power and communicati...

Страница 25: ...40 display alternately with the main menu Only in Aircoolair units an alarm code different from the one for the Climatic 40 being shown on the DC40 display alternately with the main menu A red bell appears on the Climatic 40 display and the alarm relay is activated contacts 99 100 In some cases depending on the type of alarm some of the outputs may be blocked thus stopping the unit The activation ...

Страница 26: ...e unit Ecolean only After 5 minutes it automatically requires to be reset manually Unit stops AUTO MAN Check water circuit is not blocked Check water filter Check water pump operation Not used Call Technical Service B1 probe error Faulty probe or connection Unit stops AUTO Check connection of B1 probe see electrical diagram check continui ty and change the faulty component B2 probe error Faulty pr...

Страница 27: ...er supply warning Power supply 20 4V AUTO Check power supply of controller 24V see electrical diagram High power supply warning Power supply 26 4V Unit stops AUTO Check power supply of controller 24V see electrical diagram Not used Call Technical Service Not used Call Technical Service Not used Call Technical Service Not used Call Technical Service Not used Call Technical Service Not used Call Tec...

Страница 28: ...RAMETERS EDITING MENU entering the password 44 instead of 22 Up to 25 events can be saved highlighting in order event code start hours start minutes start day start month end hours end minutes end day end month WARNING The alarm log is active and operative only if the clock board is fitted If there are no alarms saved noH is displayed EVENT CODE START MONTHS END MONTHS START HOURS START MINUTES ST...

Страница 29: ...28 NOTES ...

Страница 30: ...29 NOTES ...

Страница 31: ...30 NOTES ...

Страница 32: ...going commitment to quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Installation and service must be performed by a qualified installer and servicing agency MUL37E 0607 12 2009 Original manual translation BELGIUM LUXE...

Отзывы: