Electrical data
At
T
A
= 25 °C unless otherwise noted.
Parameter
Symbol
Unit
Min
Typ
Max
Comment
Primary continuous direct current
I
P N DC
A
−5000
5000
Primary nominal RMS current
1)
I
P N
A
5000
See graphs on
Primary current, measuring range
I
P M
A
−7072
7072
See graphs on
Measuring resistance
R
M
Ω
0
1.5
Secondary current
I
S
A
−2
2
Turns ratio
N
P
/
N
S
1:2500
Resistance of secondary winding
R
S
Ω
4.3
Primary withstand peak current (max)
1)
Î
P max
kA
25
Mains supply RMS voltage
V
100
240
Rated power supply frequency
f
Hz
50/60
Power consumption
I
P
= 0 A
@ Mains supply = 230 V RMS
P
C
W
VA
38
82
Average
Peak
Power consumption
I
P
=
I
P N DC
(5000 A)
@ Mains supply = 230 V RMS
P
C
W
VA
76
116
Average
Peak
RMS noise current 0 … 10 Hz
2)
I
no
ppm
0.02
RMS noise current 0 … 10 kHz
2)
2.5
RMS noise current 0 … 100 kHz
2)
20
Re-injected RMS noise on primary bus bar
0 ... 100 kHz
µV
10
Electrical offset current
3)
I
O E
ppm
−2
2
Temperature coefficient of
I
O E
3)
TCI
O E
ppm/K
−0.1
0.1
10 °C .. 40 °C
Offset stability
3)
ppm/month
−1
1
Linearity error
3)
ε
L
ppm
−3
3
Delay time @ 90 % of the final output
value
I
P N DC
step
t
D 90
µs
1
With a
d
i
/d
t
≥ 20 A/µs
Frequency bandwidth (± 3 dB)
BW
kHz
0
80
Small-signal
bandwidth,
1 % of
I
P N
DC
d
i
/d
t
accurately followed
d
i
/d
t
A/µs
20
Notes:
1)
With cable length < 12 meters (see graphs page 4)
2)
Single pulse of 100 ms only, not AC. The transducer may require a few seconds to return to
normal operation when autoreset system is running
3)
All ppm figures refer to full-scale which corresponds to a secondary current (
I
S
) output of 2 A.