INSTALLATION INSTRUCTIONS FOR MASONRY CHIMNEY VENT ADAPTER KIT (92W76)

USED WITH A80UH1, A80UH2, A80US2, 80G1UH & 80G2UH

Litho U.S.A.

506962−01
04/2012

2012

Dallas, Texas

MASONRY CHIMNEY

VENT ADAPTER

GAS UNITS
KITS & ACCESSORIES

Shipping and Packing List

Package 1 of 1 contains:

 1 − Vent adapter assembly
 1 − Template

Application

The masonry chimney vent adapter kit allows venting of
80 percent efficient furnaces into a tile−lined masonry
chimney without the use of a listed metal lining system.
The vent adapter assembly introduces dilution air into the
flue gases, thus lowering the dew point of the gases and
inhibiting the production of condensation.

This vent adapter is designed for use with units installed
in upflow air discharge applications. The kit may be used
with furnaces fueled by either natural gas or LP/propane
gas. Refer to table 1 for a complete listing of the furnaces
with which this adapter kit may be used.
This kit has been CSA International certified for use with
furnaces when installed in accordance with these
instructions.

The furnace must be installed in accordance with all
national and local building codes or, in the absence of
local codes, with the National Fuel Gas Code NFPA
54/ANSI Z223.1 (latest edition) and other applicable
codes. In Canada, installation must be in accordance
with the National Canadian Installation Code CAN/CGA
B149.1 OR B149.2 (latest edition) and other applicable
codes.

This vent adapter kit has been designed and tested for
use with units installed in masonry chimney vent
applications in accordance with limitations set by NFPA
54 and the International Mechanical Code. 

The included

vent tables and guidelines must be followed exactly
to ensure proper vent and unit operation and to
minimize chimney wet time.

Table 1 also lists the minimum allowable winter design
temperatures for each model when used with the vent
adapter. The map in figure 1 provides winter design
temperatures for the contiguous United States. Portions
of this document are reprinted with permission from NFPA
54: National Fuel Gas Code 

1999, National Fire

Protection Association, Quincy, MA 02269. This reprinted
material is not the complete and official position of the
National Fire Protection Association on the referenced
subject, which is represented only by the standard in its
entirety.

TABLE 1

Minimum Winter Design Temperatures for Use with

Furnaces with Vent Adapter Kit in Both Interior and

Exterior Masonry Chimney Applications

Minimum Winter Design Temperature* °F (°C)

All Models
All Input Sizes

Interior Chimney

−10° F (−23° C)

Exterior Chimney

+5° F (−15° C)

*Refer to 99% Minimum Winter Design Temperature table
provided in the current edition of the ASHRAE Fundamentals
Handbook.

Installation Checklist

Verify furnace model numbers approved for use
with kit (table 1).

Verify that winter design temperature is appropri-
ate for application of kit (table 1 and figure 1).

Verify condition of chimney.

Measure chimney height and inside area of lined
chimney.

Verify chimney and vent connector size (tables 3,
4 and 5).

Install vent adapter kit (page 6).

Connect blocked vent switch wiring (figure 5, page
7).

Test blocked vent switch.

Test for proper draft and check for spillage (page
8).

Place furnace into operation (page 8).

Содержание 92W76

Страница 1: ...ed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables and guidelines must be followed exactly to ensure p...

Страница 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Страница 3: ...mney and vent connector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using...

Страница 4: ...le Lined Masonry Chimney Serving a Single Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TILE LINED MASONRY CHIMNEY PERMANENTLY...

Страница 5: ...145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 163 187 209 233 255...

Страница 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Страница 7: ...to the furnace flue tran sition and the vent pipe at all times 6 The vent adapter assembly includes a blocked vent switch which must be wired into the furnace combustion air proving pressure switch a...

Страница 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...