NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

6

12

X

Roof Pitch is X/12

2 FT
MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum
Clearance to Combustibles

The vent/air intake termination clearances 
above the high side of an angled roof is as 
follows:

Roof Pitch ................. Feet 

Meters

Flat to 6/12 ................ 1.0 

0.3

6/12 to 7/12 ............... 1.25 

0.38

7/12 to 8/12 ............... 1.5 

0.46

8/12 to 9/12 ............... 2.0 

0.61

9/12 to 10/12 ............. 2.5 

0.76

10/12 to 11/12 ........... 3.25 

0.99

11/12 to 12/12 ........... 4.0 

1.22

12/12 to 14/12 ........... 5.0 

1.52

14/12 to 16/12 ........... 6.0 

1.83

16/12 to 18/12 ........... 7.0 

2.13

18/12 to 20/12 ........... 7.5 

2.29

21/12 to 21/12 ........... 8.0 

2.44

Figure 4

Figure 3

MANUFACTURED (MOBILE) HOME 
REQUIREMENTS

These models may be installed in an after-
market permanently located, manufactured 
home, where not prohibited by local codes. 
When installed in Manufactured Housing 
the following supplemental requirements 
must be met:

•   The appliance must be secured to the fl oor 

(i.e. use (4) ¼” x 2 ¾” bolts and nuts or 
equivalent. Note: Not included) for securing 
appliance to the manufactured home fl oor.

•  The appliance must be grounded to the 

chassis of the manufactured home. Use a 
No. 8 or heavier copper wire at least 18” in 
length.

•   The structural integrity of the manufactured 

home fl oor, walls, ceiling and roof must be 
maintained.

•  A manufactured (mobile) home installation 

must conform with the Manufactured Home 
Construction and Safety Standard, Title 24 
CFR, Part 3280, or, when such a stan-dard 
is not applicable, the Standard for Manufac-
tured Home Installations, ANSI / NCSBCS 
A225.1, or standard for Gas equipped 
Recreational Vehicles and Mobile Housing, 
CSA Z240.4.

Horizontal Vent Termination Clearances

The horizontal vent termination must have 
a minimum of 3" (76 mm) clearance to any 
overhead combustible projection of 2 1/2" (64 
mm) or less. See  Figure 4.  For projections 
exceeding 2 1/2" (64 mm), For additional vent 
location restrictions refer to Figure 5.

VENT TERMINATION CLEARANCES

Vertical Vent Termination  Clearances

These instructions should be used as a 
guideline and do not supersede local codes in 
any way. Install vent according to local codes, 
these instructions, the current National Fuel 
Gas Code (ANSI-Z223.1) in the USA or the 
current standards of CAN/CGA-B149.1 and 
-B149.2 in Canada.

Side Elevation View

QUESTIONS TO ASK LOCAL BUILDING 
OFFICIAL

This appliance must be installed per manu-
facturers’ instructions.

Installations must conform to appropriate 

local codes and applicable state and federal 
requirements.  Familiarity with these require-
ments before installation is essential.  Some 
important considerations to discuss with 
local building offi cials include: 

1. Applicable codes (i.e. Uniform Mechanical 

Code, State or Regional Gas Codes, National 
Fuel Gas Code)

2. Local amendments
3.  Recognized testing lab: OMNI-Test Labora-

tories Inc.; Beaverton, Oregon

4.  Is a permit required - cost?
5.  In some states or municipalities, a licensed 

gas fi tter or plumber may be required to 
install this appliance.  Check with your local 
building offi cial for requirements in your area 
(i.e. Is a license required for installation of 
gas supply line)?

6. Maximum amount of gas pipe without a 

pressure test - type of test required?

7.  Are below grade penetrations of the gas line 

allowed?

8.  Is concealed gas piping allowed?
9. Specifi c requirements of concealed fi t-

tings?

10. Is rigid pipe to appliance required?
11. Allowed piping materials?
12. Shut-off valve required within 4 feet of the 

fi rebox?

13. May the shut-off valve be concealed?
14. Rooms where the installation is not 

allowed?

In the absence of local codes, installation 
should conform to National Fuel Gas Code, 
ANSI Z223.1 / NFPA 54-Latest Edition in the 
USA or National Fuel Gas Code, CAN/CGA-
B149-Latest Edition in Canada.

3"

(76 mm)

12"

(305 mm)

Horizontal T

Combustible Projection

greater than 2 1/2 inches in length

Horizontal Vent Termination Clearances

Combustible Projection

2 1/2

    

 inches or less in length

18"

(457 mm)

Ventilated

Soffit

Unventilated

Soffit

ermination Kit

3"

(76 m

1"

(25 mm

Note - See vent manufacturer's instructions for recess 
allowances, into exterior walls for the horizontal termi-
nation caps.

Содержание 775

Страница 1: ...OTICE POURRÉDUIREAUMINIMUMLERISQUED INCENDIE OUPOURÉVITERTOUTDOMMAGEMATÉRIEL TOUTE BLESSURE OU LA MORT POUR VOTRE SÉCURITÉ Ne pas entreposer ni utiliser d essencenid autrevapeursouliquidesinflammablesdans le voisinage de cet appareil ou de tout autre appareil POUR VOTRE SÉCURITÉ Que faire si vous sentez une odeur de gaz Ne pas tenter d allumer d appareil Ne touchez à aucun interrupteur Ne pas vous...

Страница 2: ...ts Note Installation and repair should be per formed by a qualified service person The appliance should be inspected annually by a qualified professional service technician Morefrequentinspectionsandcleaningsmay berequiredduetoexcessivelintfromcarpet ing bedding material etc It is imperative that the control compartment burners and circulating air passage ways of the appliance be kept clean S assu...

Страница 3: ...Pa 10 5 WC 2 61 kPa Propane 11 0 WC 2 73 kPa 13 0 WC 3 23 kPa Table 2 Manifold Gas Supply Pressure millivolt models Fuel Low High Natural Gas Lo 1 6 WC 40 kPa Hi 3 5 WC 87 kPa Propane Lo 6 3 WC 1 57 kPa Hi 10 0 WC 2 49 kPa Table 3 Ne pas se servir de cet appareil s il a été plongé dans l eau complètement ou en partie Appeler un technicien qualifié pour inspecterl appareiletremplacertoutepartie du ...

Страница 4: ...2 mm SPECIFICATIONS CI1500DVF CI2500DVF Min Max BTU hr Input NG 17 500 28 000 25 500 38 500 Min Max BTU hr Input LP 20 500 27 000 26 500 34 500 DV Vent Size 4 inner 6 5 8 outer Room Fan CFM 150 150 Weight lb 206 290 EFFICIENCIES CI1500DVF CI2500DVF 67 NG 65 LP 67 NG 64 LP Steady State Efficiency Note Due to Lennox ongoing commitment to quality all specifications ratings and dimensions are subject ...

Страница 5: ...00DVF CI2500DVF A minimum 10 254 mm B minimum 14 1 4 362 mm 17 1 4 438 mm C minimum 15 7 8 403 mm 19 483 mm D minimum 4 102 mm 4 102 mm E minimum 2 51 mm 2 51 mm F minimum 4 102 mm 4 102 mm G minimum 0 0 mm 0 0 mm H minimum 62 1575 mm 62 1575 mm I minimum 28 1 2 724 mm 34 1 2 876 mm J MAXIMUM 48 1219 mm 48 1219 mm 10 254 mm Figure 2 CLEARANCES TO COMBUSTIBLE MATERIALS FLOOR PROTECTION The location...

Страница 6: ...nalvent location restrictions refer to Figure 5 VENT TERMINATION CLEARANCES Vertical Vent Termination Clearances These instructions should be used as a guidelineanddonotsupersedelocalcodesin anyway Installventaccordingtolocalcodes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Side Elevation View QUESTION...

Страница 7: ... i w t n e v e r p o t d e d n e m m o c e r m m 9 2 2 9 n o i t a s n e d n o c w o d n i w t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V D l a t n o z i r o h a n i h t i w l a n i m r e t e h t e v o b a d e t a c o l r e t n e c e h t m o r f m m 8 5 4 s e h c n i 8 1 f o e c n a t s i d l a n i m r e t e h t f o e n i l m m 8 5 4 8 1 m m 8 5 4 8 1 t i f f o s d e t a l...

Страница 8: ...sediment and more Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping The gas supply line should be plumbed from thefuelsourcetotheareawheretheappliance is to be installed per requirements outlined in NFPA 54 latest edition USA and B149 latest edition Canada Open both Latches as shown WARNING NEVER OPERATE APPLIANCE WITHOUTTHEFRONTGLASSENCLOSURE PANEL IN PLAC...

Страница 9: ...actory on both models see Figure 11 SIT Millivolt Wiring Diagram If any of the original wire as supplied must be replaced it must be replaced with Type AWM105 C 18 GA wire Thermopile TH TP TH TP ON OFF SWITCH OPTIONAL THERMOSTAT OR REMOTE SWITCH CONTROL RECEIVER Figure 10 Blower Wiring Diagram RELIEF DOOR Theloweraccess doorhingesopen to access Valve Controls Lower Access Door Figure 12 Step 8 INS...

Страница 10: ...ce for Natural Gas and 36 for Propane Gas before the first elbow The horizontal run may extend up to 20 feet 6 meters and include a vertical rise of up to 40 feet 12 meters see Figure 13 Horizontal termination must meet the criteria shown in Figures 4 and 5 Approved vent systems must terminate above and including the heavy line in Figure 13 Two 45 degree elbows may be substituted for each single 9...

Страница 11: ...nversion Kit for 6 I D 1 insulation SV4CCK2 Factory Built Chimney Conversion Kit for 7 I D 1 insulation 8 I D 1 insulation 6 I D 2 insulation SV4CCK3 Factory Built Chimney Conversion Kit for 10 I D 1 insulation 7 I D 2 insulation 8 I D 2 insulation Model Brand SIMPSON DURA VENT Description 934 Masonry Chimney Conversion Kit 931 Factory Built Chimney Conversion Kit A for 6 I D 932 Factory Built Chi...

Страница 12: ...ack 904B 24 Pipe Length Black SV4L36 36 Pipe Length Galvanized 903 36 Pipe Length Galvanized SV4LB36 36 Pipe Length Black 903B 36 Pipe Length Black SV4L48 48 Pipe Length Galvanized 902 48 Pipe Length Galvanized SV4LB48 48 Pipe Length Black 902B 48 Pipe Length Black SV4LA 6 Adj Pipe Length Galvanized 908 6 Adj Pipe Length Galvanized SV4LBA 6 Adj Pipe Length Black N A N A SV4LA12 12 Adj Pipe Length ...

Страница 13: ...rol valve is located in the lower control compartment To access the valve open the lower access door The millivolt control valve has a 3 8 10 mm NPT thread inlet port fitting Figure 20 Ember Strip Rear Log Figure 21 Left Front Log Figure 22 2 Place the largest log onto the rear log stoppers see Figure 20 Ensure that the grooves on the bottom of the log aligns onto the corresponding places on the r...

Страница 14: ...the cor responding pin on the rear log and align it withtheindentationonfrontleftlogasshown in Figure 26 8 Install the front right twig onto the cor responding pin on the right front log Align thetwigwiththeindentationonthefrontright log as shown in Figure 27 9 Place the glowing embers on the burner as shown in Figures 28 29 One package of ember material has been included with this log set You wil...

Страница 15: ... switch MILLIVOLT Thermocouple Hood Igniter Rod 3 8 Min 9 mm Thermopile Pilot Nozzels Figure32 Proper PilotFlameAppearance Figure 33 Burner Flame Appearance Air Shutter Adjustment Guidelines Amount of Primary Air Flame Color Air Shutter Adjustment If air shutter is closed too far Flame will be yellow Air shutter gap should be increased If air shutter is open too far Flame will be blue Air shutter ...

Страница 16: ...Y HEAVY AND MAY REQUIRE A MINIMUM OF TWOPEOPLETOLIFT ONEPERSONONEACH SIDE THE CI1500 SERIES CAST TOP WEIGHS 20 POUNDS AND THE CI2500 SERIES CAST TOP WEIGHS 40 POUNDS B Locate the ash lip from packaging Step 2 Remove the 2 bolts from the tapped holes in theashlip Aligntheashlipbelowthefirebox as shown in Figure 36 the tapped holes in ash lip should align with corresponding slots below firebox Reins...

Страница 17: ...U GAZ A EVACUATION P N 9 1452A SERIAL NUMBER NOMBRE DE SERIE XXXXX XXXXX IIIIIIIIIIIIIIIIIIII XXXXXXXXXXXXXXXX P N 9 1452A MODEL NO CI2500DVF Series MANUFACTURED AT Burlington WA FOR USE WITH NATURAL GAS EQUIPE POUR GAZ NATUREL ALTITUDE MIN GAS SUPPLY PRESS WC PRESS MIN D ALIMENTATION CE MANIFOLD PRESSURE WC PRESSION CE TUBULURE CE MANUFACTURER S RECOMMENDED ORIFICE SIZE DIMENSION DE L INJECTEUR R...

Страница 18: ...P N 775 147M REV C 11 2004 1110 West Taft Avenue Orange CA 92865 Lennox reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information ...

Отзывы: