Using the PRO3X Command Line Interface (CLI)
PRO3X User Guide
–
Command Line Interface (CLI)
140 of 182
Set the Lower Warning threshold for an inlet sensor:
config:#
sensor inlet <n> <sensor type> lowerWarning <option>
Set the deassertion hysteresis for an inlet sensor:
config:#
sensor inlet <n> <sensor type> hysteresis <hy_value>
Set the assertion timeout for an inlet sensor:
config:#
sensor inlet <n> <sensor type> assertionTimeout <as_value>
Variables:
<n> is the number of the inlet that you want to configure. For a single-inlet PDU, <n> is always 1.
<sensor type> is one of the following sensor types:
Sensor type
Description
current
Current sensor
voltage
Voltage sensor
activePower
Active power sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
lineFrequency
Line frequency sensor
phaseAngle
Inlet phase angle sensor
Note: If the requested sensor type is not supported, the "Sensor is not available" message is displayed.