13
Cast Resin Transformers
Installa
tion, use and main
tenanc
e manual
5.1
Installation examples
The cable connections of High and Low Voltage can be done with cables coming from the bottom or the top.
Some examples are listed below.
5.1.1 Installation in protection enclosure
5. Installation
Dry type cast resin transformers are designed for indoor installations, in a site protected from direct sunlight, in clean and
dry environments, without risk of water intrusion. Standard installation must be:
1. At a sea level height not above 1000 m
2. At a temperature of the cooling air not exceeding the following values:
a.
20 ° C yearly average
b.
30°C warmest month average
c.
40°C maximum
3. According to all other normal operating conditions as per IEC 60076-11 Standard.
During the installation refer to the safety rules existing in your country.
During the operations for the connection and installation, always protect the windings to avoid external
parts such as bolts, washers, cable parts, etc. following into the windings and jeopardizing the insulation
capability of the transformer.
BT
MT
1U
1V
1W
MT
BT
1U
1V
1W
1V
1W
1U