14

The centre of the board also houses a jumper J3, which must be set on the position shown in the electrical

diagram supplied with the unit (between ID COM and INT).

When the jumper is positioned in any other position, the display shows several alarms; therefore, check this jumper

when this is repeated.

ALARM CODES

The unit self-protects through safety devices, when any of these safety devices detect an anomaly, it is shown in

the display in order to advise the installer.

The activation of an alarm brings about:

- The display of the alarm code and the letters "AL", alternating with the display of the temperature

- The blocking of some or all the outputs, depending on the type of alarm.

When more than one alarm is activated at the same time, the display automatically scrolls through the active alarms.

VIS (Visualization): It indicates the type of alarm shown on the display.

RE (Reset): Type of reset.

AUT: AUTOMATIC RESET:

 Some alarms are automatically reset, when the cause is no longer present, they

disappear from the display.

MAN: MANUAL RESET: 

Pressing RESUME button, for more than 5 seconds or set the unit on OFF mode and

then set on ON mode again.

If the alarm conditions have been removed, the instrument returns to the normal operation and the alarm relay is

de-energised. If on the other hand, the alarm conditions persist, then call for technical service.

DESCRIPTION

This alarm may indicate the following problems:

- High pressure switch protection.

- Compressor internal protection open.

- Outdoor  fan internal protection open.

Indicates that unit is working at indoor temperatures

higher than 32ºC, or ambient probe is faulty.

VIS.

E ID

HI T

LO T

RE

MAN

HR F

MAN

The number of operating hours of the supply fan

exceeds the maintenance threshold set by parameter

F4.

 th f

Indoor fan protection open or disconnected.

ES R Terminal does not receive data communication from

the power board.

ES T Power board does not receive data communication from

the terminal

E 1

Temperature regulation probe error, or connection cable

broken.

E 3

E DF The defrost process has exceeded the maximum

time specified of 10 minutes and has not ended.

Outdoor coil temperature probe error, or connection

cable broken.

MAN

AUT

AUT

AUT

AUT

AUT

L OP

Low pressure protection.

After three automatic resets in one hour, becomes

to be a manual reset.

MAN

EFFECTS

ACTION

Alarm

visualization

Alarm

visualization

The unit can operate in this situation only for short

periods of time. If this situation remains, check or

change  the probe and correct hot  air stratification,

inlet outside cold air etc...

These protections are manual reset. Press the

"RESUME" button for 5 seconds, until alarm

disappear. If the alarm shows up again check

continuity of the protections and check or change

the faulty component.

Indicates that unit is working at indoor temperatures

lower than 10ºC, or ambient probe is faulty.

Turn off power supply and turn on again.

If the problem persists, must proceed to change

components.

NOTE: This alarm could be caused by a faulty

shielded cable connection  (induction) or be too long.

Check probe connections and check the cable

Unit will stop

Unit will stop

Unit will stop

Unit will stop

Unit will stop

Unit will stop

Check the position of jumper J1, shown on page 15,

check the cable

Alarm

visualization

Exists a problem of installation (ducts) or cooling

circuit (faulty refrigerant charge), the drain is

obstructed, or ice has been accumulate.

When the alarm shows continuously, and the alarm

persists, reset with "RESUME" button.

Check refrigerant charge, clean the air filters and

the rotation of indoor fan.

This protection is manual reset. Press the "RESUME"

button for 5 seconds, until alarm disappear. If the

alarm shows up again check continuity of the

protection and check or change the faulty component.

Air filter should be changed and reset parameter F3

(reset to 0 valve), press simultaneously the "set"

button, with    and   front buttons

EE

EPROM error.

E 2

Outdoor temperature probe error, or connection cable

broken. (freecooling option, heat pump).

AUT

Unit will stop

Check the outdoor probe connection and jumpers

situation according to the electrical wiring diagram.

Содержание A111C

Страница 1: ...CONTROLS A111C A112H English 03 2004 USER MANUAL ...

Страница 2: ...ON USER INTERFACE DESCRIPTION SELECTING UNIT OPERATING MODE AND SET POINT SELECTING THE TEMPERATURE SET POINT CATEGORY CLOCK AND TIME BANDS AS AN OPTION PARAMETERS STATUS AND READINGS PROGRAMMING DEFROST MANAGEMENT ALARM CODES REMOTE SENSORS AS AN OPTION THERMOSTATIC FREECOOLING OPTION STANDARD GUIDELINES TO LENNOX EQUIPMENT ...

Страница 3: ...lead shielded cable If a remote sensor is requested as an option the terminal thermostat can be installed in a different place from the room to be conditioned Since this type of control panel is factory configured for each application an identification code located on the control panel of the terminal itself has been given to each panel Any query or request for a replacement of the control panel m...

Страница 4: ...rminals on the rear shell of the box as indicated in and in electrical diagram Sub base Sub base Maximum length allowed is 150m T T To PCB in electrical panel of air conditioning unit For correct installation the following warnings must be heeded Always disconnect the power supply before performing any operations on the board during assembly maintenance or replacement The terminal should be fasten...

Страница 5: ...nds the display will show up the software version SIDE BUTTONS These buttons allow access to all the other functions of the control Indicates change value of parameters THE CONTROL IS ACTIVE 5 SECONDS AFTER THE UNIT POWER IS SWITCHED ON Time band indication Set point display Mode absence comfort night Temperature probe measurement Indicates set point display Heating ON Unit OFF Indicates operating...

Страница 6: ...on the display Pressing the mode button repeatedly you can change the unit operating mode COOL The unit is working on cooling mode when compressor is working the symbol will appear on the display HEAT The unit is working on heating mode when compressor or electrical heater are working the symbol will appear on the display AUTO The system automatically switches from cooling to heating mode dependin...

Страница 7: ...symbol It is the reference room desired temperature set point used for the rest of the categories 2 Brief absence set point indicated by the symbol Typically used when the room is not occupied for a short period of time 3 Night time set point indicated by the symbol The room is occupied yet a lower level of comfort is required How to change the desired temperature set point for the different categ...

Страница 8: ...We Wednesday Th Thursday Fr Friday Sa Saturday Su Sunday 8 00 8 00 22 00 22 00 8 00 14 00 16 00 18 00 20 00 22 00 8 00 14 00 16 00 18 00 20 00 22 00 8 00 14 00 16 00 18 00 20 00 22 00 t1 t2 t3 t4 t5 t6 Mo Monday Tu Tuesday We Wednesday Th Thursday Fr Friday Sa Saturday Su Sunday Press clock to accept This Terminal Thermostat with clock function is a programmable terminal programming the time bands...

Страница 9: ... day To set a program press clock for 5 seconds t1 will show on the display Continue to program the remaining days Set the start hour and minutes for the first band with the and buttons and press clock to accept Use and buttons to scroll to the another days which will flash in turn thus extending the same program to the selected days Confirming the days using the clock button The time interval ide...

Страница 10: ...nged using the and buttons and will remain for three hours Press resume button to return to time band operation before the three hours elapse A Change the desired set point of the current time band for three hours HRS The set point will remain until resume button is pressed to return to time band operation Press hold set B Change the desired set point for an unlimited period Change set point using...

Страница 11: ...ume button or wait for 1 minute the final 15 seconds are signalled by the flashing of the characters on the display All modifications on the operating unit parameters must be carried out by qualified personnel Incorrect programming of the parameters may cause damage to the unit And consequently the loss of guarantee of the unit clock set mode fan hold resume clock set mode fan hold resume clock se...

Страница 12: ... heater will turn on as figure shows R4 0 5ºC R3 1ºC R3 1ºC R4 0 5ºC R9 1ºC R8 2ºC 22 5ºC 23 5ºC 21 5ºC 20 5ºC 24 5ºC Electrical heater compressor MODIFICATION OF SET POINT VALUE To modify the set point value see page 5 on this manual MIN MAX UNIT VAR DEF VALUES DESCRIPTION COD S4 12 12 C F 0 5 0 Regulation probe calibration Value to be added to subtracted from the value measured by the temperatur...

Страница 13: ...ours threshold It establishes the number of indoor fan operating hours beyond which the maintenance intervention signal alarm thf is activated F4 0 disables this function alarm will not be visualized F4 values from 1 to 10 number of hours x 1000 of indoor fan operating hours 10 0 H7 0 2 1 It establishes what is displayed on the field in the top right of the display H7 0 Shows the outdoor temperatu...

Страница 14: ... to the beginning of next it could be from 14 to 35 minutes depending on external conditions MAXIMUM DEFROST DURATION 10 minutes is the maximum time defrost cycle will be on POWER BOARD OF THE SYSTEM AT THE ELECTRICAL BOX OF THE AIR CONDITIONING UNIT The board features a signaling green LED which flashes when unit is electrically supplied The control features a minimum run timer which ensures that...

Страница 15: ...ture regulation probe error or connection cable broken E 3 E DF The defrost process has exceeded the maximum time specified of 10 minutes and has not ended Outdoor coil temperature probe error or connection cable broken MAN AUT AUT AUT AUT AUT L OP Low pressure protection After three automatic resets in one hour becomes to be a manual reset MAN EFFECTS ACTION Alarm visualization Alarm visualizatio...

Страница 16: ...re available two types of remote sensors REMOTE DUCT SENSOR The sensor should be located at the return air duct recording the room temperature continuously REMOTE AMBIENT SENSOR The sensor should be located at the room which has to be conditioned Both sensors should be used when the terminal thermostat can be located on a position where the room temperature could not be measured with accuracy Exam...

Страница 17: ... the safety of the unit One of them for 4ºC closes the gate in order to prevent freezing The other one for 10ºC opens the gate to take advantage from outside air These thermostats only work when the freecooling is enabled Programming option is included on it You can connect as an option remote sensors To use this option an outdoor probe is connected If it does not work properly please check the ju...

Страница 18: ...ating instructions contain useful and important information for the smooth operation and maintenance of your equipment The instructions also include guidelines on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault free operation Read the operating instructions carefully before starting the equipment familiarise y...

Страница 19: ...18 ...

Страница 20: ...NOXFRANCE tél 33164762323 fax 33164763575 e mail marketing france lennoxfrance com LENNOXDEUTSCHLANDGmbH tél 49694209790 fax 496942097940 e mail info de lennoxdeutschland com LENNOXBENELUXB V tél 31332471800 fax 31332459220 e mail info lennoxbenelux com LENNOXPOLSKASp zo o tél 48228322661 fax 48228322662 e mail info lennoxpolska pl LENNOXPORTUGALLDA tél 351229983370 fax 351229983379 e mail info le...

Отзывы: