background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

16

Fireplace

Opening

Typical Installation

⁹⁄₁₆

"

(167mm)

12"

(305mm)

Min.

Combustible

Mantel

and Trim

Spacer

Noncombustible

Wall Covering

Finished

Wall

12"

(305mm)

Max.

¹⁄₂

" (38mm)

Figure 46

Hearth Extensions and Wall Shields

A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both
radiant heat and sparks. The hearth exten-
sion must extend beyond the front at
least 20" (508 mm) and both sides at least
12" (305 mm) (

Figure 47 ).  Use a hearth

extension constructed of a durable noncom-
bustible material having an equal or better
(lower k value) insulating value of k = .84
BTU IN/FT

HR 

°

F or a thermal resistance

that equals or exceeds r = 1.19 HR 

°

F FT

2

/

BTU IN.  With these values, determine the
minimum thickness/material required using
the formula and 

Page 17.

Note: Any noncombustible material whose k
value is less than .84 or whose r value is more
than 1.19 is acceptable.

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided)
on the floor extending half under the fire-
place and half under the hearth extension.

A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening (

Figure 48 ). Use a 36" W x

36" H wall shield constructed of a durable,
noncombustible material having an equal or
better (lower k value) insulating value than k =
.54 BTU IN/FT

2

 HR 

°

F.  At no time may a

perpendicular side wall be located closer than
9" from the fireplace opening.

If fireplace is installed diagonally across a 90

°

corner; no wall shields are required.

Figure 47

A

B

D

C

C

Hearth Extension Dimensions

A

20" (508 mm)

B

36" (914 mm)

C

12" (305 mm)

D

60" (1524 mm)

Methods of Determini

ng Hearth Extension and Wall Shield

Equivalents - To determine the thickness required for the alternate
material when either the “k” value or “r” value is known, use either the
k formula or r formula.

Example: If Micore 160 is to be used for the hearth extension fireplace,
how thick must this material be?

k

M

 = k value per inch of 

alternate material

r

M

 = r value per inch of 

alternate material

T

M

 =  minimum thickness required for 

alternate material

T

 =  standard thickness of the 

alternate material

k

L

 = k value per inch of 

listed material

r

L

 = r value per inch of 

listed material

T

L

 = minimum thickness of 

listed material

Note:  An asterix “*” indicates, it is a value taken from Table 1.
Using the k formula:

Minimum

k-value (per Inch) of

Specified min.

thickness of

=

alternate material (k

M

) x

thickness

alternate

k-value  (per inch)

of listed

material (T

M

)

of listed material (k

M

)

material (T

L

)

T

M

 (inches)

=

            k

M

x

T

L

         *.84

T

M

 (inches)

=

         *.35

x

1"

         *.84

.416  (inches) =

           .416

x

1"

Answer  - The minimum required thickness of the Micore 160 is .417”,
therefore round up to nearest standard thickness available which is 1/2”.

Using the r formula:

Minimum

r-value (per Inch)

Specified min.

thickness of

=

of listed material

x

thickness

alternate

r-value  (per inch)

of listed

material

of alternate material

material

T

M

 (inches)

=

            r

L

x

T

L

            r

M

T

M

 (inches)

=

         *1.19

x

1"

         *2.86

.416  (inches)=

           .416

x

1"

Содержание COLONIAL COL-3629

Страница 1: ...nstructions before beginning your installation Do not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not l...

Страница 2: ...ur distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16 For additional safety considerations and complete operating instructions refer to...

Страница 3: ...llationinresidentialhomesandbuildingsof conventionalconstruction notinmobilehomes These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for ch...

Страница 4: ...n Note Non Combustible Chase Flashing Must be Used to Cover Chase Opening Optional Insulation in Outside Walls of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 2 4m Level He...

Страница 5: ...ng Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney and surround ma terials such as brick stone...

Страница 6: ...THEM Step 4 Fireplace may be anchored to floor Bend down four 4 anchor tabs located at the base of the fireplace and secure to the floor by nailing with 8d nails Figure 10 Note The Z type safety stri...

Страница 7: ...7 445 mm K 67 1702 mm Framing Dimensions Figure 16 Flue Type A B FTF10 19 19 Vertical 483 mm 483 mm FTF10 30 19 29 Offset 483 mm 737 mm Framing Dimensions for Ceiling Figure 14 Figure 15 Pitch C D 0 1...

Страница 8: ...ward Ensure nothing blocks the hood opening This air duct must never terminate higher than the chimney Step 9 Cut or frame hole through the outside wall for the installation of the duct inlet hood A 4...

Страница 9: ...tenoughtopen etrate the roof flashing openings Figure 26 Always maintain 2 minimum air space to com bustiblematerialsandalwayscheckeachchim ney joint inner and outer to ensure proper engagement Checkv...

Страница 10: ...ntative paint designed for metal This is especially important when installationsaremadeinabnormallyadverseor corrosive environments such as near lakes oceans or in areas with consistently high hu midi...

Страница 11: ...sfromtotaldesiredheight Reference Vertical Elevation Chart and deter minethenumberofchimneysections quantity and length required SPECIAL OFFSET INSTRUCTIONS To clear any overhead obstructions you may...

Страница 12: ...3 Use Elevation Chart as job estimator only Add necessary firestop spacers and sta bilizers as required Firestop spacers must be used as shown in Figures 21 and 22 and stabilizers as shown in Figure...

Страница 13: ...171 14 3 0 0 5 182 15 2 1 0 5 188 15 8 0 1 5 192 16 0 2 0 5 198 16 6 1 1 5 206 17 2 0 0 6 215 17 11 1 0 6 222 18 6 0 1 6 226 18 10 2 0 6 232 19 4 1 1 6 240 20 0 0 0 7 250 20 10 1 0 7 256 21 4 0 1 7 FT...

Страница 14: ...s install the same way as round terminations and stabilizers Step 1 Hold return elbow over top of last chimney section Step 2 Center inner slip section into inner flue pipe slip down Step3 Centerouter...

Страница 15: ...line connects to a gas shut off valve recessed flush into the wall or floor The valve should be controlled by a removable valve key for safety Always plumb gas line installation per local codes Check...

Страница 16: ...BTU IN FT2 HR F At no time may a perpendicular side wall be located closer than 9 from the fireplace opening If fireplace is installed diagonally across a 90 corner no wall shields are required Figure...

Страница 17: ...4 2 3 4 Cultered Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111...

Страница 18: ...er any problems or have ques tions concerning the installation or application of this system please contact your distributor For the name of your nearest distributor call LENNOX HEARTH PRODUCTS 1110 W...

Страница 19: ...2 Firestop Spacer Flat 63L36 F10FS 2 Chase Termination Square 63L52 FTF10 CT2RS INSTALLATION COMPONENTS Firestop Spacer 30 63L37 F10FS30 2 Round Termination 63L55 FTF10 CTDTM Termination Shroud 63L56...

Страница 20: ...at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A...

Отзывы: