CS3E-E Series EtherCAT Closed Loop stepper drive User Manual
31
0x819
0x8212
No valid output data
0x81c
0x821C
Invalid sync manager type
0x81d
0x821D
Invalid output configuration
0x81e
0x821E
Invalid input configuration
0x821
0xA003
Waiting for the initial state of ESM
0x822
0xA004
Waiting for ESM pre-operation state
0x823
0xA005
Waiting for ESM safe operation status
0x824
0x8224
Invalid process data input mapping
0x825
0x8225
Invalid process data output mapping
0x827
0x8727
Free running mode is not supported
0x828
0x8728
Does not support synchronous mode
0x82b
0x8210
Invalid input and output
0x82c
0x872C
Fatal sync error
0x82d
0x872D
No synchronization errors
0x82e
0x872E
Synchronization period is too small
0x830
0x8730
Invalid
DC
synchronization
configuration
0x832
0x8732
DC phase locked loop failure
0x833
0x8733
DC sync IO error
0x834
0x8734
DC synchronization timeout
0x835
0x8735
Invalid DC cycle
0x850
0x5550
EEPROM inaccessible
0x851
0x5551
EEPROM error
0x852
0x5552
The hardware is not ready
5.2 Alarm LED
As shown in the figure below, there are two red alarm indicator lights. ALM usually shows the drive motion
alarms ,and ERR shows the drive communication alarms.
ALM red light alarm indication table:
ALM
flicker
number
Description
Error code in
0x603F
Trouble Shooting
1
Over-current
0x2211
1. Check whether the wiring is short-circuited,or the motor is short-circuited.
2. Switch power supply alarm caused,replace other power supply for a try.
2
Over-voltage
0x3211
1. Check the voltage of power supply;
2. If over-voltage occurs in motion, the acceleration and deceleration time can
be increased
4
Shaft
locking
error
0x7323
1.Check whether the motor wire is not connected
2.Check whether motor wiring is incorrect
5
Save
parameter
error
0x5530
1. Reset parameters to the factory and restart power supply
2. If it still exists,the hardware failure