26
Appendix 2: Symbol instructions:
Symbols and significations
Symbol
Significations
Symbol
Significations
Caution
Protect grounding
Danger! High Voltage!
Alarm cancel
Turn on
Overload
Turn off
Battery inspection
Standby or Shutdown
Repeat
AC
Display screen repeat key
DC
Battery
Appendix 3: Specification Sheet
MODEL
LEGA 3106
LEGA 3110
LEGA 3115
LEGA 3120
Capacity
6KVA/5.4KW
10KVA/9KW
15KVA/13.5KW
20KVA/18KW
INPUT
Rated Voltage
3/1: 360V/365V/380V/400V/415VAC;
1/1: 208V/210V/220V/230V/240VAC.
(Set up by LCD display)
Voltage Range
3/1: Half load (190-
520)±5VAC, Full load (277-520)±5VAC;
1/1: Half load (110-
300)±5VAC, Full load (160-300)±5VAC.
Frequency
40-
70Hz±0.5% (Auto sensing)
Power Factor
3/1: ≥0.95;
1/1: ≥0.99.
BYPASS
Voltage Range
160V-Rated output 32V
Frequency
50/60Hz±5Hz
OUTPUT
Voltage
208V/210V/220V/230V/240Vac Setting available via LCD
Voltage Regulation
±1%
Frequency
Synchronized with utility on AC mode; 50/60±0.1Hz on battery mode
Waveform
Pure sine wave
Crest Factor
3:1
Harmonic Distortion
≤2%(Linear load); ≤5%(Non-linear load)
Transfer Time
AC mode to battery mode: 0ms
Inverter mode to bypass mode: 0ms
Overload Capability
105%-125%: Transfer to bypass after 3mins;
125%-150%: Transfer to bypass after 30s;
>150%: Transfer to bypass after 100ms
EFFICIENCY
AC Mode
≥93%