background image

507371-02

Issue 1706

Page 4 of 5

Start-Up & Adjustment

BEFORE PLACING THE UNIT INTO OPERATION

Smell all around the appliance area for gas. Be sure to 

smell next to the floor because LP/Propane gas is heavier 

than air and will settle on the floor.

Use only your hand to move the gas control switch. Never 

use tools. If the switch will not move by hand, do not try to 

repair it. Force or attempted repair may result in a fire or 

explosion.

A - Placing the Unit into Operation

 IMPORTANT

Follow the lighting instructions provided on the unit. 

If lighting instructions are not available, refer to the 

following section.

Units are equipped with a two-stage integrated ignition 

system. The integrated ignition control automatically lights 

the burners each time the thermostat calls for heat.

1. 

STOP!

 Read the safety information at the beginning 

of this section.

2.  Set the thermostat to its lowest setting.

3. 

Turn off all electrical power to the furnace.

4.  Do not try to light the burners by hand.
5.  Remove the unit access panel.
6.  Move the switch on the gas valve to OFF. Do not force 

the switch. See Figure 1.

7. 

Wait five (5) minutes for any gas to clear out. If you 

then smell gas, STOP! Immediately call your gas 

supplier from a neighbor’s phone. Follow the gas 

supplier’s instructions. If you do not smell gas, go to 

the next step.

8.  Move the switch on the gas valve to ON.
9.  Replace the unit compartment access panel.
10.  Turn on all electrical power to the unit.
11.  Set the thermostat to desired setting.
12.  If the furnace will not operate, see section E- “Turning 

Gas Off to the Unit” and call the gas supplier.

Gas Pressure Measurement

A - Supply Pressure Measurement

An inlet pressure post located on the gas valve provides 

access to the supply pressure. See Figure 1. Back out the 

3/32 hex screw one turn, connect a piece of 5/16 tubing 

and connect to a manometer to measure supply pressure. 

Check the unit on high fire. On multiple unit installations, 

check the unit separately and with the other units operating. 

See Table 1 for supply line pressure. Following the supply 

pressure check, turn off unit, remove manometer and 

tighten post hex screw.

B - Measuring & Adjusting the Manifold Pressure

A952 & 95G2 Models

A manifold pressure post located on the gas valve provides 

access to the manifold pressure. See Figure 1. Back out 

the  3/32  hex  screw  one  turn,  connect  a  piece  of  5/16 

tubing and connect to a manometer to measure manifold 

pressure. To correctly measure manifold pressure, the 

differential pressure between the positive gas manifold 

and the negative burner box must be considered. Furnace 

should operate at least 5 minutes before checking manifold 

pressure.

1.  Connect the test gauge positive side “+“ to manifold 

pressure tap on gas valve as noted above.

2.  Tee into the gas valve regulator vent hose and connect 

to test gauge negative “-”.

3.  Ignite unit on low fire and let run for 5 minutes to allow 

for steady state conditions.

4.  After allowing unit to stabilize for 5 minutes, record 

low fire manifold pressure and compare to value given 

in Table 1. If necessary, make adjustment. Figure 1 

shows location of low fire adjustment screw.

5. 

Repeat  on  high  fire  and  compare  to  value  given  in 

Table 1. If necessary, make adjustment. Figure 1 

shows location of high fire adjustment screw. 

A802 & 80G2 Models

A manifold pressure post located on the gas valve provides 

access to the manifold pressure. See Figure 1. Back out 

the  3/32  hex  screw  one  turn,  connect  a  piece  of  5/16 

tubing and connect to a manometer to measure manifold 

pressure.

1.  Connect test gauge to manifold pressure post (Figure 

1) on gas valve.

2. 

Ignite unit on low fire and let run for 5 minutes to allow 

for steady state conditions.

3. 

After allowing unit to stabilize for 5 minutes, record 

manifold pressure and compare to value given in 

Table 1.

4.  If necessary, make adjustments. Figure 1 shows 

location of high fire and low fire adjustment screws.

5. 

Repeat steps 2, 3 and 4 on high fire. See values in 

Table 1.

Manifold Pressure in w.g.

Gas Line Pressure in w.g.

Low Fire

High Fire

Minimum

Maximum

4.9

10.0

11.0

13.0

Table 1. Manifold and Gas Line Pressure

Отзывы: