background image

3/8

CONTENTS

Data sheet: S000077898EN-2 

Updated: 03/07/2014 

Created: 10/03/2014

Cat.No(s): 0 489 17

Corridor lighting management sensor - PIR

PIR

2.1 A max.

SN

S2

S1

100 m max.

8.5 A 

max.

8.5 A 

max.

8.5 A 

max.

PB

LN

L2

L1

   4.  CONNECTION (continued)

4.4 Wiring for several loads connected in parallel

1

2

  5. DISMANTLING

  6. INSTALLATION

6.1   Installation recommendations

2.5 m

3.5 m

6.2  Recommended light exposure

Содержание 0 489 17

Страница 1: ... current breaking in order to limit the effect of the current draw on the cut off relay by the fluorescent loads in particular this sensor cuts out at zero current Switching occurs when the voltage reaches 0 which helps to prolong the life of the power supplies and the sensor Cover removed CONTENTS Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 2 4 Connection 2 5 Dismantling 3 6 Installat...

Страница 2: ...ng management sensor PIR 3 DIMENSIONS With protective cover 84 46 31 118 2 1 A max SN S2 S1 100 m max 8 5 A max PB 8 5 A max 2 1 A max PB 100 m max 8 5 A max 2 1 A max V U 30 V 4 CONNECTION 4 1 Wiring with auxiliary control 4 3 Wiring for a single load connected in parallel 4 2 Wiring without auxiliary control ...

Страница 3: ...Corridor lighting management sensor PIR PIR 2 1 A max SN S2 S1 100 m max 8 5 A max 8 5 A max 8 5 A max PB LN L2 L1 4 CONNECTION continued 4 4 Wiring for several loads connected in parallel 1 2 5 DISMANTLING 6 INSTALLATION 6 1 Installation recommendations 2 5 m 3 5 m 6 2 Recommended light exposure ...

Страница 4: ... Created 10 03 2014 Cat No s 0 489 17 Corridor lighting management sensor PIR 6 INSTALLATION continued 6 3 Positioning 6 INSTALLATION continued 6 3 Positioning continued 3 50 Ø 67 4 0 489 71 6 4 Choice of detection zone CLICK CLICK CLICK 1 2 3 2 60 mm 1 60 mm ...

Страница 5: ...ion It is possible to control the sensor by infrared remote control using Cat Nos 0 882 20 31 7 2 More than one sensor and more than one load Synchronising the products is done in two stages one long press 1s all the sensors S change to ON one short press all the sensors S invert their state from OFF to ON or ON to OFF L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ...

Страница 6: ...r parameter Default value Modifiable parameters Configuration tools 0 882 30 0 882 35 Time delay 15 mn 3 5 10 15 20 min 5 sec 59 min 59s Sensitivity PIR very high Low medium high very high Modes Auto on Auto off Inactive Activate Deactivate Walk through mode Active Activate Deactivate Manual on Auto off Inactive Activate Deactivate Detection system Initial PIR Non modifiable Maintain PIR Non modif...

Страница 7: ...4 6 5 6 Maximum installation height 3 m Height 2 5 m Sensitivity Low 25 Sensitivity Medium 50 Sensitivity High 75 Sensitivity Very high 100 a m b m a m b m a m b m a m b m 8 4 10 6 12 6 15 6 Maximum installation height 3 m 9 PERFORMANCE 9 1 Radial movement 9 3 Performance with blanking plate CLICK CLICK b b a a CLICK CLICK CLICK CLICK 15 m 15 m 5 m 5 m 5 2 5 m 2 5 m 0 0 0 0 CLICK CLICK 3 m 15 m 5 ...

Страница 8: ...off during the day when there is an adequate level of natural light Regulation function not active Light level threshold set too high Light source too bright Activate the regulation function Reduce the light level threshold Check that the sensor is positioned correctly in relation to the window Decrease the power of the luminaires Lighting switches off when there are people present and the natural...

Отзывы: