background image

LEAK

SAFE

 SOLUTIONS  

|

  WATERSWITCH2 INSTALLATION INSTRUCTIONS  

|

  VERSION 3

PAGE 03

Wired aux ON/OFF 

via BM system to 

open/close valve(s) 

OV = common

Volt free output relay

Setting DIPs switches

Input L for directly 

connected leak 

detection tape

Setting button

Yellow LED

2nd valve 

connection (optional)

green = open

black = OV

red = close

Input V for 5VDC Valve

Input F for Flow 

Sensor (optional)

3 x AA 1.5 batteries

Mains Power Adaptor 

connection 9VDC- 

‐12VDC 300mA

Figure 1. Water valve control, switches and connections

1.  PROGRAMMING & TEST INSTRUCTIONS

1.1  Programming the WaterSwitch Valve Control

Lift and remove the catch cover on the top of the case. Press the catch underneath to release the front panel. 

If the Water Valve Control is to be mains powered or any other auxiliary connections are to be made, cut out cable paths and connect 
to terminals as shown in Figure 1.

Install 3 x AA batteries (the Water Valve Control will beep 3 times to indicate correct installation). Plug in to mains supply if a power 
adaptor is being used.

If installing an Extended Range system, install 3 x AA batteries in the battery compartment of the Valve Driver (the Driver will beep to 
indicate correct installation).  If the Valve Driver is to be mains powered, drill a cable entry point and connect the mains power adaptor 
cable to the 12V terminal block as indicated on the PCB.

Follow the programming Instructions (sections 1.2 & 1.3) and wireless tests (sections 1.6.2 & 1.6.4) before mounting the Water Valve 
Control and the Valve Driver (if installing an Extended Range system) in its intended position.

1.2  Water Valve Control – DEFAULT SETTINGS

Set Water Valve Control DEFAULT SETTINGS using the DIP switches and Setting Button on the PCB (Figure 1). 

1.  To set AUTO CHECK THAT A VALVE IS CONNECTED set DIP 1 ON. All other DIPs OFF.  If set, an alarm will sound if valve is 

disconnected.

 

DEFAULT = do not check (DIP 1 OFF).

2.  To set VALVE AUTO CLOSE ON MAINS POWER FAILURE (when using the optional mains power adaptor) set DIP 2 ON. All other 

DIPs OFF.

 

DEFAULT = do not close valve on mains power failure (DIP 2 OFF).

Once the DIPs are set, press and hold the Setting Button UNTIL the Yellow LED comes on and continue to hold until it flashes. Release 
the Setting Button. The Water Valve Control will beep twice to confirm that the settings are stored in memory.

Содержание WaterSwitch2

Страница 1: ...LeakSafe solutions TM WaterSwitch2 Installation Instructions ...

Страница 2: ... PAGE 02 WATERSWITCH2 COMPONENTS Valve Wireless On Off Switch with delay function Water Flow Sensor Wireless Leak Detection transmitter Leak Detection tape available in 0 3M or 1M lengths and 1 5M connecting cable WaterSwitch2 Valve Control Extended Range Valve Driver ...

Страница 3: ... system install 3 x AA batteries in the battery compartment of the Valve Driver the Driver will beep to indicate correct installation If the Valve Driver is to be mains powered drill a cable entry point and connect the mains power adaptor cable to the 12V terminal block as indicated on the PCB Follow the programming Instructions sections 1 2 1 3 and wireless tests sections 1 6 2 1 6 4 before mount...

Страница 4: ...pprox 4 seconds to operate Release the button when the Valve Control beeps Press the WATER ON button on the Water Valve Control and the red LEAK FLOW ALARM LED will illuminate Press the Enrol button on the Valve Driver Figure 3 for approx 3 5 seconds and then release it The Valve Control will emit a short beep and the Valve Driver will give a long single beep to indicate successful enrolment Time ...

Страница 5: ...TE THE VALVE NB THE WATER ON WATER OFF AND TEST BUTTONS Figure 2 MUST BE HELD DOWN FOR APPROX 4 SECONDS TO OPERATE THE WATER VALVE CONTROL WILL BEEP WHEN A COMMAND IS ACCEPTED 1 Ensure a Valve is connected to input V on the bottom of the Water Valve Control or the connection lead on the valve driver if installed 2 Press and hold down the WATER ON button until it beeps once The green VALVE OPERATIN...

Страница 6: ...d insert 2 x AA batteries as shown on the battery holder and reassemble the transmitter will beep 3 times to confirm correct installation Leave the cover off the transmitter whilst you complete the enrolling procedure 2 Press the TEST button on the Valve Control 4 times holding the button down each time until the LEDs illuminate and the Valve Control beeps The first three times all 3 LEDs will ill...

Страница 7: ...rom the Water Valve Control press the WATER OFF button on the Switch The Valve Control will beep twice the VALVE OPERATING green LED will flash and the valve will close 2 Press WATER ON to reopen the valve 1 6 3 Installing batteries and enrolling a Wireless On Off Switch 1 Install the CR2032 battery 2 Ensure that the On Off Switch is at least 1M away from the Water Valve Control 3 Press the TEST b...

Страница 8: ... installed The Flow Sensor is usually installed after the Valve but can be installed either before or after the valve depending on the available amount of room on the pipe If room permits the Flow Sensor can be connected directly to the valve as shown Figure 7 If space is limited the sensor can be located on the pipe separately to the valve However it must be positioned before any tee off points a...

Страница 9: ...which the wireless signal will work will depend on a number of factors including building construction position of the Water Valve Control and Wireless Transmitter and in some instances the effect of interference from other wireless or electronic devices Test the wireless signal between the Wireless Leak Detector Transmitter and the Water Valve Control by temporarily positioning all the components...

Страница 10: ...r naturally or with a hairdryer on a medium setting held 1M away from the tape or on a warm not hot radiator 5 Reposition and reconnect the tape once dry 6 Press WATER ON on the Water Valve Control to open the valve 1 2 3 3 To connect the 1 5M connection cable to two or more lengths of leak detection tape with interconnecting 2 core cable between crimp the female bullet connectors at the end of th...

Страница 11: ...and at right angles when closed Push operating button down when finished Manual operating button Valve status window Fig 10 4 INDICATORS AND ALARMS 3 4 Manual override on the Motorised Valve LEAK ALARM VALVE OPERATING WARNING 3 3 Isolating a leak and turning the water on Leaksafe recommend you repair all leaks before the mains water is turned back on Where a detected leak is from an appliance e g ...

Страница 12: ...the Water Valve Control disconnect the tape then press the WATER OFF button to mute the alarm 2 Identify where in the property the leak has occurred 3 If you have wireless leak detector transmitters installed the one that has instigated the alarm will be beeping If none of the Transmitters are beeping but you have a leak detection tape or tab directly connected to the Water Valve Control then this...

Отзывы: