INTRODUCTION
Page 1
F196
INTRODUCTION
The Lehigh Electric Products Co., Solitaire System is designed to be a self-contained
preset lighting control system, i.e. no external dimming rack is necessary. The
Solitaire is a microprocessor based unit that can control up to 2000 Watts (16.7A) of
lighting load and is available in a 4 and a 6 channel version.
SPECIFICATIONS
Model Numbers:
WBX-4 (4-Channel) and WBX-6 (6-Channel)
Electrical Ratings:
120VAC, 60HZ
Maximum Lighting Load Per Channel:
800 Watts (6.7 Amps)
Maximum Total Lighting Load:
2000 Watts (16.7 Amps), total combined load of all
channels cannot exceed 2000 W
Compatible Load Types:
Incandescent;
use optional Power Booster for Magnetic,
Electronic Low Voltage, Fluorescent or for 277 Volt loads
Maximum Number of Channels per Station:
6
(for more channels, multiple stations
may be daisy chained together, see Figure 3 and Figure 4 for low voltage wiring)
Allowable Fade Times:
0 - 59 seconds and 1 - 60 minutes
Maximum Number of Optional Remote Stations per Master Station:
3
Maximum Allowable Ambient Temperature:
40 C (104 F)
Approvals:
"UL Listed to U.S. and Canadian safety standards"
INSTALLATION
Always check all applicable N.E.C. and local electrical codes before beginning
installation. The Solitaire mounts in a 4 gang, 3 1/2" deep back box. All line voltage
wiring is terminated to screw terminal blocks located on the rear of the unit. All low
voltage control wiring between master stations or optional remote stations is Class
2. The Solitaire must be grounded to an N.E.C. earth ground by connecting to the
chassis ground pigtail provided.
The Solitaire can be fed by either a single 15 - 20 Amp circuit breaker or a two-pole
15 - 20 Amp circuit breaker wired as a "multi-wire branch circuit" as defined in the
N.E.C.*. The Solitaire also requires a Neutral to power the station control
electronics.
Lighting Load
Circuit Breaker Needed
12 Amps or less
(1) 15 Amp
12 - 16 Amps
(1) 20 Amp
up to 16.7 Amps
(1) Two-pole 15 -20 Amp*
*Both circuit breakers in a multi-wire branch circuit must be on the same phase.
Содержание SOLITAIRE WBX-4
Страница 7: ...INSTALLATION Page 4 F196 ...