ES2-3DA2306 Vector Easy Servo Drive User Manual
The tolerance for position following error, if the error is over this value of setting, drive will display
ERR20 .
NO. in Protuner
NO. on HMI panel
Lock
Shaft
Current
Percentage( power on)
Range
unit
default
30007
10
1—100
0.1A
40
The current uses for locking the motor shaft when, it is effective only when NO.30015 in ProTnuer is set to
3or 4. And if the parameter No.24 in ProTuner is set to 0 (Open-loop), this current will be peak current for
motor.
NO. in Protuner
NO. on HMI panel
Soft Start Time(power on)
Range
unit
default
30006
12
1—30
100ms
8
The time for output current increasing from 0 to Maximum. if the motor with load, it need a suitable time
setting to find a balance point to reduce vibration when power on or motor enable.
NO. in Protuner
NO. on HMI panel
Command Pulse Filter
Time
Range
unit
default
3001
14
0—600
0.05ms
30
Smoothing the command pulse, higher value will reduce the vibration when the motor is beginning run and
increase the largest motor startup frequency.
NO. in Protuner
NO. on HMI panel
Motor model
Range
unit
default
59
42
0--100
11
11: ES-MH33480
12: ES-MH334100
13: ES-MH334120
Set correctly codebase on the motor model you are using. Not to be recommended connecting other motors.
NO. in Protuner
NO. on HMI panel
Speed loop Kp in high
speed
Range
unit default
134
45
0—10000
-
700
If the motor needs to run up to 1000RPM, Set a value as large as possible base on the machine without
shout.
NO. in Protuner
NO. on HMI panel
Motion model
Range
unit
default
30015
50
0--9
0
0-3
:
interpolation motion
4-5
:
point to point motion
This parameter setting depend on the application, if it is used for interpolation application, such as
engraving, laser cutting, milling, and so on, it can be set 0-3; if used for point to point application, like
SCARA arm or STM, it can be set 4-5.