background image

Page 18

Maintenance

 

WARNING

Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at discon-
nect switch(es). Unit may have multiple
power supplies.

Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
or heating season, the system should be checked as fol-
lows:

Outdoor Unit

 1 − Clean and inspect the outdoor coil. The coil may be

flushed with a water hose. Ensure the power is turned
off before you clean the coil.

 2 − Outdoor unit fan motor is pre-lubricated and sealed. No

further lubrication is needed.

 3 − Visually inspect all connecting lines, joints and coils for

evidence of oil leaks.

 4 − Check wiring for loose connections.
 5 − Check for correct voltage at unit (unit operating).
 6 − Check amp draw on outdoor fan motor.

Unit nameplate__________Actual__________.

 7 - Inspect drain holes in coil compartment base and clean

if necessary.

NOTE − If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer
to section on refrigerant charging in this instruction.

Indoor Coil

 1 − Clean coil if necessary.

 2 − Check connecting lines, joints and coil for evidence of

oil leaks.

 3 − Check condensate line and clean if necessary.

Indoor Unit

 1 − Clean or change filters.
 2 - Lennox blower motors are prelubricated and permanent-

ly sealed. No more lubrication is needed.

 3 − Adjust blower speed for cooling. Measure the pressure

drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.

 4 −

Belt Drive Blowers − 

Check belt for wear and proper

tension.

 5 − Check all wiring for loose connections.
 6 − Check for correct voltage at unit. (blower operating)
 7 − Check amp draw on blower motor.

Motor nameplate__________Actual__________.

Optional Accessories

Refer to the Engineering Handbook for optional accesso-
ries that may apply to this unit. The following may or may
not apply:

 

 

Loss of Charge Kit

 

 

High Pressure Switch Kit

 

 

Compressor Monitor

 

 

Compressor Crankcase Heater

 

 

Hail Guards

 

 

Mounting Bases

 

 

Stand−off Kit

 

 

Sound Cover

 

 

Low Ambient Kit

 

 

Monitor Kit

 

 

Mild Weather Kit

Start−Up and Performance Check List

Start−up and Performance Check List

Job Name

Job Location
Installer

Unit Model No.

Nameplate Voltage

Rated Load Ampacity

Maximum Fuse or Circuit Breaker

Refrigerant Lines:

Service Valves Fully Opened?

Outdoor Fan Checked?

Job No.

City

City

Serial No.

Date

State

State

Service Technician

Compressor

Outdoor Fan

Indoor Filter Clean?

Electrical Connections Tight?

Supply Voltage (Unit Off)

Vapor Pressure

Thermostat

Refrigerant Charge Checked?

Calibrated?

Properly Set?

Level?

Properly Insulated?

Voltage With Compressor Operating

Leak Checked?

Service Valve Caps Tight?

Indoor Blower RPM

Outdoor Coil Entering Air Temp.

Liquid Line Pressure

S.P. Drop Over Indoor (Dry)

Cooling

Vapor Pressure

Refrigerant Charge Checked?

Liquid Line Pressure

Heating

Sequence of Operation

Heating Correct

Cooling Correct

Содержание 12HPB Series

Страница 1: ...4 532M 06 04 Supersedes 04 04 Table of Contents 12HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Refrigerant M...

Страница 2: ...tion 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 compressor coil drain outlets around perimeter of base optional unit stand off kit 4 field installed B C A optional unit stand off kit 4 field in...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...G Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death 1 Install line voltage power supply to unit from a properly sized disconnect switch...

Страница 5: ...power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor Figure 5 R C W1 Y1 O G R C W1 W2 W3 G Outdoor Unit and Blower Unit Thermostat Designations with emergency heat...

Страница 6: ...o the compressor Installing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...d line at the indoor coil Refrigerant Metering Device 12HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application informat...

Страница 11: ...e wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjus...

Страница 12: ...r use oxygen to pressurize a refrigera tion or air conditioning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage in...

Страница 13: ...r port hose from vacuum pump Attach the manifold center port hose to a nitrogen cylin der with pressure regulator set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break th...

Страница 14: ...which charg ing method to use Proceed with the appropriate charg ing procedure Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient...

Страница 15: ...erature to check liquid line tempera ture Verify the unit charge using the approach method 5 The difference between the ambient and liquid temper atures should match values given in table 6 If the val...

Страница 16: ...ts An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode Emergency heat is usually used during an outdoor shut down but it should al...

Страница 17: ...mode If the jumper is removed before an addi tional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If th...

Страница 18: ...lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tabl...

Отзывы: