59
Figure 5-41. Battery setting page 3
Figure 5-42. Battery setting page 4
Figure 5-43. Charge setting 1
Figure 5-39. Battery setting page 1
Figure 5-40. Battery setting page 2
Charge setting
5.6.2 Battery management
In setting management page, click battery management icon , it will enter the battery management page.
The page includes battery setting and charging setting, and can be changed by the top button. Click enter box
to change the parameter. Click Save button to save the setting. The marks of setting success and setting
failure is the same as that of system setting.
Battery setting
Batt. Type Setting
Batt. Capacity Set(Ah)
Batt. Cell Number Set(Cell)
Batt. Backup Pre-alarm
Batt. Backup Pre-alarm Time(min)
Changing Set
Lead-acid
100
120
On
5
Next
Back
Save
Battery Set
Batt. Over-volt.Prot.Point(V/Cell)
Batt. Under-volt.Prot.Point(V/Cell)
Secondary Under-volt.Protection
Second Under-volt.Prot.Point(V/Cell)
Batt. Under Volt.Call Self-initiated
Changing Set
2.400
1.700
On
Next
Back
Save
Previous
Battery Set
Off
1.600
Share Parallel Batt.
Batt. Low-temperature Alarm Point(
0
C)
Batt. High-temperature Alarm Point(
0
C)
Batt. Discharging Time
Batt. Discharging Protection Time(h)
Changing Set
-10
50
Next
Back
Save
Previous
Battery Set
18
On
Off
Battery Circuit Abnormal Alarm
Changing Set
Next
Back
Save
Previous
Battery Set
Off
Batt. Equalized Charge Volt.(V/Cell)
Batt. Floating Charge Volt.(V/Cell)
Charging Curr-limiting Coefficient(C)
Battery Charging Current(A)
Equal-Chargr Maintain Time(h)
Changing Set
2.220
2.240
0.35
1.0
5
Next
Back
Save
Battery Set