NOTE

 – 

When the coil is connected directly with a con-

densing furnace, the coil must be level from return end to 

supply end. The front (access side) of the furnace may be 

pitched downward up to 1 inch to accommodate a ½-inch 

pitched coil.

 

3 -  Secure the supply duct to the coil cabinet. 
4 -   

Refer to the instructions provided with the 

condensing unit for leak testing, evacuating and 

charging procedures. 

Always check the entire 

system for leaks before charging.

 

5 -   

Applications using CHX35-60 D-width unit with 

C-width furnace

 – Figure 2 shows an application 

that includes a D-width coil and a C-width furnace. 

This application requires construction of an 

insulated, field-supplied block-off plate to cover the 

open space on the coil housing

SUPPLY AIR UNIT

FRONT

PLUMBING

CONNECTIONS

SUPPLY AIR

UNIT REAR

TEST HOLE

AIR FLOW

FIELD

FABRICATED

INSULATED BLOCK-

OFF PLATE

FIGURE 2. D-Width Coil with C-Width Furnace 

 

(Top View)

SUPPLY AIR UNIT FRONT

PLUMBING

CONNECTIONS

SUPPLY AIR UNIT REAR

AIR FLOW

TEST HOLE

SLOPE 1/2”

(13 MM)

90% GAS FURNACE

DRAIN

COIL DRAIN

SUPPLY AIR UNIT

FRONT

BACK

COIL

(SUPPLY AIR END VIEW)

AIR

FLOW

FIGURE 3. Left-Hand Air Discharge

COIL

FRONT

NOTE - Use of this orientation is acceptable for 80% AFUE furnaces.

Do not use this orientation for 90% condensing furnaces.

(SUPPLY AIR END VIEW)

SUPPLY AIR UNIT FRONT

PLUMBING CONNECTIONS

SUPPLY AIR UNIT REAR

TEST HOLE

SLOPE 1/2”

(13 MM)

COIL

DRAIN

SUPPLY AIR UNIT

SUPPLY AIR

UNIT FRONT

COIL

AIR FLOW

(Top View)

AIR

FLOW

FIGURE 4. Right-Hand Air Discharge

FIELD-PROVIDED SPACER

(6 IN.)

COIL

BACK

FRONT

SUPPLY AIR UNIT FRONT

PLUMBING CONNECTIONS

SUPPLY AIR UNIT REAR

TEST HOLE

SLOPE 1/2”

(13 MM)

COIL DRAIN

SUPPLY AIR

UNIT FRONT

(TOP VIEW)

AIR FLOW

90% GAS FURNACE

DRAIN

(SUPPLY AIR END VIEW)

AIR

FLOW

FIGURE 5. Right-Hand Air Discharge with Spacer

Содержание CHX35 Series

Страница 1: ...ts for shipping damage if found im mediately contact the last carrier INSTALLATION INSTRUCTIONS INDOOR COILS 507835 01 067198001 4 2018 CHX35 Series Coils General Information CHX35 horizontal evaporat...

Страница 2: ...3 8 3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14...

Страница 3: ...et to the drain Position the coil in the left to right configuration on the service access side of the furnace Insert a field provided spacer between the furnace and the coil Use field provided screws...

Страница 4: ...NIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE FIGURE 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR FLOW TEST...

Страница 5: ...brazing rod 5 or 6 percent silver alloy for copper to copper connections or 45 percent silver al loy for copper to brass or copper to steel connections Before making brazed connections place a field...

Страница 6: ...uld be properly sized and installed according to the ASHRAE Standard Manual D The supply and return air duct systems should be designed for the cfm and static requirements of the job Consult the blowe...

Страница 7: ...lations Blower Speed Selection Proper air volume must be provided over the evaporator coil Select a blower motor speed tap that will provide 400 50 CFM per 12 000 Btuh of cooling capacity wet coil A s...

Страница 8: ...the distributor lines are not rubbing together or kinked All tubes must have enough clearance from other metal parts Use wire ties to secure tubes to prevent movement that could cause the refrigerant...

Отзывы: