45
MODEL
ITEM
1 kVA FM
2 kVA 72 V
FM
2 kVA 96 V
FM
3 kVA 72 V
FM
3 kVA 96 V
FM
OUTPUT
Overload Capacity
(tolerance±1%)
<105% continuous
106-120% UPS shuts down after 30sec at battery mode or transfer
to bypass when the utility is normal.
121-150% UPS shuts down after 10sec at battery mode or transfer
to bypass when the utility is normal.
>150% Immediately trip at battery mode or transfer to bypass when the
utility is normal.
Transfer Time
(AC to DC)
0 ms
Transfer Time (
Inverter to Bypass)
4 ms (Typical)
BATTERY
Battery Type
Depending on the capacity of external batteries
Number of Batteries
3
6
8
6
8
Maximum Battery AH
160
Rated Battery Voltage
36 V
72 V
96 V
72 V
96 V
CHARGER
Charging Current
2A/4A/6A/8A (selectable)
Floating Mode
Charging Voltage(±1%)
40.9 V±1%
81.9 V±1%
109.2 V±1%
81.9 V±1%
109.2 V±1%
Indication
LED
Utility Normal, Battery Mode, Programmable Outlet1/ Programmable
Outlet2, Bypass Mode & Fault
LCD
Voltage –Input, Output, Battery. Frequency – Input, Output.
Current –Output & Load level % Warning & Fault codes.
Audible
Alarm
Battery Mode
Sounds once every 1.5 seconds
Low Battery
Sounds once every 0.2 seconds
Overload
Continuous tone
Normal Alarm
Sounds once every 3 seconds
Fault
Continuous tone
Protection
Short Circuit
Normal Mode: Output Breaker/Electronic Circuit Battery Mode: Output
Breaker/Electronic Circuit
Battery
Battery Low & High / Electronic Circuit
EPO
UPS shuts down immediately
Over Temperature
Normal Mode: Transfer to Bypass Mode
Battery Mode: UPS shuts down immediately
Содержание PREMIUS
Страница 1: ...PREMIUS 1 10 kVA User and Installation Manual ...
Страница 13: ...13 2 3 2 Rear Panel 1 kVA 3 kVA FMI 3 kVA FM 2 kVA FMI 2 kVA FM 1 kVA FMI ...
Страница 14: ...14 EN PREMIUS 1 10 kVA 5 kVA 6kVA FMI 5 kVA 6kVA FM 7 5 kVA 10kVA FM 7 5 kVA 10kVA FMI ...
Страница 39: ...39 6 Optional Interface Cards 6 1 RSE F RS 485 card 6 2 DCE Dry Contact 6 3 SNMP Card ...
Страница 50: ......