Page 15
CB29M/CB30M SERIES
Table 17
CB30M-51 Blower Performance (208/230V)
Air Volume and Motor Watts at Specific Blower Taps
External Static Pressure
Low
Medium
High
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
1475
695
430
1785
845
520
1910
900
590
.05
10
1480
700
430
1770
835
515
1895
895
585
.10
25
1475
695
425
1750
825
510
1870
880
580
.15
35
1465
690
420
1720
810
500
1840
865
570
.20
50
1445
680
410
1685
795
490
1800
850
565
.25
60
1415
670
405
1645
775
480
1755
830
550
.30
75
1380
650
395
1600
755
465
1700
805
540
.40
100
1290
610
370
1485
700
440
1580
745
515
.50
125
1170
550
345
1350
635
410
1425
675
485
.60
150
1020
480
320
1190
560
380
1250
590
450
.70
175
840
395
295
1000
470
350
1045
495
415
.75
185
740
350
280
900
425
335
930
440
400
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
Table 18
CB30M-51 Blower Performance (460V − 1 ph)
Air Volume and Motor Watts at Specific Blower Taps
External Static Pressure
Low
High
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
1775
835
530
1870
885
610
.05
10
1775
835
530
1875
885
610
.10
25
1765
835
515
1870
880
590
.15
35
1750
825
510
1850
875
585
.20
50
1720
815
500
1825
860
575
.25
60
1685
795
490
1790
845
560
.30
75
1645
775
480
1745
825
545
.40
100
1530
720
450
1625
765
505
.50
125
1380
650
420
1465
690
470
.60
150
1195
565
385
1270
600
425
.70
175
975
460
350
1030
485
385
.80
200
720
340
320
755
355
340
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.
Table 19
CB30M-65 Blower Performance (208/230V)
External Static Pressure
Air Volume and Motor Watts at Specific Blower Taps
External Static Pressure
Low
Medium
High
in. w.g.
Pa
cfm
L/s
Watts
cfm
L/s
Watts
cfm
L/s
Watts
.00
0
1775
835
585
2025
955
670
2115
995
780
.05
10
1775
835
590
2010
950
665
2100
990
770
.10
25
1770
835
580
1995
940
655
2085
985
765
.15
35
1760
830
570
1975
930
645
2060
970
750
.20
50
1745
825
560
1950
920
635
2030
960
740
.25
60
1725
815
550
1915
905
625
2000
945
730
.30
75
1695
800
535
1880
885
610
1960
925
715
.40
100
1630
770
505
1795
845
580
1870
880
685
.50
125
1540
725
475
1690
795
545
1755
830
655
.60
150
1425
675
440
1560
735
515
1620
765
625
.70
175
1295
610
410
1415
670
480
1465
690
590
.80
200
1140
535
375
1250
590
445
1290
610
560
.85
210
1050
495
360
1160
550
425
1195
565
545
NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.