background image

Page 8 of 24

506468-01

Issue  1946

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

LIQUID LINE SERVICE VALVE

LIQUID LINE

BRAZE LINE SET

Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set.

Cloths must remain water-saturated throughout the brazing and cool-down process.

WATER-SATURATED

CLOTH

IMPORTANT  — 

Allow  braze  joint  to  cool.  Apply

additional  water-saturated cloths to help cool brazed

joint.  Do  not  remove  water-saturated  cloths  until

piping  has  cooled.  Temperatures  above  250ºF  will

damage valve seals.

6

VAPOR LINE

WATER-SATURATED

CLOTH

VAPOR LINE

 SERVICE VALVE

After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both

services valves to cool piping. Once piping is cool, remove all water-saturated cloths.

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

PREPARATION FOR NEXT STEP

7

WRAP SERVICE VALVES

To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use

additional water-saturated cloths underneath the valve body to protect the base paint.

4

FLOW NITROGEN

Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and

out of the vapor valve stem port. See steps 

3A, 3B 

and 

3C

 on manifold gauge set connections.

5

WARNING

FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE

may result if you do not wrap a water-saturated cloth around

both liquid and suction line service valve bodies and copper

tube  stub  while  brazing  the  line  set!  The  braze,  when

complete, must be quenched with water to absorb any

residual heat.

Do not open service valves until refrigerant lines and

indoor coil have been leak-tested and evacuated. Refer

to Leak Test and Evacuation section of this manual.

WARNING

While protecting the 

service valve seals with 

water-saturated cloths, 

ensure that water does 

NOT enter the system.

Содержание Allied Air Enterprises BHP16L

Страница 1: ...l as well as the instructions supplied in separate equipment before starting the installation Observe and follow all warnings cautions instructional labels and tags Failure to comply with these instru...

Страница 2: ...when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment Locate unit away from wi...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...Size 12 ft 25 ft 50 ft 75 ft 100 ft 24 000 3 4 7 8 3 4 7 8 7 8 36 000 7 8 7 8 7 8 7 8 1 1 8 48 000 7 8 7 8 7 8 1 1 8 1 1 8 60 000 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 For lines longer than 50 ft refer to lo...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...e 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adju...

Страница 14: ...he compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike...

Страница 15: ...rost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second compressor delay feature known as the quiet shift must be deactivated during any unit performance testing The feature...

Страница 16: ...e will be initiated after 30 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable syste...

Страница 17: ...n system 3 Improper metering device installed or incorrect operation of metering device 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coil...

Страница 18: ...Page 18 of 24 506468 01 Issue 1946 24V No 24V...

Страница 19: ...he control board without experiencing nuisance alerts Thermostat Wiring The diagnostic module requires a thermostat demand signal to operate properly See Figure 6 for connections The thermostat signal...

Страница 20: ...mer is overloaded 2 Low line voltage contact utility if voltage at disconnect is low Check wiring conditions Table 7 Diagnostic Module Codes Mis wired Module Troubleshooting Mis wired Module Indicatio...

Страница 21: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 22: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Страница 23: ...506468 01 Page 23 of 24 Issue 1946 Figure 9 Two Stage Wiring Diagram 24 36 48 Models Only...

Страница 24: ...Page 24 of 24 506468 01 Issue 1946 Figure 10 Two Stage Wiring Diagram 60 Model Only...

Отзывы: