The LNL-400XA Power Supply Unit (PSU)

The LNL-400XA is a high-efficiency and cost-effective power supply 
designed to house a variety of Lenel controllers and modules in an 

OnGuard

®

 system.

Featuring a regulated 13.8 VDC output, the LNL-400XA supplies 
continuous full rated current to load. Maximum battery life is assured using 
deep discharge protection to prevent premature battery failure when 
operating in standby mode for extended periods. Two sets of volt-free 
contacts are provided to signal (i) loss of mains and (ii) battery and loss of 
output faults.

The LNL-400XA can supply a continuous full-rated current to load plus an 
additional 0.5A for charging a 12V standby battery.

The universal mains input voltage enables the power supply to be used 
across a wide geographical area. The highly efficient switch mode design 
ensures low operating costs while generating less heat. The modular 
construction simplifies maintenance.

Continuous full-rated current-to-load

Universal mains input voltage 90-264 VAC

High-efficiency electronics for reduced running costs and lower 
operating temperatures

Mains transient protection circuit

Lid and removal from wall tamper detection

Installer-safe design with all high-voltage electronics fully shrouded

PCB supports and fixings supplied

Houses a variety of Lenel controllers and modules

PSU status and diagnostic LEDs (mains present and fault)

Volt-free contact signaling mains failure (EPS)

Volt-free contact signaling output and battery faults (GEN)

Full electronic short circuit and overload protection on load output 
under mains operation

Individual battery and output fuse protection

Three-year warranty

Installation

This unit is only suitable for installation as permanently connected 
equipment. The PSU is NOT SUITABLE for external installation.

Before installation, ensure that the mains power source has a separate 
(approved) disconnect device that is fitted with a fuse or other over-current 
protection rated at 3 A maximum. Ensure that the disconnect device has the 
appropriate earth fault protection to the applicable standard.

Before connecting the PSU to the mains power source, verify that the 
external disconnect device is OFF.

Install the PSU according to all relevant safety regulations applicable to the 
application. EQUIPMENT MUST BE EARTHED.

Mounting

1.

Mount the PSU securely in correct orientation allowing minimum 
clearance. Fasten cables using cable tie securing points as shown.

Mounting the Power Supply

2.

Route mains and low voltage output cables via different knockouts 
and/or cable entry holes.

Note:

Use bushes and cable glands rated to UL94 HB minimum.

Mains Power-up

1.

Attach the appropriately-rated mains cable (minimum 0.5mm

2

 [3A], 

300/500 VAC) and fasten using cable ties.

2.

Apply mains power. Check for 13.8 VDC on load outputs. Ensure that 
the green Mains LED is on.

3.

Disconnect mains power.

Load Output

1.

Attach the appropriately-rated load cable and fasten using cable ties. 
Note polarity.

2.

Apply mains power. Check green Mains LED is on.

Note:

The red LED on the PSU may be on to indicate that no battery 
has been connected. This is normal.

3.

Verify load is operating correctly.

4.

Disconnect mains power.

Standby Battery

1.

Attach supplied battery cables to terminal block and battery.

Note:

Ensure correct polarity of battery connections: 

+ve

 use 

red

 lead, 

-ve 

use 

black

 lead.

2.

Apply mains power. Ensure that the green Mains LED is on.

3.

Ensure that there is no fault indication on the red LED (see 

Signaling 

Outputs

).

4.

Disconnect mains power. Check that the batteries continue to supply 
voltage and current to the load. The Green LED should be off.

Note:

Batteries must have sufficient charge to supply the load.

5.

Reconnect mains power. The green LED should be on.

LNL-400XA 13.8 VDC 4A Switch Mode Power Supply

Quick Reference

Содержание LNL-400XA

Страница 1: ... The PSU is NOT SUITABLE for external installation Before installation ensure that the mains power source has a separate approved disconnect device that is fitted with a fuse or other over current protection rated at 3 A maximum Ensure that the disconnect device has the appropriate earth fault protection to the applicable standard Before connecting the PSU to the mains power source verify that the...

Страница 2: ...D flashes and the corresponding EPS or GEN fault signal contacts open Maintenance Note Dispose of used batteries according to the battery manufacturer s instructions and all local and national regulations This unit is intended for use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing calibration chec...

Страница 3: ...t 4 A max Ripple 150 mV pk pk max Load Output Fuse F4 0A Overload Electronic shutdown until overload or short circuit removed under mains power only Standby Battery Battery Type 12 V Valve Regulated Lead Acid Battery Capacity 1 x BS131N 18Ah max Battery Charging Fuse protection F4 0A Mechanical Enclosure Dimensions 400W x 500H x 80D mm Weight excluding battery 5 8 Kg Enclosure Material Steel white...

Страница 4: ...LenelS2 is a part of Carrier 4 DOC 6005 EN US revision 1 002 Controller and Module Layouts LNL 1000 1100 1200 1300 1300 U 1320 2000 2220 4420 LNL 1000 1100 1200 1300 1300e 1300 U 1320 2000 2210 2220 4420 LNL 500 3300 8000 LNL 1300e 2210 ...

Отзывы: