background image

Page 12 of 24

506468-01

Issue  1946

Electrical Wiring

All  field  wiring  must  be  done  in  accordance  with  the 

National Electrical Code (NEC) recommendations, 

Canadian Electrical Code (CEC) and CSA Standards, or 

local codes, where applicable.

Electrical Shock Hazard! 

Turn OFF electric power before connecting 

unit, performing any maintenance or 

removing panels or doors. More than one 

disconnect may be required to turn off all 

power.

FAILURE TO DO SO COULD RESULT IN 

BODILY INJURY OR DEATH.

 WARNING

Unit must be grounded in accordance with national and 

local codes. Failure to ground unit properly can result in 

personal injury or death.

 WARNING

Line voltage is present at all components when unit is 

not in operation on units with single pole contactors. 

Disconnect all remote electric power supplies before 

opening access panel. Unit may have multiple power 

supplies. Failure to disconnect all power supplies could 

result in personal injury or death.

 WARNING

Refer to the furnace or blower coil Installation Instructions 

for additional wiring application diagrams and refer to unit 

rating plate for minimum circuit ampacity and maximum 

overcurrent protection size.

1.  Install line voltage power supply to unit from a properly 

sized disconnect switch. Any excess high voltage field 

wiring should be trimmed or secured away from the 

low voltage field wiring.

2.  Ground unit at unit disconnect switch or to an earth 

ground. To facilitate conduit, a hole is in the bottom 

of the control box. Connect conduit to the control box 

using a proper conduit fitting. Units are approved for 

use only with copper conductors. 24V Class II circuit 

connections are made in the low voltage junction box. 

A complete unit wiring diagram is located inside the 

unit control box cover.

3.  Install room thermostat according to thermostat 

installation instruction and on an inside wall that is 

not subject to drafts, direct sunshine, or other heat 

sources.

4.  Install low voltage wiring from outdoor to indoor unit 

and from thermostat to indoor unit (see Figure 6).

5.  Do not bundle any excess 24V control wire inside 

control box. Run control wire through installed wire tie 

and tighten wire tie to provide low voltage strain relief 

and  to  maintain  separation  of  field-installed  low  and 

high voltage circuits.

1 Refer to thermostat installation instructions

2 If applicable

3 Refer to indoor unit installation instructions

4 “L” is used for any accessories (e.g. diagnostic / 

warning / alarm), used to activate thermostat 

warning light

W / W1 / W2 / W3 are auxiliary heat 

(supplemental to heat pump).
“E” is emergency heat (disables heat pump).

NOTES:

W3

W2

R

R

R

C

C

C

W1

W/

W1

W1

Auxiliary Heat

(Heat Pump)

G

G

Indoor Blower Only

O

O

Heat Pump

Y2

Y2

Thermostat

Indoor Unit

Outdoor Unit

E

L

L

B

Y1

Compressor / 1st Stage

Y1

4

1

2

3

1 2

3

1 2

1

1

Not Used

L

Auxiliary Heat

(Heat Pump)

Compressor / 2nd Stage

Figure 6. Thermostat Designations -  

Non-Communicating

Содержание Allied Air Enterprises BHP16L

Страница 1: ...l as well as the instructions supplied in separate equipment before starting the installation Observe and follow all warnings cautions instructional labels and tags Failure to comply with these instru...

Страница 2: ...when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment Locate unit away from wi...

Страница 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Страница 4: ...Size 12 ft 25 ft 50 ft 75 ft 100 ft 24 000 3 4 7 8 3 4 7 8 7 8 36 000 7 8 7 8 7 8 7 8 1 1 8 48 000 7 8 7 8 7 8 1 1 8 1 1 8 60 000 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 For lines longer than 50 ft refer to lo...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Страница 13: ...e 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adju...

Страница 14: ...he compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike...

Страница 15: ...rost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second compressor delay feature known as the quiet shift must be deactivated during any unit performance testing The feature...

Страница 16: ...e will be initiated after 30 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable syste...

Страница 17: ...n system 3 Improper metering device installed or incorrect operation of metering device 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coil...

Страница 18: ...Page 18 of 24 506468 01 Issue 1946 24V No 24V...

Страница 19: ...he control board without experiencing nuisance alerts Thermostat Wiring The diagnostic module requires a thermostat demand signal to operate properly See Figure 6 for connections The thermostat signal...

Страница 20: ...mer is overloaded 2 Low line voltage contact utility if voltage at disconnect is low Check wiring conditions Table 7 Diagnostic Module Codes Mis wired Module Troubleshooting Mis wired Module Indicatio...

Страница 21: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 22: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Страница 23: ...506468 01 Page 23 of 24 Issue 1946 Figure 9 Two Stage Wiring Diagram 24 36 48 Models Only...

Страница 24: ...Page 24 of 24 506468 01 Issue 1946 Figure 10 Two Stage Wiring Diagram 60 Model Only...

Отзывы: