Table 2. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
432
28
Service
Soon/Service
Urgent
OD Inverter
DC Link High
Voltage
The inverter has detected a DC link high voltage condition.
•
Error occurs when the DC link capacitor voltage is greater than 480VDC.
• If condition is detected, outdoor unit will stop (compressor and fan) – service soon condition.
• Anti-short cycle timer is initiated.
•
If condition occurs 10 times within 60 consecutive minutes, the system will lockout – service
urgent condition.
•
Inverter LEDs will flash code 28.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter flash code 28.,
The sequence is:
•
Red LED: Two Flashes
•
Green LED: Eight Flashes
NOTE:
Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
Troubleshooting Suggestions:
•
Check wire connections (U, V and W) at inverter plug in harness and compressor.
•
Check the resistance of compressor windings. If not in range, replace compressor.
•
Check compressor to ground. If ground issue, replace compressor.
•
Check input power (Single Phase - 208/230VAC
+ 10%. If out of range, correct main power
issue.
•
Check DC Link voltage and MICOM Sensing voltage. If out of range, replace inverter. if okay,
possible mechanical issue with compressor.
Go to outdoor unit service manual for detail troubleshooting procedures and require values for
testing DC link voltages and various insulation resistance characteristics.
To clear, disconnect power to outdoor unit
and restart.