C - Gas Flow (Approximate)

NOTE: 

To obtain accurate reading, shut off all other gas 

appliances connected to meter.

Furnace should operate at least 5 minutes before checking 

gas flow. Determine time in seconds for two revolutions of 

gas through the meter. (Two revolutions assures a more 

accurate time.) Divide by two and compare to time in 

Table 2. If manifold pressure matches Table 1 and rate is 

incorrect, check gas orifices for proper size and restriction. 

Remove temporary gas meter if installed.

Unit Capacity

Seconds for One Revolution

LP

1 cu ft Dial

2 cu ft Dial

-045

200

400

-070

136

272

-090

102

204

-110

82

164

-135

68

136

2500 btu/cu ft

Table 2. Gas Meter Clocking Chart

D- Proper Combustion

Furnace should operate minimum 15 minutes with correct 

manifold  pressure  and  gas  flow  rate  before  checking 

combustion.  Take  combustion  sample  beyond  the  flue 

outlet. See Table 3 through Table 5 .

NOTE: 

Shut unit off and remove manometer as soon as 

supply  line  pressure,  manifold  pressure  and  combustion 

sample have been obtained. Take care to replace pressure 

tap plug.

Unit Capacity

CO

2

% for LP

Low Fire

High Fire

-045

6.4 - 7.4

8.8 - 9.8

-070

6.3 - 7.3

8.7 - 9.8

-090

6.8 - 7.8

8.9 - 9.9

-110

7.1 - 8.1

9.3 - 10.3

-135

7.1 - 8.2

9.1 - 10.1

The carbon monoxide reading should not exceed 100 ppm.

Table 3. 

A952 & 95G2 Upflow / Horizontal Furnaces

Unit Capacity

CO

2

% for LP

Low Fire

High Fire

-045

6.6 - 7.6

9.1 - 10.1

-070

6.5 - 7.5

8.6 - 9.6

-090

6.9 - 7.9

9.1 - 10.1

-110

7.3 - 8.3

9.5 - 10.5

The carbon monoxide reading should not exceed 100 ppm.

Table 4. 

A952 & 95G2 Downflow Furnaces

All Models

Firing Rate CO

2

% for Nat CO

2

% for LP

Upflow/

Horizontal

High Fire

6.8 - 7.4

7.5 - 9.0

Low Fire

4.2 - 5.7

5.0 - 6.0

Downflow

High Fire

6.0 - 7.4

6.9 - 8.4

Low Fire

4.8 - 6.0

5.7 - 7.0

The carbon monoxide reading should not exceed 100 ppm.

Table 5. A802 & 80G2

E - Turning Off Gas to the Unit

1.  Set the thermostat to its lowest setting.
2.  Turn off all the electrical power to the unit.

3. 

Remove the unit access panel.

4.  Move the switch on the gas valve to OFF. Do not force 

the switch.