background image

Page 8

CLEANING THE COIL 

1 -   Remove the coil from the cabinet or plenum, and 

take the coil to an appropriate place to clean it. 

2 -   

Vacuum or brush the coil to remove matted 

and  surface  debris  from  the  fins.  Use  vacuum 

attachments and /or brushes that are non-

destructive to fins. 

3 -   If oil deposits are present, spray the coil with a mild 

coil cleaner with a pH in the range of 5 to 9 to soften 

deposits. Do not leave the coil cleaner on the coil 

for more than 10 minutes. Flush the coil thoroughly 

with potable water. 

4 -   Spray the coil at a vertical angle of 30 to 45 degrees 

with a constant stream of water at moderate 

pressure. A pressure washer with a fan nozzle will 

work best. Do not spray the coil from a horizontal 

direction. 

5 -   Direct the spray so that any debris is washed out of 

the coil. For most residential units, hot water is not 

necessary. 

NOTE -

 

Attempting to back flush from the inside of the coil 

will require removing parts from the unit, and it may be 

very difficult to flush the whole coil surface. Attempting to 

blow water through a coil will slow the water stream and 

reduce the flushing action of the outer fin surface.

 

6 -   Replace the coil into the cabinet or plenum. Ensure 

that you have followed the proper procedure for 

routing and securing the refrigerant tubing.

 IMPORTANT

Ensure that the distributor lines are not rubbing together 

or kinked. All tubes must have enough clearance 

from other metal parts. Use wire ties to secure tubes 

to prevent movement that could cause the refrigerant 

tubing to fail. 

6 -   

When the required draft gauge readings are 

obtained, remove the draft gauge lines and insert 

snaphole plugs into the test holes. 

TABLE 2. Air Volume / Static Pressure Drop Across Coil

Cabinet

Vol: CFM

Drop: in. w.g.

CHX35

Model

Width in.

Dry

Wet

-18A-2F

14-1/2

600

.09

.11

-24A-2F

-24B-2F

14-1/2

17-1/2

800

800

.15

.09

.19

.11

-30A-2F

-30B-2F

14-1/2

17-1/2

1000

1000

.24

.14

.27

.16

-36A-2F

-36B-2F

-36C-F

14-1/2

17-1/2

21

1200

1200

1200

.30

.16

.15

.39

.21

.18

-42B-2F

-42C-2F

14-1/2

17-1/2

1400

1400

.26

.18

.31

.21

-48B-2F

17-1/2

1400

.25

.29

-48C-2F

21

1600

.27

.30

-51C-2F

21

1600

.25

.29

-60D-2F

24-1/2

2000

.24

.30

Maintenance 

NOTICE !

Failure to follow instructions will cause damage to 

the unit.
This unit is equipped with an aluminum coil. Alu-

minum coils may be damaged by exposure to solu-

tions with a pH below 5 or above 9. The aluminum 

coil should be cleaned using potable water at a mod-

erate pressure (less than 50psi). If the coil cannot 

be cleaned using water alone, Lennox recommends 

use of a coil cleaner with a pH in the range of 5 to 9. 

The coil must be rinsed thoroughly after cleaning.

A trained technician or service agency must perform main-

tenance and service on equipment. At the beginning of 

each heating or cooling season, indoor coils should be 

inspected to determine whether the coil requires cleaning. 

Содержание CHX35 Series

Страница 1: ...ts for shipping damage if found im mediately contact the last carrier INSTALLATION INSTRUCTIONS INDOOR COILS 507835 01 067198001 4 2018 CHX35 Series Coils General Information CHX35 horizontal evaporat...

Страница 2: ...3 8 3 8 3 8 3 8 Condensate drain fpt in 3 4 3 4 3 4 3 4 3 4 Evaporator Coil Net face area sq ft 1 75 3 5 3 5 4 33 4 67 Tube diameter in 3 8 3 8 3 8 3 8 3 8 Number of rows 2 3 2 3 3 Fins per inch 18 14...

Страница 3: ...et to the drain Position the coil in the left to right configuration on the service access side of the furnace Insert a field provided spacer between the furnace and the coil Use field provided screws...

Страница 4: ...NIT REAR TEST HOLE AIR FLOW FIELD FABRICATED INSULATED BLOCK OFF PLATE FIGURE 2 D Width Coil with C Width Furnace Top View SUPPLY AIR UNIT FRONT PLUMBING CONNECTIONS SUPPLY AIR UNIT REAR AIR FLOW TEST...

Страница 5: ...brazing rod 5 or 6 percent silver alloy for copper to copper connections or 45 percent silver al loy for copper to brass or copper to steel connections Before making brazed connections place a field...

Страница 6: ...uld be properly sized and installed according to the ASHRAE Standard Manual D The supply and return air duct systems should be designed for the cfm and static requirements of the job Consult the blowe...

Страница 7: ...lations Blower Speed Selection Proper air volume must be provided over the evaporator coil Select a blower motor speed tap that will provide 400 50 CFM per 12 000 Btuh of cooling capacity wet coil A s...

Страница 8: ...the distributor lines are not rubbing together or kinked All tubes must have enough clearance from other metal parts Use wire ties to secure tubes to prevent movement that could cause the refrigerant...

Отзывы: