1/8
Data sheet: S000077898EN-2
Updated: 03/07/2014
Created: 10/03/2014
Cat.No(s): 0 489 17
Corridor lighting management sensor - PIR
1. USE
This device allows a light source to be controlled automatically through
the detection of movement in the surveillance zone.
It can be installed in places of passage such as corridors. It has an
auxiliary output and can be used to control ventilation (switch to
comfort ECO mode) when motion is detected.
Motion sensor with 180° detection angle.
Detection type: infrared (PIR)
Mounting type: wall
2. TECHNICAL CHARACTERISTICS
Voltage: 100 - 240 V~
Frequency: 50/60 Hz
No-load power consumption: 0.6 W
Output via normally open contact connected to the phase
Wiring: 2 x 2.5 mm
2
Number of terminals: 6
Terminal type: screw
Stripped length: 8 mm
Drilling diameter: 67 mm with flush-mounting box
Weight: 120 g
Impact resistance: IK04
Penetration by solid and liquid matter: IP42
Operating temperature: -5 °C to +45 °C
Storage temperature: -20 °C to +70 °C
2. TECHNICAL CHARACTERISTICS (continued)
Products qualified for 40,000 operations
Zero current breaking: in order to limit the effect of the current draw on
the cut-off relay by the fluorescent loads in particular, this sensor cuts
out at zero current. Switching occurs when the voltage reaches 0 which
helps to prolong the life of the power supplies and the sensor.
Cover removed
CONTENTS Page
1. Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Technical characteristics . . . . . . . . . . . . . . 1
3. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5. Dismantling. . . . . . . . . . . . . . . . . . . . . . . . . . 3
6. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . 3
7. Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
8. Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
9. Performance . . . . . . . . . . . . . . . . . . . . . . . . . 7
10. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
11. Standards and approvals . . . . . . . . . . . . . 8
12. Troubleshooting . . . . . . . . . . . . . . . . . . . . . 8
Light level cell
PIR sensor
Learn button
Detection LED
Learn LED
1 - Halogen bulbs
2 - ELV halogen, compact fluorescent and fluorescent bulbs with
separate electronic ballast
3 - ELV halogen, compact fluorescent and fluorescent bulbs with
separate ferromagnetic ballast
4 - Fluorescent tubes
5 - Compact fluorescent bulbs with built-in electronic ballast
6 - Compact fluorescent bulbs with built-in ferromagnetic ballast
7 - LED bulbs
1
2
3
4
5
6
7
8
8 - Contactor
9 - Motor
230 V~ 2000 W 8.5 A 1000 VA
4.3 A
1000 VA
4.3 A
10x(2x36 W) 4.3 A
250 W
1 A
250 W
1 A
250 W
1 A
500 VA
2.1 A
110 V~ 1000 W 8.5 A
500 VA
4.3 A
500 VA
4.3 A
5x(2x36 W)
4.3 A
125 W
1 A
125 W
1 A
125 W
1 A
250 VA
230 V~
500 VA 2.1 A
max.
I max.
≤ 2.1 A
110 V~
250 VA
U ≤ 30 V
=
2.1 A max.