  8. SETTINGS

8.1   Detection parameters

   Time  delay:

 Length of time the load is on after detection occurs 

 Sensitivity:

 Detection range setting 

Modes:

 Auto on/Auto off mode:

 

The lighting switches on automatically: 

- When movement is detected and there is insufficient natural light. 

The lighting switches off automatically: 

- If no movement is detected at the end of the set time delay. 

- Or if there is an adequate level of natural light (regulation function 

activated).

The lighting will switch on again automatically if another movement is 

detected and there is insufficient light.

 Walk-through mode:

-  If no movement is detected in the 20 seconds following an initial 

detection, the device will cut off the load after 3 minutes.

-  If another movement is detected in the 3 minutes following initial 

detection, the device will cut off the load at the end of the set time 

delay.

 Manual on/Auto off mode:

 

The lighting is switched on manually and switched off automatically: 

-  If no movement is detected at the end of the set time delay.
After switch-off, if any movement is detected within a 30-second period, 

the lighting switches on automatically (provided the Restart function 

has been activated).

For any period of inactivity longer than 30 seconds, the lighting is 

switched on manually.

Detection system:
Initial detection:

 The load is switched on as soon as the first detection 

occurs if the natural light level is below the light level threshold.

Maintain: 

The load remains active if another movement is detected.

Restart:

 In manual mode. After switch-off, if any movement is detected 

within a 30-second period, the lighting switches on automatically.

For any period of inactivity longer than 30 seconds, the lighting must be 

switched on manually. 

Possible in Manual on/Auto off mode only.

Alarm:

 An audible signal is emitted before switch-off (1 minute before, 

then 30 seconds, then 10 seconds).

Sensor parameter

Default 

value

Modifiable  

parameters

Configuration  

tools

0 882 30 0 882 35

Time delay

15 mn

3,5,10,15,20 min

5 sec - 59 min 59s

Sensitivity

PIR (very 

high)

Low, medium, 

high, very high

Modes

Auto on/Auto off

Inactive

Activate/

Deactivate

Walk-through 

mode

Active

Activate/

Deactivate

Manual on/Auto 

off

Inactive

Activate/

Deactivate

Detection  system

Initial

PIR

Non-modifiable

Maintain

PIR

Non-modifiable

Restart

PIR

PIR and/or US, PIR, 

US, Deactivate

Alarm

Inactive

Activate/

Deactivate

   8.  SETTINGS (continued)

8.2   Light parameters

  Light level threshold:

 Value at which the load switches on if the 

natural light level is less than the setting.

  Eye function:

 Value 0 (eye on configuration tool 0 882 30) is 

used to save the ambient light level in the room as the light level 

threshold.

Advanced mode:

    Calibration:

 The ambient light level measured with a luxmeter 

must then be transmitted to the sensor.

    Regulation:

 Automatic switch-off of the load 10 minutes after the 

light level threshold is exceeded with an additional safety threshold 

(to avoid lights switching off at the wrong moment).

Light contribution:

 Quantity of additional lux brought in by the load 

being switched on.  

When the light contribution parameter is set to "Auto" (value 0) on 

configuration tool Cat. No. 0 882 30, the sensor automatically calculates 

the light contribution.

 8.3 Modifying the parameters using the configuration tools

Warning: 

Make sure blanking plate is removed before  

modifying parameters with a configuration tool.

• 0 882 35: Simplified configuration tool 

• 0 882 30: Advanced configuration tool

When the sensor receives an IR command via the configuration tool  

it emits a beep to confirm the modification.

For more information about setting parameters, refer to the 

configuration tool (Cat. No. 0 882 30) data sheet.

-  Restore factory settings:

1st press: Short press on LEARN; the LED flashes slowly.

2nd press:  Press LEARN for 10 seconds until the LED flashes quickly.

Sensor parameter

Default 

value

Modifiable  

parameters

Configuration  

tools

0 882 30 0 882 35

Light level threshold

300 lux

20, 100, 300, 500, 

1000 lux

5 - 1275 lux

Advanced

 

mode

Calibration

0 - 99995 lux

Regulation

Active

Activate/

Deactivate

Light  

contribution

Auto

Auto - 1275 lux

Содержание 0 489 17

Страница 1: ... current breaking in order to limit the effect of the current draw on the cut off relay by the fluorescent loads in particular this sensor cuts out at zero current Switching occurs when the voltage reaches 0 which helps to prolong the life of the power supplies and the sensor Cover removed CONTENTS Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 2 4 Connection 2 5 Dismantling 3 6 Installat...

Страница 2: ...ng management sensor PIR 3 DIMENSIONS With protective cover 84 46 31 118 2 1 A max SN S2 S1 100 m max 8 5 A max PB 8 5 A max 2 1 A max PB 100 m max 8 5 A max 2 1 A max V U 30 V 4 CONNECTION 4 1 Wiring with auxiliary control 4 3 Wiring for a single load connected in parallel 4 2 Wiring without auxiliary control ...

Страница 3: ...Corridor lighting management sensor PIR PIR 2 1 A max SN S2 S1 100 m max 8 5 A max 8 5 A max 8 5 A max PB LN L2 L1 4 CONNECTION continued 4 4 Wiring for several loads connected in parallel 1 2 5 DISMANTLING 6 INSTALLATION 6 1 Installation recommendations 2 5 m 3 5 m 6 2 Recommended light exposure ...

Страница 4: ... Created 10 03 2014 Cat No s 0 489 17 Corridor lighting management sensor PIR 6 INSTALLATION continued 6 3 Positioning 6 INSTALLATION continued 6 3 Positioning continued 3 50 Ø 67 4 0 489 71 6 4 Choice of detection zone CLICK CLICK CLICK 1 2 3 2 60 mm 1 60 mm ...

Страница 5: ...ion It is possible to control the sensor by infrared remote control using Cat Nos 0 882 20 31 7 2 More than one sensor and more than one load Synchronising the products is done in two stages one long press 1s all the sensors S change to ON one short press all the sensors S invert their state from OFF to ON or ON to OFF L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ...

Страница 6: ...r parameter Default value Modifiable parameters Configuration tools 0 882 30 0 882 35 Time delay 15 mn 3 5 10 15 20 min 5 sec 59 min 59s Sensitivity PIR very high Low medium high very high Modes Auto on Auto off Inactive Activate Deactivate Walk through mode Active Activate Deactivate Manual on Auto off Inactive Activate Deactivate Detection system Initial PIR Non modifiable Maintain PIR Non modif...

Страница 7: ...4 6 5 6 Maximum installation height 3 m Height 2 5 m Sensitivity Low 25 Sensitivity Medium 50 Sensitivity High 75 Sensitivity Very high 100 a m b m a m b m a m b m a m b m 8 4 10 6 12 6 15 6 Maximum installation height 3 m 9 PERFORMANCE 9 1 Radial movement 9 3 Performance with blanking plate CLICK CLICK b b a a CLICK CLICK CLICK CLICK 15 m 15 m 5 m 5 m 5 2 5 m 2 5 m 0 0 0 0 CLICK CLICK 3 m 15 m 5 ...

Страница 8: ...off during the day when there is an adequate level of natural light Regulation function not active Light level threshold set too high Light source too bright Activate the regulation function Reduce the light level threshold Check that the sensor is positioned correctly in relation to the window Decrease the power of the luminaires Lighting switches off when there are people present and the natural...

Отзывы: