background image

Page 17

12HPB Defrost Control Board

24V

terminal strip

High Pressure Switch

Safety Circuit

Connections

S4

connection for

optional

high pressure

switch

defrost

interval

timing pins

high

 pressure

switch

diagnostic

LEDs

Figure 16

NOTE − To add pressure

switch, remove factory−

installed jumper

Defrost Control Timing Pins

Each timing pin selection provides a different accumu-
lated compressor run time period during one thermostat
run cycle. This time period must occur before a defrost
cycle is initiated. The defrost interval can be adjusted to
30 (T1), 60 (T2), or 90 (T3) minutes. See figure 16. The
defrost timing jumper is factory−installed to provide a
60−minute defrost interval. If the timing selector jumper is
not in place, the control defaults to a 90−minute defrost
interval. The maximum defrost period is 14 minutes and
cannot be adjusted.

A TEST option is provided for troubleshooting. 

The TEST

mode may be started any time the unit is in the heating
mode and the defrost thermostat is closed or jump-
ered. 

If the jumper is in the TEST position at power-up, the

control will ignore the test pins. When the jumper is placed
across the TEST pins for two seconds, the control will enter
the defrost mode. If the jumper is removed before an addi-
tional 5−second period has elapsed (7 seconds total), the
unit will remain in defrost mode until the defrost thermostat
opens or 14 minutes have passed. If the jumper is not re-
moved until after the additional 5−second period has
elapsed, the defrost will terminate and the test option will
not function again until the jumper is removed and re−ap-
plied.

Pressure Switch Circuit

The defrost control incorporates a pressure switch circuit
that allows the application of an optional high pressure
switch. See figure 16. During a demand cycle, the defrost
control will lock out the unit if the optional high pressure
switch opens. The diagnostic LEDs will display a pattern for
an open high pressure switch. See table 8. The unit will re-
main locked out until the switch resets or is reset.

Remove the factory-installed jumper before connecting the
optional high pressure switch to the control board.

NOTE − If not using a pressure switch, the factory-installed
jumper wire must be connected.

Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The LEDs
flash a specific sequence according to the condition.

Table 8

Defrost Control Board Diagnostic LED

Mode

LED 1

LED 2

Normal operation / 

power to board

Synchronized
Flash with LED 2 

Synchronized

Flash with LED 1 

Board failure or no power

Off

Off

Board failure

On

On

Pressure switch open

Flash

On

Содержание 12HPB Series

Страница 1: ...4 532M 06 04 Supersedes 04 04 Table of Contents 12HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Refrigerant M...

Страница 2: ...tion 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 compressor coil drain outlets around perimeter of base optional unit stand off kit 4 field installed B C A optional unit stand off kit 4 field in...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...G Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death 1 Install line voltage power supply to unit from a properly sized disconnect switch...

Страница 5: ...power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor Figure 5 R C W1 Y1 O G R C W1 W2 W3 G Outdoor Unit and Blower Unit Thermostat Designations with emergency heat...

Страница 6: ...o the compressor Installing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...d line at the indoor coil Refrigerant Metering Device 12HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application informat...

Страница 11: ...e wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjus...

Страница 12: ...r use oxygen to pressurize a refrigera tion or air conditioning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage in...

Страница 13: ...r port hose from vacuum pump Attach the manifold center port hose to a nitrogen cylin der with pressure regulator set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break th...

Страница 14: ...which charg ing method to use Proceed with the appropriate charg ing procedure Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient...

Страница 15: ...erature to check liquid line tempera ture Verify the unit charge using the approach method 5 The difference between the ambient and liquid temper atures should match values given in table 6 If the val...

Страница 16: ...ts An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode Emergency heat is usually used during an outdoor shut down but it should al...

Страница 17: ...mode If the jumper is removed before an addi tional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If th...

Страница 18: ...lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tabl...

Отзывы: