Lennox 2SCU13 Series Скачать руководство пользователя страница 11

# 48283B006

Page 11

Charge Using Weigh-In Method (Fixed Orifice/TXV
Systems)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, first locate and repair any leaks then
use the weigh-in method to charge the unit.

1. Recover the refrigerant from the unit.

2. Conduct a leak check, then evacuate as previously

outlined.

3. Weigh in the charge according to the total amount

shown on the unit nameplate.

If weighing facilities are not available or if unit is being
charged during warm weather, follow one of the other
procedures outlined below.

Charge Using Subcooling Method (Fixed Orifice/TXV
Systems) – Outdoor Temperatures 65°F or Above

If charging a fixed orifice or TXV system when the outdoor
ambient temperature is 65°F or above, the subcooling
method can be used to charge the unit.

1. With the manifold gauge hose on the liquid service

port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.

2. At the same time, record the liquid line pressure reading.

3. Use a temperature/pressure chart for HCFC-22 to

determine the saturation temperature for the liquid line
pressure reading.

4. Subtract the liquid line temperature from the satura-

tion temperature (according to the chart) to determine
subcooling.

3. Use a temperature/pressure chart for HCFC-22 to

determine the saturation temperature for the suction
line pressure reading.

4. Subtract the saturation temperature (according to the

chart) from the suction line temperature to determine
the superheat.

_____ °

Suction Line Temperature °F

_____ °

Saturation Temperature °F

_____ °

Superheat Value °F

=

_____ °

Saturation Temperature °F

_____ °

Liquid Line Temperature °F

_____ °

Subcooling Value °F

=

r

o

o

d

t

u

O

.

p

m

e

T

F

°

)

F

°

1

±

(

g

n

i

l

o

o

c

b

u

S

d

i

u

q

i

L

8

1

-

4

2

-

0

3

-

6

3

-

2

4

-

8

4

-

0

6

-

5

6

3

1

3

1

7

4

1

5

1

9

3

1

5

7

0

1

1

1

5

3

1

3

1

9

2

1

5

8

8

0

1

5

1

1

1

1

9

1

1

5

9

7

0

1

4

9

9

9

0

1

5

0

1

6

9

3

8

7

9

9

5

1

1

3

6

2

6

5

8

8

Subcooling Values for

Fixed Orifice or TXV Systems

Table 6

5. Compare the subcooling value with those shown in

Table 6. If subcooling is greater than shown, recover
some refrigerant. If subcooling is less than shown,
add some refrigerant.

Charge Using Superheat Method (Fixed Orifice
Systems) – Outdoor Temperatures 65°F or Above

1. With the manifold gauge hose on the suction service

port and the unit operating stably, use a digital ther-
mometer to record the suction line temperature.

2. At the same time, record the suction line pressure

reading.

5. Compare the superheat value with those shown in

Table 7 on page 12. If superheat is greater than
shown, add some refrigerant. If superheat is less than
shown, recover some refrigerant.

Charge Using Approach Method (TXV Systems)
– Outdoor Temperatures 65°F or Above

The following procedure is intended as a general guide
and is for use on expansion valve systems only. For best
results, indoor temperature should 70°F to 80°F. Monitor
system pressures while charging.

1. Record outdoor ambient temperature using a digital

thermometer.

2. Attach high pressure gauge set and operate unit for

several minutes to allow system pressures to stabilize.

3. Compare stabilized pressures with those provided in

Table 9 on page 13. Minor variations in these pres-
sures may be expected due to differences in installa-
tions. 

Significant differences could mean that the

system is not properly charged or that a problem
exists with some component in the system.

Содержание 2SCU13 Series

Страница 1: ...trical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death W...

Страница 2: ...or inspection by the carrier s agent If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT as claim may be denied Check the unit rating plate to confirm specifications are...

Страница 3: ...rcuit connections are made to the low voltage pigtails A complete unit wiring diagram is located inside the unit control box cover see also pages 16 and 17 of this instruction 3 Install room thermosta...

Страница 4: ...although vertical lift applications and trapping require ments need to be reviewed with Technical Services for line sets over 50 energy or vibration can be expected Close attention to line set isolat...

Страница 5: ...line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter Tape or Wire Tie Wire Tie around vapor line only Refrigerant Line Sets Installing Horizontal Runs Figure 7 Refrigerant Line Sets...

Страница 6: ...t damage to the valve core and opening port The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the factory supplied fixed orif...

Страница 7: ...id and Suction Line Service Valves The liquid line and suction line service valves and service ports are used for leak testing evacuating charging and checking charge Each valve is equipped with a ser...

Страница 8: ...e line set connections and indoor unit must be checked for leaks Ball Type Service Valve Valve Open Figure 11 Use adjustable wrench To open rotate stem counterclockwise 1 4 turn 90 To close rotate ste...

Страница 9: ...HCFC 22 into the line set and indoor unit Weigh in a trace amount of HCFC 22 A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the HCFC 22 cylinder and the valve...

Страница 10: ...d has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and suction line temperatures 6 The ou...

Страница 11: ...e F _____ Saturation Temperature F _____ Liquid Line Temperature F _____ Subcooling Value F r o o d t u O p m e T F F 1 g n i l o o c b u S d i u q i L 8 1 4 2 0 3 6 3 2 4 8 4 0 6 5 6 3 1 3 1 7 4 1 5...

Страница 12: ...e 7 Approach Values for TXV Systems Approach value is the liquid line temperature minus the outdoor ambient temperature 1 F NOTE For best results use the same digital thermometer to check both outdoor...

Страница 13: ...1 8 8 6 2 9 7 8 6 2 4 8 5 6 2 5 8 7 7 2 1 8 F 5 1 1 4 9 2 6 8 7 0 3 5 8 9 9 2 3 8 9 0 3 1 8 8 0 3 5 8 3 0 3 6 8 8 1 3 3 8 C F R e c i f i r O d e x i F F 5 6 4 4 1 3 7 7 4 1 8 6 0 4 1 6 6 0 5 1 7 6 7...

Страница 14: ...or correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged an...

Страница 15: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Страница 16: ...OCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINIMUM NEC...

Страница 17: ...2 L3 EQUIPMENT GROUND HR1 S40 K1 1 BLACK BLACK B1 BLACK ORANGE BLACK B4 C1 PURPLE RED 1 FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURR...

Страница 18: ...the only warranty made by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to...

Отзывы: