NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

Figure 20

Figure 21

Figure 22

The outer chimney section installs the opposite
way; the lanced end goes down and each new
section installs OVER the outside of the previ-
ous section (

Figure 23 ).

Figure 23

Continue to assemble the chimney up through
framed opening. Assemble just enough to pen-
etrate the roof flashing openings (

Figure 24 ).

Always maintain 2" minimum air space to com-
bustible materials and always check each chim-
ney joint (inner and outer) to ensure proper
engagement. Check vertical alignment of chim-
ney so that it projects from the roof in true
vertical position.

Figure 24

Security's chimney sections do not need to be
screwed together. Additional reinforcement is
not necessary except in certain offset condi-
tions (refer to page 12, 

Figure 35 ).

Step 4. The height of vertical chimney pipe
supported only by the fireplace must not ex-
ceed 30'. Chimney heights above 30' must be
supported by a Model FTF10-S4 stabilizer in-
stalled at 30' intervals.

Note: The Model FTF10-S4 adds 3" net effective
height to the total chimney system.

F10FS30-2

Firestop Spacer

FTF10-S4

Stabilizer

2" (51mm)

Min. Air

Space

30

°

 Firestop

and Space Above

10' (3m) Max.

2" (51mm)

Min. Air

Space

F10FS30-2

Firestop Spacer

30

°

 Firestop and

Space Above

10' (3m) Max.

2" (51mm)

Min. Air

Space

2" (51mm)

Min. Air

Space

FTF10-S4

Stabilizer

Locking Tabs
(Lances)

2"  (51mm) Min.
Air Space to Combustibles

Step 3.

  Note: All chimney sections are con-

structed with a unique locking tabs and hem
design, which ensures and immediate, tight
assembly between sections. Plan your chimney
requirements carefully before assembly, as the
chimney is difficult to disassemble after instal-
lation. If disassembled, the tabs might become
damaged. Be certain that the tabs are properly
formed to ensure they engage properly.

Note: For Canadian installations, all chimney
installed outside the building must be constructed
with galvalume (outer sections only) effective
January 1, 1992. The appropriate model desig-
nations are located in the back of this manual.

Install the Model FTF10-S4 stabilizer by fitting
inner section down into respective section of
proceeding flue pipe and locking outer stabi-
lizer section into place over the outer chimney
pipe. Position for proper clearance through
framed opening and nail straps securely (under
tension in “shear”) into place on framing. Use
8d nails. Attach successive lengths of chimney
pipe directly to stabilizer using same tech-
niques as described in Step 3 (

Figure 25 ).

Figure 25

FTF8-S4 Stabilizer

Note: Assemble one component of chimney at a
time (inner section first; then outer section last)
before preceding with the next complete section.

The FTF10 chimney system is a two piece chim-
ney that snap locks together from the fireplace
up. Always start with the inner flue section. With
the lanced end up, snap lock the joint into the
matching collar on top of the fireplace. At all
subsequent joints, the upper flue section fits into
the lower or preceding flue section. Each section
snaps together by means of locking tabs (9 tabs
per joint).  Check each section by pulling up
slightly from the top to ensure proper engage-
ment before installing succeeding sections. If
the flue has been installed correctly, it will not
separate when tested. Also, the inner flue joint
where each section is joined should be tight and
flat without gaps (

Figure 22 ).

CHIMNEY 30

°

 OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at
30

°

 when passing through the floor or ceiling

area.  Use the F10FS30-2 firestop spacer as
shown in 

Figures 20 and 21.  Support the

chimney at floor or ceiling penetration with a
FTF10 stabilizer if distance of chimney below
ceiling is 10' or more. Maintain 2" minimum air
space to combustibles from chimney sections.

Содержание LSO-43

Страница 1: ...nents under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories may void the warranty listings and ap...

Страница 2: ...arwithcom monlyacceptedfireplaceinstallationandsafety techniques as well as prevailing local codes The most important areas of concern dealing with the installation of factory built fireplaces areclea...

Страница 3: ...lso be enclosed to prevent impact damage to the fireplace However the enclosure must now be finished on all four 4 sides The exterior of the enclosure may be finished in a textured plywood a wood clap...

Страница 4: ...wall mate rial surround and hearth extension to your individual taste 7 Assemble and attach optional glass door assembly Study the three dimensional illustration Fig ure 1 to get a general idea of ea...

Страница 5: ...emove it by depressing the locking tabs and pushing down through the outside air opening at the bottom of the fireplace Step 3 On the exposed hole install a PVC threaded coupling reducer 3 4 x 1 2 goi...

Страница 6: ...219mm 52 1327mm 39 1008mm 4 114mm Side View Left Top View 44 1133mm 12 316mm 39 1008mm 9 252mm 1 40mm 1 32mm Drain Plug 11 287mm Metal Safety Strips with 13mm Min Overlap 1 38mm The safety strips shou...

Страница 7: ...e Figure 14 Figure 15 Figure 13 Note All framing dimensions calculated for 1 2 dry wall at the fireplace face If sheathing the chaseorfinishingwithotherthicknessmaterials calculations will need to be...

Страница 8: ...oof from below to mark position Mark and cut a holeintheceiling aroundthenail Figure19 Then plumb from ceiling or roof directly above the cut hole to determine roof hole position Step 6 Route the Clas...

Страница 9: ...ure they engage properly Note For Canadian installations all chimney installedoutsidethebuildingmustbeconstructed with galvalume outer sections only effective January 1 1992 The appropriate model desi...

Страница 10: ...vertical position of the chimney and the 2 minimum air space to combustibles Figure 26 Note Do not caulk or seal the flashing at the chimney Step 6 Secure flashing by nailing along the perimeter into...

Страница 11: ...deter mine the number of chimney sections quan tity and length required Note It is recommended that all exterior ex posed metal chimney components such as ter minations flashings storm collars and or...

Страница 12: ...y be attached together or a section or sections of chimney may be used between but do not exceed 20 in total length between elbows If sections of pipe exceed 10 between elbows a chimney stabi lizer mu...

Страница 13: ...hes Feet Inches 12 18 36 MM M 461 38 5 0 1 13 11722 11 72 465 38 9 2 0 13 11824 11 82 471 39 3 1 1 13 11976 11 98 479 39 11 0 0 14 12179 12 18 489 40 9 1 0 14 12433 12 43 495 41 3 0 1 14 12586 12 59 4...

Страница 14: ...0 0 362 851 17 38 1 0 1 1 0 438 978 20 43 1 0 0 2 0 514 1111 21 45 1 0 0 0 1 533 1149 22 47 1 0 2 1 0 565 1207 25 52 1 0 1 2 0 641 1334 26 54 1 0 1 0 1 667 1378 28 57 1 0 0 3 0 718 1467 29 59 1 0 0 1...

Страница 15: ...TH AN UNVENTED GAS LOG SET TO REDUCE THE RISK OF FIRE OR INJURY DO NOT INSTALL AN UNVENTED GAS LOG SET INTO THIS FIREPLACE If you re installing a gas line connect it before the fireplace is framed and...

Страница 16: ...40 H wall shield constructed of a durable noncombustible material having an equal or better lower k value insulating value than k 84 BTU IN FT2 HR F At no time may a perpendicular side wall be located...

Страница 17: ...earest standard thickness available which is 1 2 If the hearth extension material s that is intended to be used is NOT listed on Table 1 the material can still be used if the material s is noncombusti...

Страница 18: ...e in the installation of this appliance Fireplace Information Model Catalog Number Weight LSO 43 H0303 270 lbs LSO 43 H H0304 270 lbs 18 457mm 45 Combustible Materials Allowed in Shaded Area 1 25mm 18...

Страница 19: ...Termination Square 63L49 FTF10 CT1 Firestop Spacer Flat 63L36 F10FS 2 Chase Termination Round 63L46 FTF10 CTDT Chase Termination Square 63L52 FTF10 CT2 Stabilizer 63L26 FTF10 S4 INSTALLATION COMPONENT...

Страница 20: ...ges at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S...

Отзывы: