Lennox 2SCU13 Series Скачать руководство пользователя страница 9

# 48283B006

Page 9

5. Evacuate the line set and indoor unit to a minimum of 500

microns or lower. During the early stages of evacuation, it
is desirable to close the manifold gauge valve at least
once to determine if there is a rapid rise in pressure. A
rapid rise in pressure indicates a relatively large leak. If
this occurs, the leak testing procedure must be repeated.

6. When 500 microns or lower is maintained, close the

manifold gauge valves, turn off the vacuum pump, and
disconnect the manifold gauge center port hose from
the vacuum pump. Attach the manifold gauge center
port hose to a nitrogen cylinder with pressure regulator
set to 150 psig and purge the hose. Open the manifold
gauge  valves to break the vacuum in the line set and
indoor unit. Close the manifold gauge valves.

7. Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

8. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line
set and indoor unit until 500 microns is maintained
within a 20-minute period after shutting off the
vacuum pump and closing the manifold gauge valves.

9. When the requirements above have been met,

disconnect the manifold hose from the vacuum pump.
Open the service valves to break the vacuum in the
line set and indoor unit.

2. With both manifold valves closed, connect the cylin-

der of HCFC-22 refrigerant. Open the valve on the
HCFC-22 cylinder (vapor only).

3. Open the high pressure side of the manifold to allow

HCFC-22 into the line set and indoor unit. Weigh in a
trace amount of HCFC-22. (A trace amount is a
maximum of 2 oz. of refrigerant or 3 lbs. pressure.)
Close the valve on the HCFC-22 cylinder and the
valve on the high pressure side of the manifold gauge
set. Disconnect the HCFC-22 cylinder.

4. Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

When using high pressure gas such as nitrogen
for this purpose, be sure to use a regulator that
can control the pressure  down to 1 or 2 psig.

5. Adjust nitrogen pressure to 150 psig. Open the valve

on the high side of the manifold gauge set to pressur-
ize the line set and the indoor coil.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper
piping and compressor parts.

Do not use a compressor to evacuate a sys-
tem. Avoid deep vacuum operation. Extremely
low vacuums can cause internal arcing and
compressor failure. Danger of equipment
damage. Damage caused by deep vacuum
operation will void warranty.

  WARNING

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument that
reads down to  50 microns.

1. Connect the manifold gauge set to the service valve

ports as follows:

Low pressure gauge to suction line service valve

High pressure gauge to liquid line service valve

2. Connect micron gauge.

3. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

4. Open both manifold valves and start vacuum pump.

Содержание 2SCU13 Series

Страница 1: ...trical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death W...

Страница 2: ...or inspection by the carrier s agent If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT as claim may be denied Check the unit rating plate to confirm specifications are...

Страница 3: ...rcuit connections are made to the low voltage pigtails A complete unit wiring diagram is located inside the unit control box cover see also pages 16 and 17 of this instruction 3 Install room thermosta...

Страница 4: ...although vertical lift applications and trapping require ments need to be reviewed with Technical Services for line sets over 50 energy or vibration can be expected Close attention to line set isolat...

Страница 5: ...line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter Tape or Wire Tie Wire Tie around vapor line only Refrigerant Line Sets Installing Horizontal Runs Figure 7 Refrigerant Line Sets...

Страница 6: ...t damage to the valve core and opening port The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the factory supplied fixed orif...

Страница 7: ...id and Suction Line Service Valves The liquid line and suction line service valves and service ports are used for leak testing evacuating charging and checking charge Each valve is equipped with a ser...

Страница 8: ...e line set connections and indoor unit must be checked for leaks Ball Type Service Valve Valve Open Figure 11 Use adjustable wrench To open rotate stem counterclockwise 1 4 turn 90 To close rotate ste...

Страница 9: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the HCFC 22 cylinder and the valve...

Страница 10: ...d has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and suction line temperatures 6 The ou...

Страница 11: ...e F _____ Saturation Temperature F _____ Liquid Line Temperature F _____ Subcooling Value F r o o d t u O p m e T F F 1 g n i l o o c b u S d i u q i L 8 1 4 2 0 3 6 3 2 4 8 4 0 6 5 6 3 1 3 1 7 4 1 5...

Страница 12: ...e 7 Approach Values for TXV Systems Approach value is the liquid line temperature minus the outdoor ambient temperature 1 F NOTE For best results use the same digital thermometer to check both outdoor...

Страница 13: ...1 8 8 6 2 9 7 8 6 2 4 8 5 6 2 5 8 7 7 2 1 8 F 5 1 1 4 9 2 6 8 7 0 3 5 8 9 9 2 3 8 9 0 3 1 8 8 0 3 5 8 3 0 3 6 8 8 1 3 3 8 C F R e c i f i r O d e x i F F 5 6 4 4 1 3 7 7 4 1 8 6 0 4 1 6 6 0 5 1 7 6 7...

Страница 14: ...or correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged an...

Страница 15: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Страница 16: ...OCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINIMUM NEC...

Страница 17: ...2 L3 EQUIPMENT GROUND HR1 S40 K1 1 BLACK BLACK B1 BLACK ORANGE BLACK B4 C1 PURPLE RED 1 FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURR...

Страница 18: ...the only warranty made by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to...

Отзывы: