LEGRAND DW-311 Скачать руководство пользователя страница 2

2

4’

(1.2m)

20’

(6.1m)

35’

(10.6m)

0

PIR

Coverage

7.5’

(2.2m)

15’

(4.5m)

20’

(6.1m)

35’

(10.6m)

Major motion
Minor motion

Ultrasonic

Coverage

10'

(3.0m)

7.5’

(2.2m)

20’

(6.1m)

15’

(4.5m)

Major motion

Minor motion

Top View

Side View

COVERAGE PATTERNS

Coverage testing has been performed according to the NEMA WD 7 guideline. 

For best performance, use in spaces not larger than 15’ x 12’.

PIR Sensor

The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree 

field of view. The red LED on the sensor flashes when the PIR detects motion.

Masking the lens

Opaque adhesive tape is supplied so that sections of the PIR sensor’s view 

can be masked. This allows you to eliminate coverage in unwanted areas. 

Since masking removes bands of coverage, remember to take this into account 

when troubleshooting coverage problems.

MULTI-WAY

The Multi-Way capability is available on all models. Sensors can easily be wired together for convenient control of a common load. 

When wiring this way, only use DW-311 series sensors. Multi-Way in DW-311 series is not compatible with prior sensor models.
The following principles apply for Multi-Way:

•  All units should be on the same phase.

•  All units can sense each other’s push button events and respond accordingly.

•  All units can sense each other’s PIR trigger event. The response will be determined by the Light Level setting and/or conditions of 

the space of the detecting sensor.

•  The time delay for all units is defined by the unit with the smallest time delay.

•  All Units can sense each other’s dimming events and respond accordingly.

NOTE: 

Models with v2 cannot be used with non-v2 models for multi-way applications.

BUTTON FUNCTIONS

Pressing and holding the UP button will ramp the lights up to the maximum value as determined by the High Trim setting. Pressing 

and holding the DOWN button will dim the lights down to the minimum value as determined by the Low Trim setting. See 

Additional 

Programming Features

 for detail on setting the trim.

•  Tapping the UP button when the load is OFF sets the load to the last non-zero value.

•  Tapping the UP button when the load is ON sets the load to the maximum (high trim) value.

•  Tapping the UP button twice when the load is OFF turns the load to its maximum (high trim) value.

•  Tapping the DOWN button when the load is ON, turns the load OFF.

ADJUSTING THE SENSOR AND ACCESSING OTHER FEATURES

Remove the wall plate. Remove the button cap by firmly squeezing together 

the top sides of the button assembly. Gently pull it away from the unit. 
When the adjustments are completed, replace the button cap by inserting 

its hinges into the tabs on the main unit and then squeeze the top of the 

button while pressing it into the unit. Reinstall the cover plate.

Turning the Load ON (ON Mode)

The relay is programmed for either 

Auto ON

 or 

Manual ON

. In either 

mode, the load can be turned 

ON

 or 

OFF

 using the up and down buttons.

Manual ON

With DIP switch 1 in the 

ON

 position, the occupant must press the 

Up 

button to turn 

ON

 the load. The sensor keeps the load 

ON

 until no motion 

is detected for the selected time delay. There is a 30 second re-trigger 

delay. If occupancy is detected during the delay, the sensor turns the 

load back 

ON

. After the re-trigger delay elapses the 

Up

 button must be 

pressed to turn 

ON

 the load.

Auto ON

With DIP switch 1 in the 

OFF

 position, the load turns 

ON

 and 

OFF

 

automatically based on occupancy. There is a 5 second re-trigger delay. If the load is turned 

OFF

 manually, the enable/disable setting 

for Presentation Mode operation applies.  See

 Presentation Mode / Disable Presentation Mode

 for details.

DELA

Y

MODE

ADDITIONAL 

FEA

TURES

Ultrasonic 

Sensitivity

Adjustment 

Trimpot

TRIGGER

Button

Hinges

Tabs

Dip Switches

Detection LED

  Red = PIR

  Green = Ultrasonic
PIR Lens

Up Button

Down Button

Ultrasonic Cones

Содержание DW-311

Страница 1: ...ow control of the dimming DW sensors contain a light level sensor If adequate daylight is present the sensor holds the load OFF until light levels drop even if the area is occupied See the Light Level...

Страница 2: ...ding the DOWN button will dim the lights down to the minimum value as determined by the Low Trim setting See Additional Programming Features for detail on setting the trim Tapping the UP button when t...

Страница 3: ...ogramming is complete return all four DIP switches to the OFF value The DW 311 exits Setup Mode saves the current values for each feature and resumes normal operation The saved values are remembered i...

Страница 4: ...links three times if you are selecting Smart Light Level mode 4 Set the four DIP switches so that they are all in the Down position 5 Step away from the sensor After 10 seconds the unit will beep twic...

Страница 5: ...If the lights come ON adjust the light level setting 3 If lights still do not turn ON call 800 879 8585 for technical support Lights do not turn ON with motion LED does not flash 1 Press and holde th...

Страница 6: ...le courant a bien t COUP au niveau du disjoncteur 2 Raccordez les fils aux c bles volants du DW comme illustr dans le sch ma de c blage correspondant votre mod le de DW et votre alimentation lectriqu...

Страница 7: ...de maintenir le bouton HAUT enfonc permet d augmenter la lumi re jusqu la valeur maximale d finie l aide du param tre Niveau maximum Le fait de maintenir le bouton BAS enfonc permet de r duire la lumi...

Страница 8: ...n unique des interrupteurs DIP Lorsque vous s lectionnez les valeurs sp cifiques la DEL rouge clignote pour indiquer que vous tes en mode r glage Dans le mode r glage la DEL verte clignote de mani re...

Страница 9: ...de luminosit Cette fonctionnalit permet de d finir un seuil de luminosit qui d termine la r action du DW 311 en fonction du niveau de luminosit ambiant Cette fonctionnalit est uniquement disponible lo...

Страница 10: ...niveau de luminosit la luminosit ambiante la plus intense ne maintiendra pas les lumi res TEINTES R GLAGES DES INTERRUPTEURS DIP ALLUM TEINT 1 Marche automatique Marche manuelle Mode 9 1 2 3 4 5 6 7...

Страница 11: ...qu aucune source de chaleur importante ampoule de forte intensit par exemple ne se trouve proximit du d tecteur 3 Si les lumi res ne S TEIGNENT toujours pas appelez le 1 800 879 8585 pour obtenir une...

Страница 12: ...como se muestra en el diagrama de cableado apropiado para el modelo DW y el suministro el ctrico El cable a tierra verde debeajustarse a tierra para que el sensor funcione correctamente 3 Adjunte el s...

Страница 13: ...uperiores del conjunto del bot n Con cuidado ret rela de la unidad Cuando se completen los ajustes vuelva a colocar la tapa del bot n insertando sus bisagras en las pesta as de la unidad principal y l...

Страница 14: ...na vez que seleccione los valores espec ficos el LED rojo parpadea para indicar que se encuentra en el modo de configuraci n Mientras se encuentre en el modo de configuraci n el LED verde parpadear de...

Страница 15: ...l nivel de luz ambiente Esta funci n est disponible nicamente cuando el DW 311 se configura en Encendido autom tico Hay dos modos de ajuste de nivel de luz En el modo Est ndar se establece un nivel m...

Страница 16: ...ontrol de nivel de luz la luz ambiente m s brillante no mantendr la luz Apagada CONFIGURACI N DEL CONMUTADOR SELECTOR PARA BASCULAR ENCENDIDO APAGADO 1 Mode 9 1 2 3 4 5 6 7 8 Modo ON Activador Prueba...

Страница 17: ...cables en especial la conexi n de l nea Verifique que las conexiones est n aseguradas firmemente 3 Si las luces todav a no se encienden llame al 800 879 8585 para obtener soporte t cnico Las luces no...