4.2.3 Earthing connection
Before carrying out any other installation operation, connect the earthing wiring coming from the low voltage switchgear
to one of the earthing bars located on the left and right side of the busbars connection system.
The minimum cross-sectional area of the earthing conductor must be chosen according to the following criteria:
• if the cross-sectional area S of the phase conductors is S ≤ 16 mm
2
, the minimum cross-sectional area of the earthing
conductor must be the same as the phase conductors;
• if the cross-sectional area S of the phase conductors is 16 mm
2
< S ≤ 35 mm
2
, the minimum cross-sectional area of the
earthing conductor must be16 mm
2
;
• if the cross-sectional area S of the phase conductors is S > 35 mm
2
, the minimum cross-sectional area of the earthing
conductor must be S/2 mm
2
.
Each earthing cable must be crimped with M8 eyelets and fixed to the earthing metal bar using hex M8x20 screws along
with M8 flat washers and M8 grower washer.
The grower washer must be put on the top of the flat washer.
KEOR MOD 125 – earthing bars
Содержание Keor MOD 100
Страница 1: ...Part LE11406AB 04 19 01 GF Keor MOD Installation and maintenance manual ...
Страница 2: ...2 EN ENGLISH 3 Keor MOD ...
Страница 20: ...20 4 Installation 3 4 5 ...
Страница 22: ...22 4 Installation 9 10 ...
Страница 24: ...24 4 Installation KEOR MOD 250 earthing bars ...
Страница 79: ...Keor MOD Installation and maintenance manual 79 6 3 3 Removal of the SSS drawer 1 2 3 4 ...
Страница 87: ...Keor MOD Installation and maintenance manual 87 ...
Страница 88: ...88 9 Mechanical characteristics ...
Страница 89: ...Keor MOD Installation and maintenance manual 89 ...
Страница 90: ...90 9 Mechanical characteristics ...
Страница 91: ...Keor MOD Installation and maintenance manual 91 9 2 Power module PM25 all the dimensions are in mm ...
Страница 92: ...92 9 Mechanical characteristics 9 3 Battery drawer all the dimensions are in mm ...
Страница 93: ...Keor MOD Installation and maintenance manual 93 9 4 Battery block all the dimensions are in mm ...