Page 12
504719M 09/05
Table 8
CB29M−51 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
External Static Pressure
Low
Medium
High
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
1590
750
665
1790
845
805
2055
970
1005
.05
10
1570
740
660
1770
835
790
2035
960
995
.10
25
1555
735
655
1750
825
785
2005
945
980
.15
35
1530
720
645
1730
815
775
1980
935
970
.20
50
1510
710
640
1710
805
765
1945
920
955
.25
60
1485
700
635
1685
795
755
1915
905
940
.30
75
1460
690
625
1660
785
745
1885
890
930
.40
100
1415
670
615
1610
760
725
1820
860
900
.50
125
1370
645
600
1550
730
705
1750
825
875
.60
150
1310
620
580
1490
705
685
1670
790
845
.70
175
1240
585
560
1405
665
660
1575
745
820
.75
185
1210
570
550
1360
640
645
1520
720
800
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
Table 9
CB29M−51 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
External Static Pressure
Low
Medium
High
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
1695
800
680
1900
895
805
2140
1010
965
.05
10
1675
790
670
1880
885
795
2110
995
950
.10
25
1655
780
665
1855
875
780
2080
980
935
.15
35
1640
775
655
1830
865
770
2050
970
920
.20
50
1620
765
650
1805
850
755
2025
955
910
.25
60
1595
750
640
1775
840
740
1995
940
895
.30
75
1570
740
630
1750
825
730
1965
925
885
.40
100
1525
720
610
1700
805
710
1905
900
860
.50
125
1475
695
595
1640
775
685
1845
870
835
.60
150
1420
670
575
1585
750
665
1770
835
805
.70
175
1355
640
555
1515
715
640
1700
800
780
.80
200
1290
610
535
1450
685
620
1625
765
755
.85
210
1255
590
525
1405
665
610
1595
750
745
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
Table 10
CB29M-65 Blower Performance (208/230v)
External Static
Air Volume and Motor Watts at Specific Blower Taps
External Static
Pressure
Low
Medium−Low
Medium
Medium−High
High
in.w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
1570
740
575
1800
850
700
2005
945
825
2135
1005
930
2245
1060
1080
.05
10
1550
730
570
1780
840
690
1980
935
815
2110
995
925
2220
1050
1070
.10
25
1530
725
560
1760
830
680
1950
920
805
2080
985
915
2190
1035
1060
.15
35
1520
715
560
1735
820
670
1930
910
795
2055
970
905
2165
1020
1050
.20
50
1495
705
550
1710
805
660
1910
900
790
2025
955
895
2135
1010
1040
.25
60
1475
695
545
1690
795
655
1880
890
780
1995
940
885
2105
995
1030
.30
75
1460
690
540
1670
785
650
1855
875
770
1965
930
875
2075
980
1020
.40
100
1415
670
530
1615
760
630
1795
850
750
1910
900
855
2005
945
995
.50
125
1370
645
520
1560
735
615
1735
820
730
1850
875
835
1935
910
975
.60
150
1310
620
505
1495
705
595
1670
790
710
1780
840
810
1855
875
950
.70
175
1250
590
490
1425
675
575
1600
755
690
1705
805
785
1780
840
925
.80
200
1175
555
470
1360
640
560
1520
715
665
1620
765
755
1685
795
900
.90
225
1025
485
440
1280
605
545
1420
670
645
1520
715
725
1595
750
875
.95
235
- - - -
- - -
- - - -
1240
585
535
1365
645
630
1460
690
705
1545
730
860
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.