Page 25

Outdoor Coil 

It  may  be  necessary  to  flush  the  outdoor  coil  more  fre

-

quently if it is exposed to substances which are corrosive 

or which block airflow across the coil (e.g., pet urine, cot

-

tonwood  seeds,  fertilizers,  fluids  that  may  contain  high 

levels of corrosive chemicals such as salts) 
• 

 Outdoor Coil – The outdoor coil may be flushed with a 

water hose. 

• 

 Outdoor Coil (Sea Coast) – Moist air in ocean locations 

can carry salt, which is corrosive to most metal. Units 

that are located near the ocean require frequent in-

spections and maintenance. These inspections will de-

termine the necessary need to wash the unit including 

the outdoor coil. Consult your installing contractor for 

proper intervals/procedures for your geographic area or 

service contract. 

Indoor Unit 

1. Clean or change filters. 
2.  Lennox  blower  motors  are  prelubricated  and  perma

-

nently sealed. No more lubrication is needed. 
3. Adjust blower speed for cooling. Measure the pressure 

drop over the coil to determine the correct blower CFM. 

Refer to the unit information service manual for pressure 

drop tables and procedure. 
4. Belt Drive Blowers - Check belt for wear and proper 

tension. 
5. Check all wiring for loose connections. 
6. Check for correct voltage at unit. (blower operating) 
7. Check amp draw on blower motor. 

Motor Nameplate:_________ Actual:__________. 

Indoor Coil 

1 -  Clean coil if necessary. 
2 -   Check connecting lines, joints and coil for evidence 

of oil leaks. 

3 -  Check condensate line and clean if necessary. 

HOMEOWNER

 

Cleaning of the outdoor unit's coil should be performed by 

a trained service technician. Contact your dealer and set 

up a schedule (preferably twice a year, but at least once a 

year) to inspect and service your outdoor unit. The follow-

ing maintenance may be performed by the homeowner.

 IMPORTANT

Sprinklers and soaker hoses should not be installed 

where they could cause prolonged exposure to the 

outdoor unit by treated water. Prolonged exposure 

of the unit to treated water (i.e., sprinkler systems, 

soakers, waste water, etc.) will corrode the surface of 

the steel and aluminum parts, diminish performance  

and affect longevity of the unit. 

 IMPORTANT

After testing has been completed, properly reposition 

test jumper across desired timing pins 

Maintenance  

DEALER

 WARNING

Electric Shock Hazard. Can cause injury or 

death. Unit must be properly grounded in 

accordance with national and local codes.

Line  voltage  is  present  at  all  components 

when unit is not in operation on units with 

single-pole contactors. Disconnect all remote 

electric power supplies before opening 

access panel. Unit may have multiple power 

supplies.

 WARNING

Improper installation, adjustment, alteration, service 

or maintenance can cause property damage, personal 

injury or loss of life. Installation and service must  be 

performed by a licensed professional HVAC installer or 

equivalent, service agency, or the gas supplier.

Maintenance and service must be performed by a quali-

fied installer or service agency. At the beginning of each 

cooling season, the system should be checked as follows:

Outdoor Unit

1 - 

 Clean and inspect outdoor coil (may be flushed with 

a water hose). Ensure power is off before cleaning.

2 -   Outdoor unit fan motor is pre-lubricated and sealed. 

No further lubrication is needed.

3 -   Visually inspect all connecting lines, joints and coils 

for evidence of oil leaks.

4 -  Check all wiring for loose connections. 
5 -  Check for correct voltage at unit (unit operating). 
6 -  Check amp draw on outdoor fan motor.

Motor Nameplate:_________ Actual:__________.

7 -   Inspect drain holes in coil compartment base and 

clean if necessary.

NOTE

 – 

If  insufficient  heating  or  cooling  occurs,  the 

unit should be gauged and refrigerant charge should be 

checked. 

Содержание 16HPX Series

Страница 1: ...plies before opening access panel Unit may have multiple power supplies 16HPX Table of Contents Installation Clearances 2 Model Number Identification 2 Dimensions 3 Specifications 4 Typical Unit Parts...

Страница 2: ...14 mm Clearance to one of the remaining two sides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification 16 HP X 0...

Страница 3: ...NNECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4 3...

Страница 4: ...ctor 0 98 0 99 0 99 0 99 Outdoor Coil Fan Motor Full load amps 0 7 1 7 1 8 2 8 CONTROLS ORDER SEPARATELY iComfort M30 Smart Wi Fi Thermostat 15Z69 Remote Outdoor Temperature Sensor X2658 OPTIONAL ACCE...

Страница 5: ...d wrench should be used and fitted snugly over the cap before tightening When servicing or repairing HVAC components ensure the fasteners are appropriately tightened Table 3 provides torque values for...

Страница 6: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Страница 7: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Страница 8: ...ons that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO...

Страница 9: ...unt of refrigerant charge in the system No need to add oil in system with 20 pounds of refrigerant or less For systems over 20 pounds add one ounce for every five pounds of refrigerant Recommended top...

Страница 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Страница 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Страница 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Страница 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Страница 15: ...hreads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Страница 16: ...losed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allo...

Страница 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Страница 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Страница 19: ...TO PREVENT DAMAGE TO CONTROL SEE INSTALLATION INSTRUCTION FOR FURTHER DETAILS Typical Field Wiring Heat Pump Application with CBA38MV FIGURE 12 YELLOW BLUE NOT REQUIRED FOR SINGLE STAGE RED BLACK PUR...

Страница 20: ...ssure switches Defrost Thermostat S6 The defrost thermostat is located on the liquid line be tween the check expansion valve and the distributor When defrost thermostat senses 42 F 5 5 C or cooler the...

Страница 21: ...CONNECTIONS TEST PINS P1 Note Component locations vary by board manufacturer SENSOR CONNECTION COIL AND AMBIENT SENSORS P4 REVERSING VALVE O OUT DELAY PINS P5 LOW AMBIENT THERMOSTAT PINS P3 DEFROST T...

Страница 22: ...of the defrost mode When a jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY...

Страница 23: ...ature probe is de signed with a spring clip to allow mounting to the outside coil tubing The location of the coil sensor is important for proper defrost operation NOTE The demand defrost control accur...

Страница 24: ...tem Remove any blockages or restrictions from coils and or fans Check indoor and outdoor fan motor for proper current draws Check system charge using subcooling method Check system operating pressures...

Страница 25: ...performed by the homeowner IMPORTANT Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water Prolonged exposure of the unit t...

Страница 26: ...rmostat homeowner manual for instructions on how to operate your thermostat Heat Pump Operation Your new Lennox heat pump has several characteristics that you should be aware of Heat pumps satisfy hea...

Страница 27: ...Page 27 Wiring and Sequence of Operation FIGURE 15 Typical Unit Wiring 024 036 and 048 Units...

Страница 28: ...Page 28 FIGURE 16 Typical Unit Wiring 060 Units...

Страница 29: ...Page 29 FIGURE 17 Typical Factory Wiring 024 036 and 048 Units...

Страница 30: ...Page 30 FIGURE 18 Typical Factory Wiring 060 Units...

Страница 31: ...emand cycle If the coil sensor temperature is still below the selected termination temperature the control will continue the defrost cycle until the cycle is terminated in one of the methods mentioned...

Страница 32: ...um Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Vapor P...

Отзывы: