CONTENTS

Data sheet: S000077898EN-2 

Updated: 03/07/2014 

Created: 10/03/2014

Cat.No(s): 0 489 17

Corridor lighting management sensor - PIR

PB

PB

PB

PB

PB

  7. OPERATION

7.1  Outputs

- The load (lighting output) switches on when motion is detected (auto 

mode) or if the control is pressed (manual ON/auto OFF mode) and 

there is insufficient natural light.

- The load (lighting output) switches off at the end of the time delay or 

when the level of natural light is adequate.

- The load (auxiliary output) switches on when motion is detected (auto 

mode and manual ON/auto OFF mode).

- The load (auxiliary output) switches off at the end of the time delay 

only.

Manual ON/Automatic OFF mode: 

 

Pressing the auxiliary control allows the load to be switched on or off 

manually. If the control is not pressed, the sensor will cut off the load 

at the end of the time delay or when the light level threshold has been 

reached.

Auto ON/OFF mode: 

 

The load will be switched on and off automatically.

Option:

  It is possible to control the sensor by infrared remote control 

using Cat. Nos. 0 882 20/31.

7.2  More than one sensor and more than one load

Synchronising the products is done in two stages:
- one long press (>1s) - all the sensors (S) change to ON 
-  one short press - all the sensors (S) invert their state from OFF to ON or 

ON to OFF

 L1 OFF

 L2 OFF

 Ln OFF

 S1 OFF

 S2 OFF

 Sn OFF

< 1 s

 L1 ON

 L2 ON

 Ln ON

 S1 ON

 S2 ON

 Sn ON

 L1 ON

 L2 ON

 Ln ON

 S1 ON

 S2 ON

 Sn ON

< 1 s

 L1 OFF

 L2 OFF

 Ln OFF

 S1 OFF

 S2 OFF

 Sn OFF

 L1 ON

 L2 OFF

 Ln OFF

 S1 ON

 S2 OFF

 Sn OFF

< 1 s

 L1 OFF

 L2 ON

 Ln ON

 S1 OFF

 S2 ON

 Sn ON

PB

PB

PB

PB

PB

   7.  OPERATION (continued)

7.3  Several sensors connected to a single load

 L OFF

 S1 OFF

 S2 OFF

 Sn OFF

< 1 s

 L ON

 S1 ON

 S2 ON

 Sn ON

 L ON

 S1 ON

 S2 ON

 Sn ON

< 1 s

 L OFF

 S1 OFF

 S2 OFF

 Sn OFF

 L ON

 S1 ON

 S2 OFF

 Sn OFF

< 1 s

 L ON

 S1 OFF

 S2 ON

 Sn ON

 L ON

 S1 ON

 S2 OFF

 Sn OFF

> 1 s 

                      + 

                   < 1 s

 L OFF

 S1 OFF

 S2 OFF

 Sn OFF

 L ON

 S1 ON

 S2 OFF

 Sn OFF

> 1 s

 L ON

 S1 ON

 S2 ON

 Sn ON

 L1 ON

 L2 OFF

 Ln OFF

 S1 ON

 S2 OFF

 Sn OFF

> 1 s 

                      + 

                   < 1 s

 L1 OFF

 L2 OFF

 Ln OFF

 S1 OFF

 S2 OFF

 Sn OFF

 L1 ON

 L2 OFF

 Ln OFF

 S1 ON

 S2 OFF

 Sn OFF

> 1 s

 L1 ON

 L2 ON

 Ln ON

 S1 ON

 S2 ON

 Sn ON

7.2 More than one sensor and more than one load (continued)

Содержание 0 489 17

Страница 1: ... current breaking in order to limit the effect of the current draw on the cut off relay by the fluorescent loads in particular this sensor cuts out at zero current Switching occurs when the voltage reaches 0 which helps to prolong the life of the power supplies and the sensor Cover removed CONTENTS Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 2 4 Connection 2 5 Dismantling 3 6 Installat...

Страница 2: ...ng management sensor PIR 3 DIMENSIONS With protective cover 84 46 31 118 2 1 A max SN S2 S1 100 m max 8 5 A max PB 8 5 A max 2 1 A max PB 100 m max 8 5 A max 2 1 A max V U 30 V 4 CONNECTION 4 1 Wiring with auxiliary control 4 3 Wiring for a single load connected in parallel 4 2 Wiring without auxiliary control ...

Страница 3: ...Corridor lighting management sensor PIR PIR 2 1 A max SN S2 S1 100 m max 8 5 A max 8 5 A max 8 5 A max PB LN L2 L1 4 CONNECTION continued 4 4 Wiring for several loads connected in parallel 1 2 5 DISMANTLING 6 INSTALLATION 6 1 Installation recommendations 2 5 m 3 5 m 6 2 Recommended light exposure ...

Страница 4: ... Created 10 03 2014 Cat No s 0 489 17 Corridor lighting management sensor PIR 6 INSTALLATION continued 6 3 Positioning 6 INSTALLATION continued 6 3 Positioning continued 3 50 Ø 67 4 0 489 71 6 4 Choice of detection zone CLICK CLICK CLICK 1 2 3 2 60 mm 1 60 mm ...

Страница 5: ...ion It is possible to control the sensor by infrared remote control using Cat Nos 0 882 20 31 7 2 More than one sensor and more than one load Synchronising the products is done in two stages one long press 1s all the sensors S change to ON one short press all the sensors S invert their state from OFF to ON or ON to OFF L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ...

Страница 6: ...r parameter Default value Modifiable parameters Configuration tools 0 882 30 0 882 35 Time delay 15 mn 3 5 10 15 20 min 5 sec 59 min 59s Sensitivity PIR very high Low medium high very high Modes Auto on Auto off Inactive Activate Deactivate Walk through mode Active Activate Deactivate Manual on Auto off Inactive Activate Deactivate Detection system Initial PIR Non modifiable Maintain PIR Non modif...

Страница 7: ...4 6 5 6 Maximum installation height 3 m Height 2 5 m Sensitivity Low 25 Sensitivity Medium 50 Sensitivity High 75 Sensitivity Very high 100 a m b m a m b m a m b m a m b m 8 4 10 6 12 6 15 6 Maximum installation height 3 m 9 PERFORMANCE 9 1 Radial movement 9 3 Performance with blanking plate CLICK CLICK b b a a CLICK CLICK CLICK CLICK 15 m 15 m 5 m 5 m 5 2 5 m 2 5 m 0 0 0 0 CLICK CLICK 3 m 15 m 5 ...

Страница 8: ...off during the day when there is an adequate level of natural light Regulation function not active Light level threshold set too high Light source too bright Activate the regulation function Reduce the light level threshold Check that the sensor is positioned correctly in relation to the window Decrease the power of the luminaires Lighting switches off when there are people present and the natural...

Отзывы: